[ VII Control ]
2. Function of the switch (Indoor unit)
(1) Dipswitches
1) SW1,3
Switch
Function
Room temperature
1
detection position
2
Clogged filter detection
3
Filter check reminder time setting
4
Outside air intake
Remote display option
5
SW1
Humidifier control
6
Fan speed setting for
7
Heating Thermo-OFF
Fan speed setting for
8
Heating Thermo-OFF
9
Self-recovery after power failure
10
Power source start-stop
1
Unit model selection
2
Louver
3
Vane
4
Vane swing function
5
-
Vane angle limit setting
6
SW3
for cooling operation
Raises supply air
7
temperature in heating mode
Heating 4°C [7.2°F] up
8
Precooling standby
9
Preheating standby end
10
conditions
Note 1. Settings in the shaded areas are factory settings.(Refer to the table below for the factory setting of the switches whose factory settings are not indicated by the shaded cells.)
Note 2. If both SW1-7 and SW1-8 are set to ON, the fan remains stopped during heating Thermo-OFF.
To prevent incorrect temperature detection due to a build-up of warm air around the indoor unit, use the built-in temperature sensor on the remote controller (SW1-1)
instead of the one on the indoor unit inlet thermistor.
Note 3. By setting SW3-1, SW1-7, and SW1-8 to a certain configuration, the fan can be set to remain stopped during cooling Thermo-OFF. See the table below for details.
Switch setting
SW3-1
SW1-7 SW1-8
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
ON
2) SW2
Model
P15
P20
Capacity (model) code
3
4
SW2
setting
Note. The setting timing for SW2 is before power is turned on.
HWE1113B
Function according to switch setting
OFF
Indoor unit inlet
Not available
100h
Disabled
Fan output
During heating operation
Very Low
According to the
SW1-7 setting
Disabled
Disabled
Heat pump
Not available
Not available
Not available
-
Downblow B,C
OFF
Enabled
OFF
Water inlet temp. ≥ 35°C
or 5 minutes have elapsed
after starting operation
Fan speed during Thermo-OFF
Cooling-only/heat pump
Heating
Cooling
Very Low
Low
Heat pump
Preset speed
Preset speed
Stop
-
Preset speed
Cooling-only
-
-
Stop
Stop
Stop
Heat pump
P25
P32
P40
P50
5
6
8
10
Switch setting timing
ON
OFF
Built-in sensor on
the remote controller
Available
2500h
Enabled
Thermo-ON signal
Always on while in the heating mode
Low
Preset speed
Enabled
While the unit is stopped
Enabled
(Remote controller OFF)
Cooling only
Available
Available
Available
-
Horizontal
ON
Disabled
ON
Water inlet temp. ≥ 35°C
or 10 minutes have elapsed
after starting operation
P63
P71
P80
13
14
16
- 92 -
Notes
ON
Set to OFF on floor-standing
(PFFY) type units
P100
P125
P140
P200
20
25
28
40
P250
50
GB