5. TROUBLESHOOTING

If the UPS system does not operate correctly, please attempt to solve the problem using the table
below.
Problem
No indication, no warning
tone even though system
is connected to mains
power supply
LINE LED blinks
LINE-LED blinks and
BATTERY-LED lights up
LINE and BYPASS LED
light up even though the
power supply is available
INVERTER LED lights
up, warning tone at
intervals (every 1 or 4
seconds)
FAULT LED lights,
warning tone once a
second
FAULT-LED lights up,
permanent warning tone
Emergency supply
period shorter than
nominal value
Please have the following information at hand before calling the After-Sales Service Department:
1. Model number, serial number
2. Date on which the problem occurred
3. Detailed description of the problem
Possible cause
No input voltage
Phase and neutral
conductor at input of UPS
system are reversed
Input power and/or
frequency are out of
tolerance
Inverter not switched on
Mains power supply has
failed
Overload
UPS-mistake
Batteries not fully charged /
batteries defective
---8---
Remedy
Check building wiring socket outlet,
check input cable
Connect UPS system according to
chapter 4
Check input power source and inform
dealer if necessary
Press On button " I "
Not necessary, battery operation;
warning tone at intervals of 1 second
means battery is almost empty
Reduce number of users at UPS
output
Notify dealer !!
Charge the batteries for at least 1 - 2
hours. Check capacity. If the problem
still persists, consult your dealer