Mitsubishi Electric PURY-P72 Service Handbook page 336

Hide thumbs Also See for PURY-P72:
Table of Contents
[ IX Troubleshooting ]
[YKMU-A]
(3) Trouble treatment when the main power breaker is tripped
Items to be checked
[1]
Check the breaker capacity.
[2]
Perform Meg check between the
terminals on the power terminal
block TB1.
[3]
Turn on the power again and
check again.
[4]
Turn on the outdoor unit and check
that it operates normally.
(4) Trouble treatment when the main power earth leakage breaker is tripped
Items to be checked
[1]
Check the earth leakage breaker
capacity and the sensitivity cur-
rent.
[2]
Check the resistance at the power
supply terminal block with a meg-
ger.
[3]
Disconnect the compressor wir-
ings and check the resistance of
the compressor with a megger.
[4]
Disconnect the fan motor wirings
and check the resistance of the fan
motor with a megger.
The insulation resistance could go down to close to 1 M after installation or when the power is kept off for an extended period
of time because of the accumulation of refrigerant in the compressor. If the earth leakage breaker is triggered, please use the
following procedure to take care of this.
ŒDisconnect the wires from the compressor's terminal block.
ŒIf the resistance is less than 1 M , switch on the power for the outdoor unit with the wires still disconnected.
ŒLeave the power on for at least 12 hours.
ŒCheck that the resistance has recovered to 1 M or greater.
Earth leakage current measurement method
ŒFor easy on-site measurement of the earth leakage current, enable the filter with a measurement instrument that has filter
functions as below, clamp all the power supply wires, and measure.
Recommended measurement instrument: CLAMP ON LEAK HiTESTER 3283 made by HIOKI E.E. CORPORATION
ŒWhen measuring one device alone, measure near the device's power supply terminal block.
HWE1116D
Phenomena
Use of a non-specified break-
er
Zero to several ohm, or Meg
failure
1) Main power breaker trip
2) No remote control display
1) Operates normally without
tripping the main breaker.
2) Main power breaker trip
Phenomena
Use of a non-specified earth
leakage breaker
Failure resistance value
Failure compressor if the insu-
lating resistance value is not in
specified range.
Failure when the insulating re-
sistance value is 1 M or less.
Failure fan motor if the insulat-
ing resistance value is not in
specified range.
Failure when the insulating re-
sistance value is 1 M or less.
- 327 -
Remedy
Replace it with a specified breaker.
Check each part and wiring.
*Refer to (5) "Simple checking procedure
for individual components of main inverter
circuit".(page 328)
ŒIGBT module
ŒRush current protection resistor
ŒElectromagnetic relay
ŒDC reactor
a) The wiring may have been short-circuit-
ed. Search for the wire that short-circuit-
ed, and repair it.
b) If item a) above is not the cause of the
problem, refer to (2)-[1]-[6].
Remedy
Replace with a regulation earth leakage
breaker.
Check each part and wiring.
*Refer to (5) "Simple checking procedure
for individual components of main inverter
circuit".(page 328)
ŒIGBT module
ŒRush current protection resistor
ŒElectromagnetic relay
ŒDC reactor
Check that there is no liquid refrigerant in
the compressor. If there is none, replace
the compressor.
Replace the fan motor.
GB
Table of Contents
loading

Table of Contents