GE DIGITAL ENERGY 1018959 Installation Manual

Snmp / web adapter
Hide thumbs Also See for DIGITAL ENERGY 1018959:

Quick Links

GE Digital Energy
Power Quality
GE Consumer & Industrial SA
General Electric Company
CH – 6595 Riazzino (Locarno)
Switzerland
T +41 (0)91 / 850 51 51
F +41 (0)91 / 850 51 44
www.gedigitalenergy.com
GE imagination at work

Installation Guide

Digital Energy™
SNMP / WEB ADAPTER
P/N 1018959 3-ph SNMP/Web plug-in adapter
P/N 1019070 1-ph SNMP/Web plug-in adapter
P/N 23954 SP SNMP/Web plug-in adapter
P/N 1019071 1-ph SNMP/Web external adapter
Table of Contents
loading

Summary of Contents for GE DIGITAL ENERGY 1018959

  • Page 1: Installation Guide

    SNMP / WEB ADAPTER P/N 1018959 3-ph SNMP/Web plug-in adapter P/N 1019070 1-ph SNMP/Web plug-in adapter P/N 1019071 1-ph SNMP/Web external adapter GE Consumer & Industrial SA General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 51 44 www.gedigitalenergy.com...
  • Page 2 The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE. The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.
  • Page 3 Dear Customer, We thank you for selecting our products and are pleased to count you amongst our very valued customers at GE. We trust that the use of the SNMP/Web adapters for our Uninterruptible Power Supply systems, developed and produced to the highest standards of quality, will give you complete satisfaction.
  • Page 4: Table Of Contents

    Table of contents SAFETY RULES ... 5 WARNINGS AND CAUTIONS ...6 EMC COMPATIBILITY ...8 INTRODUCTION ... 9 CHECKING PACKAGE CONTENTS ...9 OVERVIEW ... 10 FEATURES ... 12 ARCHITECTURE... 12 ADDITIONAL DOCUMENTS... 13 INSTALLATION ... 14 3-PH SNMP/WEB PLUG-IN ADAPTER (P/N 1018959) ... 14 3.1.1 Setting the logical address ...
  • Page 5: Safety Rules

    SAFETY RULES With this document, GE gives to the user all the necessary information about the correct installation of the SNMP/Web adapters. Please read carefully this Installation Manual before installing or operating the adapters. We recommend that this manual be kept next to the UPS for future references.
  • Page 6: Warnings And Cautions

    WARNINGS AND CAUTIONS GENERAL • Always strictly observe the “UPS Safety Rules” • Check carefully the integrity of the equipment. In case you note some visible damage, do not install the equipment but contact the nearest Service Centre. • WARNING: RISK OF ELECTRICAL SHOCK. Do not remove any UPS covers;...
  • Page 7 ENVIRONMENT • Please take care of packaging material: either save it for later use or recycle/dispose in compliance with local and other applicable regulations. • The SNMP/Web adapters contain a removable, Lithium coin-cell battery. Dispose of used batteries in compliance with local and other applicable regulations. WARNING ! The UPS contains hazardous voltages.
  • Page 8: Emc Compatibility

    EMC COMPATIBILITY 1-ph SNMP/Web plug-in adapter (P/N 1019070) 1-ph SNMP/Web external adapter (P/N 1019071) This device has been tested for compliance with the following standards: • EN 61000-6-2 • EN 61000-6-3 NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules.
  • Page 9: Introduction

    INTRODUCTION CHECKING PACKAGE CONTENTS The SNMP/Web adapters are delivered in different kits according to the model. 3-ph SNMP/Web plug-in adapter (P/N 1018959) • 3-ph SNMP/Web plug-in adapter, with pre-installed standard front panel • A front panel designed for LP33 Series UPSs •...
  • Page 10: Overview

    • Third Party License ReadMe • CD-ROM AC adapter Serial cable OVERVIEW 3-ph SNMP/Web plug-in adapter (P/N 1018959) LP 33 Series UPS RS-232 RS-232 Active Active UTP 10/100 UTP 10/100 Reset Reset • 1 – RJ45 Connector Ethernet connection, 10Base-T or 100Base-TX •...
  • Page 11 • 1 – RJ45 Connector Ethernet connection, 10Base-T or 100Base-TX • 2 – LEDs Ref. specific section • 3 – RS-232 port Local console connection (115200-N-8-1) • 4 – Reset button HW reset • 5 – RJ11 Connector Contact interface, open-collector output SP SNMP/Web plug-in adapter (P/N 23954) RS-232 RS-232...
  • Page 12: Features

