Error Code [4106]; Error Code [4109] - Mitsubishi Electric PURY-HP72 Service Handbook

R410a
Hide thumbs Also See for PURY-HP72:
Table of Contents
[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
7-6-3

Error Code [4106]

1. Error code definition
2. Error definition and error detection method
Transmission power output failure
3. Cause
1) Wiring failure
2) Transmission power supply cannot output voltage because overcurrent was detected.
3) Voltage cannot be output due to transmission power supply problem.
4) Transmission voltage detection circuit failure
4. Check method and remedy
Check the transmission power supply circuit on all outdoor units in a given refrigerant circuit for problems.
[8-12-2 Troubleshooting Problems with Outdoor Unit Transmission Power Supply Circuit](page 308)
[8-13-2 Troubleshooting Problems with Outdoor Unit Transmission Power Supply Circuit](page 310)
1. Error code definition
2.
Error definition and error detection method
Transmission power reception failure
3.
Cause
One of the outdoor units stopped supplying power, but no other outdoor units start supplying power.
4.
Check method and remedy
Check the transmission power supply circuit on all outdoor units in a given refrigerant circuit for problems.
[8-12-2 Troubleshooting Problems with Outdoor Unit Transmission Power Supply Circuit](page 308)
[8-13-2 Troubleshooting Problems with Outdoor Unit Transmission Power Supply Circuit](page 310)
7-6-4

Error Code [4109]

1. Error code definition
Indoor unit fan operation error
2. Error definition and error detection method
1) Connector CN28 has remained open-circuited for 100 consecutive secondsduring operation.
3. Cause, check method and remedy
(1)
Auxiliary relay (X13) fault
(2)
Connector (CN28) is disconnected.
(3)
Blown fuse
(4)
Motor error (thermistor error inside the motor)
HWE13080
Cause
Check method and remedy
The coil or the wiring of the auxiliary relay connected to
CN28 is faulty.
Check the connector for proper connection.
Check the fuse on the control circuit board.
Check the unit fan for proper operation in the test run
mode.
If no problems are found with items 1 through 3 above and
the fan does not operate, replace the motor.
- 194 -