[ IX Troubleshooting ]
4102
1. Error Code
4102
(TKMU-A)
Open phase
2. Error definition and error detection method
ŒAn open phase of the power supply was detected at power on.
The open phase of the power supply may not always be detected if a power voltage from another circuit is applied.
3. Cause, check method and remedy
Cause
(1)
Power supply problem
ŒOpen phase voltage of the power supply
ŒPower supply voltage drop
(2)
Noise filter problem
ŒCoil problem
ŒCircuit board failure
(3)
Wiring failure
(4)
Blown fuse
(5)
Control board failure
HWE1116D
Check method and remedy
Check the input voltage to the power supply terminal block TB1.
ŒCheck the coil connections.
ŒCheck for coil burnout.
ŒConfirm that the voltage at the CN001 connector is 188 V or
above.
ŒCheck Noise filter CN110, relay connector CNFG2, and control
board CN110 connector for damage to wire or for incomplete
connection.
ŒCheck Noise filter CN012 and control board CNAC connector.
Check F01 on the control board, F4, and F5 for a blown fuse.
->If a blown fuse is found, check for a short-circuiting or earth fault
of the actuator.
Replace the control board if none of the above is causing the
problem.