Emerson Wall-Mounted RH Sensor and RH Product Information Sheet

Emerson Wall-Mounted RH Sensor and RH Product Information Sheet

Wall-mounted rh sensor and rh/temperature sensor

Quick Links

Wall-Mounted RH Sensor and RH/Temperature Sensor
Wall-Mounted RH Sensor and RH/Temperature Sensor
Overview
CPC specs a wall-mounted relative humidity (RH)
sensor (P/N 203-5751) and/or RH and temperature
sensor (P/N 203-5752) for use in building control and
anti-sweat control applications using CPC input
boards.

Specifications

General
Input Power
12VDC
Enclosure
High-impact plastic, white
Relative Humidity (RH)
Sensing
Digitally profiled thin-film
Element
capacitive
RH Accuracy
±3% RH over the range 20%-90%
RH
Stability
<0.5% RH per year
Operating
0-100% RH
Humidity Range
Analog Output
0-5VDC; 3-wire, observe
polarity
Scaling
0-100% RH
Temperature
Temperature
±0.4°F from 32°F to 140°F
Accuracy
Analog Out
Resistive, 2-wire, no polarity
Choosing a Mounting
Location
Mount the sensor indoors in a central location within
the zone to be measured, away from doors, windows,
vents, heaters, and outside walls that could affect
temperature readings. The sensor should be at least
four feet from the floor, and no higher than necessary
to prevent tampering.
Product Information Sheet
Product Information Sheet
Mounting
29
1. Insert a screwdriver into the gap in the plastic
on the bottom side of the sensor enclosure,
and pry the front part of the enclosure away
from the rear mounting plate. Pull the front
away from the mounting plate until the top
separates from the mounting plate.
2. Remove the punch outs above the wiring
connectors so that the sensor cables can be
run into the sensor enclosure (see Figure 1).
3. Use the pre-made holes to mount the plate
on a junction box using the screws provided,
or mount it against a wall or riser. Do not
mount the plate upside down or sideways.
The plate should be mounted with the
terminal blocks toward the bottom.
4. If necessary, drill or cut a hole in the wall to
allow the sensor cable to be run through the
wall into the sensor's terminal block.
Figure 1 - RH/Temp Sensor Back Plate
203-5751
loading

Summary of Contents for Emerson Wall-Mounted RH Sensor and RH

  • Page 1: Specifications

    Wall-Mounted RH Sensor and RH/Temperature Sensor Wall-Mounted RH Sensor and RH/Temperature Sensor 203-5751 Product Information Sheet Product Information Sheet Overview Mounting CPC specs a wall-mounted relative humidity (RH) 1. Insert a screwdriver into the gap in the plastic sensor (P/N 203-5751) and/or RH and temperature on the bottom side of the sensor enclosure, sensor (P/N 203-5752) for use in building control and and pry the front part of the enclosure away...
  • Page 2 Wall-Mounted RH Sensor and RH/Temperature Sensor 203-5751 Product Information Sheet RH Sensor Wiring RH/Temp Sensor Wiring 1. Use Belden #8771 shielded three-conductor RH wiring is the same as the RH wiring shown in cable or equivalent. the diagram(Figure 2). For temp sensor wiring, follow the steps below: NOTE: Seat the connector on the back plate if it 1.
  • Page 3 Emerson Climate Technologies logos are trademarks and service marks of Emerson Electric Co. Intelligent Store is a trademark of Emerson Climate Technologies. All other trademarks are the property of their respective owners. © 2011 Emerson Climate Technologies, Inc. All rights reserved.

This manual is also suitable for:

Temperature sensor203-5751