Mitsubishi Electric PURY-P72 Service Handbook page 187

Hide thumbs Also See for PURY-P72:
Table of Contents
[ VIII Test Run Mode ]
Model name of BC controller
Ambient
tempera-
ture
Indoor unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
*1
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
ing
BC controller (1/2/3)
High pressure(63HS1)/
Low pressure(63LS)
Pressure
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
Outdoor
unit
Temp. of
each sec-
tion
Indoor unit
*1. Measurements of current and voltage that are listed in the table above are those of the TKMU model.
HWE1116D
Operation
Indoor
DB/WB
Outdoor
No. of connected units
No. of units in operation
Model
Main pipe
Branch pipe
Total pipe length
[lbs-oz]
*1
Pulse
Discharge (TH4)
Heat exchanger inlet
(TH6)
Accumulator inlet
Accumulator outlet
Compressor inlet
Compressor shell bottom
LEV inlet
Heat exchanger inlet
- 178 -
Outdoor unit model
PURY-P120T(Y)KMU-A
CMB-P104NU-G
21.1°C/í
[70 °F/í]
8.3°C/6.1°C
[47 °F/43 °F]
4
Unit
4
-
30/30/30/30
5 [16-3/8"]
m
10 [32-3/4"]
[ft]
45
[147-5/8"]
-
Hi
kg
28.1 [61-15]
A
30.7
V
230
Hz
86
295/295/295/295
110/í/660
2.57/0.64
[372/92]
MPa
[psi]
2.54/2.22
[368/321]
73 [163]
2 [36]
-1 [30]
°C
-1 [30]
[°F]
-1 [30]
40 [104]
28 [82]
67 [153]
PURY-P144T(Y)KMU-A
CMB-P108NU-GA
21.1°C/í
[70 °F/í]
8.3°C/6.1°C
[47 °F/43 °F]
4
4
36/36/36/36
5 [16-3/8"]
10 [32-3/4"]
45
[147-5/8"]
Hi
30.8 [67-14]
36.8
230
107
350/350/350/350
110/110/870
2.52/0.63
[365/91]
2.45/2.13
[355/309]
73 [163]
2 [36]
-1 [30]
-1 [30]
-1 [30]
40 [104]
28 [82]
67 [153]
GB