Mitsubishi Electric PURY-P72 Service Handbook page 188

Hide thumbs Also See for PURY-P72:
Table of Contents
[ VIII Test Run Mode ]
(2) Heating only operation
Model name of BC controller
Ambient
tempera-
ture
Indoor unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
ing
BC controller (1/2/3)
High pressure(63HS1)/
Low pressure(63LS)
Pressure
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
Outdoor
unit
Temp. of
each sec-
tion
Indoor unit
HWE09130
Operation
Indoor
DB/WB
Outdoor
No. of connected units
No. of units in operation
Model
Main pipe
Branch pipe
Total pipe length
[lbs-oz]
Pulse
Discharge (TH4)
Heat exchanger outlet
(TH6)
Accumulator inlet
Accumulator outlet
Compressor inlet
Compressor shell bottom
LEV inlet
Heat exchanger inlet
- 179 -
Outdoor unit model
PURY-P72TJMU-A
CMB-P104NU-G
21.1°C/í
[70 °F/-]
8.3°C/6.1°C
[47 °F/43 °F]
3
Unit
3
-
24/24/24
5 [16-3/8"]
m
10 [32-3/4"]
[ft]
35
[114-13/16"]
-
Hi
kg
19.1 [42]
A
17.1
V
230
Hz
52
205/203/200
110/í/520
2.52/0.7
[365/102]
MPa
[psi]
2.45/2.13
[355/309]
68 [154]
2 [36]
1 [34]
°C
1 [34]
[°F]
1 [34]
40 [104]
30 [86]
62 [144]
PURY-P96TJMU-A
CMB-P104NU-G
21.1°C/í
[70 °F/-]
8.3°C/6.1°C
[47 °F/43 °F]
2
2
48/48
5 [16-3/8"]
10 [32-3/4"]
25 [82]
Hi
21.3 [47]
24.1
230
74
406/406
110/í/590
2.52/0.63
[365/91]
2.48/2.27
[360/329]
78 [172]
0 [32]
-2 [28]
-3 [27]
-3 [27]
40 [104]
36 [97]
68 [154]
GB