Mitsubishi Electric PUHZ-SW75VHA Service Manual page 62

Water heat pump
Hide thumbs Also See for PUHZ-SW75VHA:
Table of Contents
SW2 setting
LEV-A opening pulse on error occurring
0 – 480
ON
1
2 3 4 5 6
Indoor room temperature (TH1) on error
occurring
ON
8 – 39
1
2 3 4 5 6
Indoor pipe temperature / Liquid (TH2)
on error occurring
ON
-39 – 88
1
2 3 4 5 6
Pressure saturation temperature (T
on error occurring
ON
1
2 3 4 5 6
2-phase pipe (TH6) on error occurring
-39 – 88
ON
1
2 3 4 5 6
Ambient temperature (TH7) on error
occurring
ON
-39 – 88
1
2 3 4 5 6
Outdoor heatsink temperature (TH8) on
error occurring
-40 – 200
ON
1
2 3 4 5 6
OCH533A
Display detail
63HS
The black square ( ) indicates a switch position.
Explanation for display
0 – 480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 130 pulse;
0.5 secs.
8 – 39
-39 – 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs.
)
-39 – 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs.
-39 – 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs.
-39 – 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs.
-40 – 200
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
62
0.5secs.
2 secs.
1
30
0.5secs.
2 secs.
15
0.5secs.
2 secs.
15
0.5secs.
2 secs.
15
0.5secs.
2 secs.
15
Unit
Pulse
:
:
:
:
:
:
Table of Contents