Mitsubishi Electric PURY-P72 Service Handbook page 138

Hide thumbs Also See for PURY-P72:
Table of Contents
[ VI Refrigerant Circuit ]
3. BC controller
(1) G type
Symbols
Part name
(functions)
Pressure
PS1
sensor
(High pres-
sure side)
PS3
(Intermedi-
ate pres-
sure)
Thermistor
TH11
(Liquid inlet
tempera-
ture)
TH12
(Bypass
outlet tem-
perature)
TH15
(Bypass in-
let tempera-
ture)
TH16
(Liquid re-
frigerant
tempera-
ture)
Solenoid
SVM1
valve
SV A
SV B
SV C
LEV
LEV1
LEV3
HWE1116D
Part
Usage
code
1) Detects high pressure
2) LEV control
1) Detects intermediate
pressure
2) LEV control
LEV control
(Liquid level control)
LEV control (Superheat)
LEV control (Superheat)
LEV control (Subcool)
Opens during cooling and de-
frost modes
Provides refrigerant to indoor
unit in cooling operation
Provides refrigerant to indoor
unit in heating operation
Provides refrigerant to indoor
unit in cooling operation
1) Liquid level control
2) Pressure differential con-
trol
- 129 -
Specifications
Pressure
PS1
0~4.15 MPa [601psi]
Vout 0.5~3.5V
1 2 3
0.071V/0.098 MPa [14psi]
Pressure [MPa]
Con-
=1.38 x Vout [V]-0.69
nector
Pressure [psi]
=(1.38 x Vout [V] - 0.69) x 145
GND (Black)
1
2
Vout (White)
3
Vcc (DC5V) (Red)
R
= 15k
0
R
= 3460
0/80
1
1
R = 15
exp
3460
t
273
0°C[32°F] : 15kohm
10°C[50°F] :9.7kohm
20°C[68°F] :6.4kohm
25°C[77°F] :5.3kohm
30°C[86°F] :4.3kohm
40°C[104°F] :3.1kohm
AC208-230V
Open while being powered/
closed while not being pow-
ered
DC12V
Opening of a valve driven by a
stepping motor
0-2000 pulses
Check method
Continuity
check with a
tester
Same as
indoor LEV
GB