Types Of Switch Setting And Address Setting - Mitsubishi Electric PURY-P200 Service Handbook

City multi r410a
Table of Contents

[2] Types of Switch Setting and Address Setting

1. Switch setting
Type and method of switch setting
Switch setting vary depending on the system configuration. Make sure to read "[3] Examples of system connection"
before conducting electrical work. Turn off the power before setting the switch. Operating the switch while the unit is
being powered will not change the setting, and the unit will not properly function.
2. Address setting
(1)
Address
setting varies depending on the system configuration. See "[3] Examples of system connection"
section for details.
Unit or controller
Indoor unit
Main/sub units
Lossnay
M-NET
Main remote controller
remote
controller
Sub remote controller
MA remote controller
Outdoor unit
Auxiliary
Hex. unit
units
BC controller (Main)
BC controller (Sub)
System
Group remote controller
controller
System remote controller
ON/OFF remote controller
Schedule timer (for M-NET)
Centralized controller
(Note 5)
LM adapter
Notes:
1. Address setting is not required for a single refrigerant system (with a few exception).
2. When setting M-NET remote controller address to "200," make it "00."
3. When setting the outdoor unit and outdoor auxiliary unit address to "100," make it "50."
4. When an address in a system overlapped with the outdoor unit or BC controller (Main) address of other refrigerant system,
choose an another address within theset range that is not in use (with a few exceptions).
5. When controlling the K-control units;
(1) A K-transmission converter (Model name: PAC-SC25KA) is required. To set the address for the K-transmission converter,
set it to thelowest address of the K-control unit to be controlled + 200.
(2) Set the address of the system controller (G-50A) to "0." The K-control unit can only be controlled by the system controller
with theaddress "0."
(3) To control both K-control unit and M-NET model unit, make the address of the K-control unit larger than that of the indoor
unit of M-NET model.
Group-register on the system controller so that the group No. and the lowest address of the K-controlled indoor units
belonging to thegroup will be identical.
Address
Symbol
setting range
Assign the smallest address to the indoor unit to
IC
0, 01~50
become the main unit within the same group, and
(Note 1)
then use sequential numbers to assign an address
to all the indoor units in the group. (Note 5)
If applicable, set the sub BC controllers in an R2
system in the following order:
Set the address so that (1) < (2) < (3)
LC
Assign any unused address after setting all indoor units.
RC
101~150
Set to the lowest address of the indoor main unit
within the same group + 100.
RC
151~200
Set to the lowest address of the indoor main unit
within the same group + 150.
(Note 2)
MA
No address setting required. (When operating with 2 remote controllers,
the main/sub selector switch must be set.
OC
0, 51~100
Use the address that equals the sum of the smallest indoor
(Note 1, 3, 4)
unit address in the same refrigerant system and 50.
OS
52~100
Use the address that equals the sum of the address of the
(Note 3, 4)
outdoor unit in the same refrigerant system and 1.
BC
Use the address that equals the sum of the smallest
BS
address of the indoor unit out of all the indoor units
that are connected to the BC controller and 50.
When a sub BC controller is connected, the automatic
start up function will not be available.
GR, SC
201~250
Set to the lowest No. of the group to be controlled + "200."
SR, SC
201~250
Choose any number within the range of addresses shown left.
AN, SC
201~250
Set to the lowest No. of the group desired tobe controlled + "200."
ST, SC
201~250
Choose any number within the range of addresses shown left.
TR, SC
0, 201~250
Choose any number within the range of addresses shown left.
However when using with the upper SC setting, or wishing to
control the k-control units, set to "0."
SC
201~250
Choose any number within the range of ad-dresses shown left.
- 19 -
Setting method
(1) Indoor unit to be connected to the main BC controller
(2) Indoor unit to be connected to No.1 sub BC controller
(3) Indoor unit to be connected to No.2 sub BC controller
Factory
setting
00
00
101
Main
00
201
201
201
202
000
247
Table of Contents
loading

Table of Contents