Mitsubishi Electric PURY-P72 Service Handbook page 192

Hide thumbs Also See for PURY-P72:
Table of Contents
[ VIII Test Run Mode ]
Model name of BC controller
Ambient
tempera-
ture
Indoor unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
*1
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
ing
BC controller (1/2/3)
High pressure(63HS1)/
Low pressure(63LS)
Pressure
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
Outdoor
unit
Temp. of
each sec-
tion
Indoor unit
*1. Measurements of current and voltage that are listed in the table above are those of the TKMU model.
HWE1116D
Operation
Indoor
DB/WB
Outdoor
No. of connected units
No. of units in operation
Model
Main pipe
Branch pipe
Total pipe length
[lbs-oz]
*1
Pulse
Discharge (TH4)
Heat exchanger outlet
(TH3)
Accumulator inlet
Accumulator outlet
Compressor inlet
Compressor shell bottom
LEV inlet
Heat exchanger inlet
- 183 -
Outdoor unit model
PURY-P240T(Y)SKMU-A
PURY-P120T(Y)KMU-A
CMB-P1013NU-GA
26.7°C/19.4°C [80 °F/67 °F]
35°C/í [95 °F/í]
Unit
-
24/36/36/36/36/36/36
m
[ft]
-
kg
A
V
Hz
75
200/275/275/275/275/275/275
2000/2000/290
2.82/0.94
[409/136]
MPa
[psi]
82 [180]
43 [109]
10 [50]
°C
10 [50]
[°F]
22 [72]
44 [111]
PURY-P120T(Y)KMU-A
7
7
5 [16-3/8"]
10 [32-3/4"]
75 [229-5/8"]
Hi
53.3 [117-8]
57.4
230
75
2.82/0.94
[409/136]
2.73/2.73
[395/395]
82 [180]
43 [109]
10 [50]
10 [50]
22 [72]
44 [111]
22 [72]
13 [55]
GB