Mitsubishi Electric PURY-P72 Service Handbook page 243

Hide thumbs Also See for PURY-P72:
Table of Contents
[ IX Troubleshooting ]
1. Error Code
6607
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans-
mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide
the response (ACK).
3. System configuration
(1) System with one outdoor unit
Error
Error dis-
source
play
address
Outdoor
M-NET
No ac-
unit (OC)
remote
knowl-
controller
edgement
(RC)
(ACK) at
MA re-
IC trans-
mote con-
mission to
troller
OC
(MA)
BC con-
M-NET
No ac-
troller
remote
knowl-
(BC)
controller
edgement
(RC)
(ACK) at
MA re-
IC trans-
mote con-
mission to
troller
BC
(MA)
Indoor
M-NET
No ac-
unit (IC)
remote
knowl-
controller
edgement
(RC)
(ACK) at
MA re-
RC trans-
mote con-
mission to
troller
IC
(MA)
LOSS-
M-NET
No ac-
NAY
remote
knowl-
(LC)
controller
edgement
(RC)
(ACK) at
MA re-
IC trans-
mote con-
mission to
troller
LC
(MA)
M-NET
M-NET
No ac-
remote
remote
knowl-
control-
controller
edgement
ler (RC)
(RC)
(ACK) at
MA re-
IC trans-
mote con-
mission to
troller
RC
(MA)
HWE0803A
Detection
method
(1)
Contact failure of transmission line of OC or IC
(2)
Decrease of transmission line voltage/signal by ex-
ceeding acceptable range of transmission wiring.
Farthest:200 m [656ft] or less
Remote controller wiring:
10m [32ft] or less
(3)
Erroneous sizing of transmission line (Not within the
range below). Wire diameter:
2
1.25mm
[AWG16] or more
(4)
Indoor unit control board failure
(1)
When BC controller address is changed or modified
during operation.
(2)
Faulty or disconnected transmission wiring of BC
controller
(3)
Disconnected connector of BC controller (CN02)
(4)
Faulty control board of BC controller
(1)
When IC unit address is changed or modified during
operation.
(2)
Faulty or disconnected IC transmission wiring
(3)
Disconnected IC connector
(CN2M)
(4)
Indoor unit controller failure
(5)
M-NET remote controller failure
(1)
The power source of LOSSNAY has been shut off.
(2)
When the address of LOSSNAY is changed in the
middle of the operation
(3)
Faulty or disconnected transmission wiring of
LOSSNAY
(4)
Disconnected connector (CN1) on LOSSNAY
(5)
Controller failure of LOSSNAY
(1)
Faulty transmission wiring at IC unit side.
(2)
Faulty wiring of the transmission line for M-NET re-
mote controller
(3)
When the address of M-NET remote controller is
changed in the middle of the operation
(4)
M-NET remote controller failure
Cause
- 234 -
Check method and remedy
Turn off the power
source of the outdoor
unit, and turn it on again.
If the error is accidental,
it will run normally. If not,
check the causes (1) -
(4).
Turn off the outdoor/in-
door units for 5 or more
minutes, and turn them
on again.
If the error is accidental,
they will run normally. If
not, check the causes
(1) - (4).
Turn off the outdoor/in-
door units for 5 or more
minutes, and turn them
on again.
If the error is accidental,
they will run normally.
If not, check the causes
(1) - (5).
Turn off the power
source of LOSSNAY
and turn it on again.
If the error is accidental,
it will run normally.
If not, check the causes
(1) - (5).
Turn off the power
source of the outdoor
unit for 5 minutes or
more, and turn it on
again.
If the error is accidental,
it will run normally.
If not, check the causes
(1) - (4).
GB
Table of Contents
loading

Table of Contents