Simple Check On Inverter Circuit Components; Troubleshooting Problems With Igbt Module - Mitsubishi Electric PURY-HP72 Service Handbook

R410a
Hide thumbs Also See for PURY-HP72:
Table of Contents
[8-11 Troubleshooting Inverter Problems (YKMU) ]
8-11-13

Simple Check on Inverter Circuit Components

Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that
the voltage between FT-P and FT-N on INV Board has dropped to DC20V or less.
Part name
IGBT module
Refer to the following page(s). [8-11-14 Troubleshooting Problems with IGBT Module](page 305)
Rush current pro-
Measure the resistance between terminals R1 and R5: 22 Ω±10%
tection resistor
R1, R5
Electromagnetic
relay
72C
DC reactor DCL
Measure the resistance between terminals: 1Ω or lower (almost 0 Ω)
Measure the resistance between terminals and the chassis: ∞
8-11-14

Troubleshooting Problems with IGBT Module

Measure the resistances between each pair of terminals on the IGBT with a tester, and use the results for troubleshooting.
The terminals on the INV board are used for the measurement.
1) Notes on measurement
Check the polarity before measuring. (On the tester, black normally indicates plus.)
Check that the resistance is not open (∞ Ω) or not shorted (to 0 Ω).
The values are for reference, and the margin of errors is allowed.
The result that is more than double or half of the result that is measured at the same measurement point is not allowed.
Disconnect all the wiring connected the INV board, and make the measurement.
2) Tester restriction
Use the tester whose internal electrical power source is 1.5V or greater
Use the dry-battery-powered tester.
(The accurate diode-specific resistance cannot be measured with the button-battery-powered card tester, as the applied volt-
age is low.)
Use a low-range tester if possible. A more accurate resistance can be measured.
HWE13080
This electromagnetic relay is rated at DC12V and is driven by a coil.
Check the resistance between terminals
Upper
1
2
3
4
Installation
direction
6
5
Judgment method
Check point
Coil
Between Terminals 5 and 6
Between Terminals 1 and 2
Contact
Between Terminals 3 and 4
- 305 -
Checking criteria( )
W
Not to be short-circuited
(Center value 75 ohm)
GB
Table of Contents
loading

Table of Contents