2.6 Initial Download to I/O Modules

2.6.1 Update Terminal Boards

Prerequisites

Successfully online with the associated controller set
All I/O modules have been correctly added to the ToolboxST system
Correctly connected IONet cables to all the I/O modules
I/O modules are powered on
Complete this procedure to detect the terminal board barcodes.
➢ ➢ To update terminal boards online
If not already online, then from the Component Editor toolbar click the Go On/Offline icon to go online with the
1.
ToolboxST application.
2.
Have available or create a written record of all installed terminal boards.
Enable the I/O modules for configuration.
3.
a.
From the Component Editor Hardware tab, select all the I/O modules.
b. From the Property Editor, under Configuration, Required, select True.
From the Tree View, double-click the I/O module icon to display the Modify dialog box.
4.
From the Bar Code text box, click the ellipsis button to display the Select Unassigned Terminal Board dialog box
5.
with the available terminal boards.
From the dialog box, select the correct Bar Code and click OK.
6.
7.
Read the warning message, then click Yes.
Click OK.
8.
9.
Repeat this procedure for the remaining I/O modules.
10. Verify using the written record that all terminal boards have been identified by the ToolboxST application.
2.6.2 Initial Download to I/O Modules
➢ ➢ To perform an initial download
If using Shared IONet, save and close both Component Editors. From the System Editor Tree View, select the Shared
1.
IONet Group. Right-click and select Download Shared IONet, then complete the wizard. Go to step 4.
From the Component Editor, click Build.
2.
Click Download and complete the wizard using the default settings.
3.
4.
Cycle power to the panel. Wait for all equipment to power on with correct status LEDs.
5.
Click to go online.
Wait and reset any alarms, if needed.
6.
7.
Build and Download again, if needed.
8.
Wait and reset any alarms, if needed.
Select the Component InfoView Status tab.
9.
38
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II