Siemens 2200 Series Installation Instructions

Siemens 2200 Series Installation Instructions

Relative humidity and temperature room units for apogee controllers

Quick Links

Series 2200 Relative Humidity and
Temperature Room Units For
APOGEE® Controllers

Product Description

These room units measure relative humidity and
temperature in the occupied space in which they are
installed. Models with display allow users to view the
measured temperature value. A version with
temperature setpoint adjustment is also offered.
These devices are intended for use with appropriate
signal input on an APOGEE Controller. The effective
sensing range is 32°F to 122°F (0°C to 50°C), and
the setpoint range is 55°F to 95°F (13°C to 35°C).
These room units can be mounted on electrical
boxes, stud-type mounting brackets, or drywall.
Obtain the necessary mounting hardware and follow
the appropriate mounting procedures for the type of
installation required.
Product Numbers
QFA3212.FWSN
QFA3212.EWSN
Accessories
AQA2200-INTL
Room Unit Back Plate
(10-pack)
AQA2200-2X4
Room Unit Back Plate
(Single)
563-102 GSKT Kit
Room Sensor Insulating
Gasket (10-pack)
(For hollow wall installations)
NOTE: If installing the Back Plate, discard the
metric screws provided with the Back Plate
and utilize the Room Unit mounting screws.
Caution Notations
CAUTION
Item Number 129-104, Rev. HA
QFA32SS.FWSN
QFA32SS.EWSN
Equipment damage or loss of
data may occur if you do not
follow a procedure as
specified.
Installation Instructions
Expected Installation Time
20 minutes
Required Tools
Sizes 1 and 2 Phillips screwdrivers
Small and medium flat-blade screwdrivers
1/16-inch hex key
Medium-duty electric drill
3/16-inch (4.8 mm) drill bit
One-inch (25 mm) hole saw
Small level
Tape measure
Marker or pencil
Prerequisites
Review these instructions before beginning.
Installed: appropriate field wiring within the
maximum wiring run length for the individual
equipment controller. The maximum
recommended length is 750 feet (229 m) for
18 AWG; 300 feet (91 m) for 22 AWG.
All wiring must comply with National Electric
Code (NEC) and local regulations.
Figure 1. Typical Temperature Room Unit.
Document No. 129-104
October 1, 2013
Page 1 of 5
loading

Summary of Contents for Siemens 2200 Series

  • Page 1: Product Description

    Installation Instructions Document No. 129-104 October 1, 2013 Series 2200 Relative Humidity and Temperature Room Units For APOGEE® Controllers Expected Installation Time Product Description 20 minutes These room units measure relative humidity and temperature in the occupied space in which they are Required Tools installed.
  • Page 2: Mounting Information

    Base. The Sensor Base has an UP arrow molded into the surface in the same quadrant location (see Figure 6). NOTE: See Figure 2 for details on optional Gasket application. Figure 3. Drywall Mounting (No Rough-in), Typical. Page 2 of 5 Siemens Industry, Inc.
  • Page 3: Sensor Setup

    Document No. 129-104 Installation Instructions October 1, 2013 7. Terminate the wires to the termination blocks on the ° ° room unit's base plate. (See Figure 6.) 8. Feed the extra cable back through the hole. Sensor Set-up R64 Resistor (°F/°C Selector) Jumper Voltage/Current...
  • Page 4 MEC, PXM, LON TEC and PPM. These require the earth ground wire to The installation is now complete. be connected to the controller as shown in Figure 8. Page 4 of 5 Siemens Industry, Inc.
  • Page 5 Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. APOGEE is a registered trademark or Siemens Industry, Inc. Other product or company names mentioned herein may be the trademarks of their respective owners.