Mitsubishi Electric PURY-P72 Service Handbook page 175

Hide thumbs Also See for PURY-P72:
Table of Contents
[ VIII Test Run Mode ]
Model name of BC controller
Ambient
tempera-
ture
Indoor unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
ing
BC controller (1/2/3)
High pressure(63HS1)/
Low pressure(63LS)
Pressure
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
Outdoor
unit
Temp. of
each sec-
tion
Indoor unit
HWE0803A
Operation
Indoor
DB/WB
Outdoor
No. of connected units
No. of units in operation
Model
Main pipe
Branch pipe
Total pipe length
[lbs-oz]
Pulse
Discharge (TH4)
Heat exchanger outlet
(TH6)
Accumulator inlet
Accumulator outlet
Compressor inlet
Compressor shell bottom
LEV inlet
Heat exchanger inlet
- 166 -
Outdoor unit model
PURY-P120THMU-A
CMB-P104NU-G
21.1°C/-
[70°F/-]
8.3°C/6.1°C
[47°F/43°F]
4
Unit
4
-
30/30/30/30
5 [16-3/8"]
m
10 [32-3/4"]
[ft]
45 [147-5/8"]
-
Hi
kg
22.5 [50]
A
28.3
V
230
Hz
81
295/295/295/295
110/-/660
2.57/0.64
[372/92]
MPa
[psi]
2.54/2.22
[368/321]
73 [163]
2 [36]
-1 [30]
°C
-1 [30]
[°F]
-1 [30]
40 [104]
28 [82]
67 [153]
GB