System With A Connection Of System Controller To Indoor-Outdoor Transmission Line - Mitsubishi Electric PURY-HP72 Service Handbook

R410a
Hide thumbs Also See for PURY-HP72:
Table of Contents
[2-7 Example System with an MA Remote Controller ]
2-7-5
System with a Connection of System Controller to Indoor-Outdoor
Transmission Line
(1) Sample control wiring
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
OS
52
TB3
M1
M2
TB7
M1
M2
S
Not
Connect
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
OS
56
TB3
M1
M2
TB7
M1
M2
S
Not
Connect
(2) Cautions
1)
ME remote controller and MA remote controller cannot both be con-
nected to the same group of indoor units.
2)
No more than 2 MA remote controllers can be connected to a group
of indoor units. It is not possible to connect a pair of PAR-30MAAU.
3)
Do not connect the terminal blocks (TB5) on the indoor units that are
connected to different outdoor units with each other.
4)
Replacement of male power jumper connector (CN41) must be per-
formed only on one of the outdoor units.
5)
Provide grounding to S terminal on the terminal block for transmis-
sion line for centralized control (TB7) on only one of the outdoor
units.
6)
A maximum of 3 system controllers can be connected to the indoor-
outdoor transmission line, with the exception that only one G(B)-50A
may be connected.
7)
When the total number of indoor units exceeds 20 (12 if one or more
indoor units of the 72 model or above is connected), it may not be
possible to connect a system controller to the indoor-outdoor trans-
mission line.
8)
When the number of the connected indoor units is as shown in the
table below, one or more transmission boosters (sold separately)
are required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that are
listed in the specifications for each outdoor unit.)
HWE13080
L11
CN41 CN40 Replace
SW5-1 OFF ON
OC
BC
51
53
TB3
TB02
M1
M2
S
M1
M2
TB7
M1
M2
S
Connect
L21
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
OC
BC
55
57
TB3
TB02
M1
M2
M1
M2
S
TB7
M1
M2
S
Not
Note1
Connect
System controller
A B S
Interlock operation with
the ventilation unit
L12
Group
Group
IC
IC
01
02
TB5
TB15
TB5
TB15
M1
M2
S
1 2
M1
M2
S
1 2
A
B
A
B
1
2
1
2
MA
MA
L22
Group
Group
IC
IC
04
05
TB5
TB5
TB15
TB15
M1
M2
S
1 2
M1
M2
S
1 2
A
B
1
2
MA
m3
Note1 LM adapters cannot be connected to the
indoor-outdoor transmission line.
When the P72 and P96 models are not
included in the connected indoor units
When the P72 and P96 models are in-
cluded in the connected indoor units
The table above shows the number of transmission boosters that is
required by the system with three BC controllers. For each BC con-
troller that is subtracted from the above-mentioned system, two ad-
ditional indoor units can be connected.
Refer to the DATABOOK for further information about how many
booster units are required for a given system.
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Maximum distance (1.25mm
L11+L12 200m [656ft]
L21+L22 200m [656ft]
L25 200m [656ft]
2) Transmission line for centralized control
L31+L21 200m [656ft]
3) MA remote controller wiring
Same as 2-7-1
4) Maximum line distance via outdoor unit
2
(1.25mm
[AWG16] or larger)
L25+L31+L12(L11) 500m [1640ft]
L12(L11)+L31+L22(L21) 500m [1640ft]
- 40 -
Group
LC
IC
03
07
TB5
TB15
TB5
M1
M2
S
1 2
M1
M2
S
A
B
1
2
MA
LC
IC
06
08
TB5
TB5
TB15
M1
M2
S
1 2
M1
M2
S
A
B
1
2
MA
Number of transmission boost-
er (sold separately) required
1 unit
27 - 50 units
21 - 39 units
40 - 50 units
2
[AWG16] or larger)
2 units
-
GB
Table of Contents
loading

Table of Contents