Error Codes [5104, 5105, 5106, 5107, 5109, 5111] - Mitsubishi Electric PURY-HP72 Service Handbook

R410a
Hide thumbs Also See for PURY-HP72:
Table of Contents
[7-7 Error Code Definitions and Solutions: Codes [5000 - 5999] ]
7-7-2

Error Codes [5104, 5105, 5106, 5107, 5109, 5111]

1. Error code definition
5104
Discharge temperature sensor (TH4) fault (Outdoor unit)
5105
Accumulator inlet temperature sensor (TH5) fault (Outdoor unit)
5106
Heat exchanger inlet temperature sensor (TH6) fault (Outdoor unit)
5107
Outside temperature sensor (TH7) fault (Outdoor unit)
5109
ON-defrost temperature sensor (TH9) error (outdoor unit)
5111
ON-defrost temperature sensor (TH11) error (outdoor unit)
2. Error definition and error detection method
When a short (high temperature intake) or an open (low temperature intake) of the thermistor is detected (the first detection),
the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts when the detected temperature of the thermistor.
When a short or an open is detected again (the second detection) after the first restart of the outdoor unit, the outdoor unit
stops, turns to anti-restart mode for 3 minutes, and restarts in 3 minutes when the detected temperature is within the normal
range.
When a short or an open is detected again (the third detection) after the previous restart of the outdoor unit, the outdoor unit
makes an error stop.
If a short- or open-circuited thermistor is detected immediately before restart, the unit comes to an abnormal stop, and an
error code "5104""5105,""5106,""5107," "5109," or "5111" will appear on the display.
During 3-minute antirestart mode, preliminary errors will be displayed on the LED display.
A short or an open described above is not detected for 10 minutes after the compressor start, during defrost mode, or for 3
minutes after defrost mode.
3. Cause, check method and remedy
Cause
(1)
Thermistor failure
(2)
Pinched lead wire
(3)
Torn wire coating
(4)
A pin on the male connector is missing or
contact failure
(5)
Disconnected wire
(6)
Thermistor input circuit failure on the control
board
TH4
240°C [464°F] and above (0.57kΩ and below)
TH5
70°C [158°F] and above (0.4kΩ and below)
TH6
70°C [158°F] and above (1.14kΩ and below)
TH7
110°C [230°F] and above (0.4kΩ and below)
TH9
110°C [230°F] and above (0.4kΩ and below)
TH11 110°C [230°F] and above (0.4kΩ and below)
HWE13080
Short detection
Check method and remedy
Check thermistor resistance.
Check for pinched lead wire.
Check for wire coating.
Check connector.
Check for wire.
Check the intake temperature of the sensor with the LED
monitor.
When the temperature is far different from the actual temper-
ature, replace the control board.
Open detection
0°C [32°F] and below (698kΩ and above)
-40°C [-40°F] and below (130kΩ and above)
-40°C [-40°F] and below (130kΩ and above)
-40°C [-40°F] and below (130kΩ and above)
-40°C [-40°F] and below (130kΩ and above)
-40°C [-40°F] and below (130kΩ and above)
- 211 -