    LEDs The various front panel LEDs have the following meaning: • LAN / Netlink Status Blink • UPS / Fail Status • Active Status Blink FEATURES Each SNMP/Web adapter provides the following features: • 10/100 Mpbs connection speed • Use of DHCP / BOOTP or manual configuration for the TCP/IP network settings •...
  • Page 13: Additional Documents

    ADDITIONAL DOCUMENTS The SNMP/Web adapter is provided with a CD-ROM containing the following documentation: • Installation Manual • Operating Manual • SNMP Management Information Base (MIB) • Release notes and other instructions, as applicable Modifications reserved ISG_CNT_SNM_BAS_CRD_1GB_V012.doc Page 13/24 Installation Guide SNMP/Web Adapter...
  • Page 14: Installation

    INSTALLATION NOTE ! Strictly observe the ‘UPS Safety Rules’. Read carefully the UPS ‘Operating Manual & Installation Guide’ before installing or operating the equipment. If any problems are encountered with the installation procedure here described, please contact the nearest Service Centre before proceeding. 3-PH SNMP/WEB PLUG-IN ADAPTER (P/N 1018959) NOTE ! SitePro units produced before 2003 require an additional...
  • Page 15: Installing The Snmp Card In Option Slot

    3.1.2 Installing the SNMP Card in option slot IMPORTANT: Switch off the UPS, and wait approx. 2 minutes or switch the UPS to the manual bypass. In the latter case, please ensure that the mains input is reliable during this period. All cables must be disconnected from the card during the installation.
  • Page 16: Connecting The Card

    1. Change the front plate with the smaller one delivered with the Kit. 2. Insert the SNMP adapter in the options slot. 3. Fix the front plate of the SNMP adapter to the connectivity box, using the screw included in the SNMP/Web adapter kit.
  • Page 17: Sp Snmp/Web Plug-In Adapter (P/N 1019070)

    Connect the UPS to the SNMP/WEB Interface box (Sub-D connector “UPS”) using the cable provided with the UPS (VIC/23 or IMV-I or 1:1 straight cable) for intelligent communication. Note: when using the Contact Interface communication on GE Digital Energy™ UPS, a VIC-25 or IMV-C cable kit is required.
  • Page 18: Interfaces

    • Connect the power to the box (left-most connector in the picture above). Make sure that the SNMP/WEB Interface box is powered by the UPS output! • The UPS / Fail LED will switch OFF once the connection to the UPS is established. If the LED remains continuously on, check the UPS connection and related cabling.
  • Page 19: Configuration

    8 data bits, Terminal emulation VT-100 • Establish the connection and press • The default username (login) and password are ge and ge • A command-line configuration interface is entered. Type menu to enter the quick network configuration menu: Modifications reserved ISG_CNT_SNM_BAS_CRD_1GB_V012.doc...
  • Page 20: Configuration Via The Network

    Launch a telnet client (e.g. on a PC running Windows, select Run from the Start menu and type telnet ) • The default username (login) and password are ge and ge • A command-line configuration interface is entered WEB BROWSER •...
  • Page 21: Network Parameters

    NETWORK PARAMETERS The SNMP/Web adapter connects to the network using the following parameters: • IP address identifies the adapter on the network. • Subnet mask defines a range of addresses within the organisation. • Gateway the node used for connection to addresses outside the subnet. The adapter can be configured to obtain these settings automatically using DHCP or BOOTP protocols, or to use static addresses (manual configuration).
  • Page 22: Access

    Launch the browser • Enter the URL of the SNMP/Web adapter: http:/// (e.g. http://192.168.24.14/) • When prompted, enter username and password (by default, these are set to ge and ge) • The SNMP/Web adapter home page will be shown TROUBLESHOOTING If no answer is received from the adapter, verify the adapter installation, cabling and network configuration.
  • Page 23: Customer Support

    CUSTOMER SUPPORT FIRST LINE SUPPORT Please contact your local GE distributor for problems with the installation of the product or its use. INTERNET On-line support available on request (Internet access required). WWW SERVER We have a WWW server running at With your favourite web browser you can access the latest information from GE, and download updates and manuals for this product.
  • Page 24: Appendix A

    APPENDIX A SitePro EARTH CONNECTION In order to guarantee correct functional behaviour, the SNMP/Web plug-in adapter must be connected to protective earth (UPS chassis). On SitePro UPSs manufactured before 2003 the square plates (delivered with the 3-ph adapter kit) must be mounted – refer to the pictures below for the installation details.

Table of Contents