INSTALLATION AND MAINTENANCE INSTRUCTIONS
H365, H365-IV, H365R,
H365R-IV, H365HT, and H365HT-IV
Intelligent Programmable Temperature Sensors
SPECIFICATIONS
Operating Voltage Range:
Operating Current @ 24 VDC:
Maximum Alarm Current:
Maximum Current:
Operating Humidity Range:
Installation Temperature:
Fixed Temperature Rating:
High Heat Temperature Rating:
Rate-of Rise Detection:
Height:
Diameter:
Weight:
UL 521 listed for Heat Detectors
This sensor must be installed in compliance with the control panel system
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ). Sensors offer maximum performance when
installed in compliance with the National Fire Protection Association (NFPA);
see NFPA 72.
Before installing sensors, please read the system wiring and installation man-
ual thoroughly. This manual provides detailed information on sensor spac-
ing, placement, zoning, and special applications. Copies of these manuals are
available from FireLite.
GENERAL DESCRIPTION
Models H365, H365-IV, H365R, H365R-IV, H365HT, and H365HT-IV are field
programmable intelligent sensors that utilize a state-of-the-art thermistor
sensing circuit for fast response. These sensors are designed to provide open
area protection with 50-foot spacing capability as approved by UL 521. The
intelligent temperature sensor can be programmed as either a 135°F fixed
temperature sensor, a rate of rise and 135°F fixed temperature sensor or a
190°F high temperature sensor through the Fire Alarm Control Panel (FACP).
Two LEDs on each sensor light to provide a local, visible sensor indication.
Remote LED annunciator capability is available as an optional accessory
(Part No. RA100Z). Rotary dial switches are provided for setting the sensor's
address. (See Figure 1.)
FIGURE 1: ROTARY ADDRESS SWITCHES
7
8
6
9
5
10
11
4
12
3
13
2
14
1 0
15
TENS
FireLite panels offer different feature sets across different models. As a re-
sult, certain features of the Intelligent Programmable Temperature Sensors
may be available on some control panels, but not on others. H365, H365R,
and H365HT will support only LiteSpeed® protocol mode. H365-IV, H365R-IV,
and H365HT-IV will support either LiteSpeed or CLIP (Classic Loop Interface
Protocol) mode.
The possible features available if supported by the control panel are:
1.
The sensor's LEDs can operate in three ways—on, off, and blinking–and
they can be set to red, green, or amber. This is controlled by the panel.
2.
The remote output may be synchronized to the LED operation or con-
trolled independent of the LEDs. Please refer to the operation manual for
the UL listed control unit for specific operation of these models
3.
Devices are point addressable up to 159 addresses.
15 to 32 Volts DC Peak
200 uA (one communication every 5 seconds with green LED blink on communication)
2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on)
4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on)
10% to 93% Relative Humidity, Non-condensing
Set for fixed-temperature or rate-of-rise (ROR): –4°F to 100°F (–20°C to 38°C)
Set for high-heat: –4°F to 150°F (–20°C to 66°C)
135°F (57°C)
190°F (88°C)
Responds to greater than 15°F/minute or 135°F (8.3°C/minute or 57°C)
2.0˝ (51 mm) installed in B300-6 Base
6.2˝ (156 mm) installed in B300-6 Base
3.4 oz. (95 g)
7
8
6
9
5
4
3
2
1 0
ONES
C0162-00
4.
The heat sensor operates as a programmable heat detector.
NOTE: In panels where this feature is not available, the H365 and
H365-IV will default to a 135°F fixed heat detector. H365R and H365R-IV
will default to a 135°F fixed heat detector and rate-of-rise. H365HT and
H365HT-IV will default to a 190°F high temperature heat detector.
Intelligent programmable temperature sensors require compatible addressable
communications to function properly. Connect these sensors to listed-compat-
ible control panels only.
WIRING GUIDE
All wiring must be installed in compliance with the National Electrical Code,
applicable local codes and the Authority Having Jurisdiction. Proper wire
gauges should be used. The installation wires should be color coded to limit
wiring mistakes and ease system troubleshooting. Improper connections will
prevent a system from responding properly in the event of a fire.
Remove power from the communication line before installing sensors.
1.
Wire the sensor base (supplied separately) as shown in the wiring
diagram. (See Figure 2.)
2.
Set the desired address on the rotary dial switches. (See Figure 1.)
3.
Install the sensor into the sensor base. Push the sensor into the base
while turning it clockwise to secure it in place.
4.
After all sensors have been installed, apply power to the control unit and
activate the communication line.
5.
Test the sensor(s) as described in the TESTING section of this manual.
FIGURE 2. WIRING DIAGRAM:
Remote
Annunciator
+
-
(+)
+
+
2
RA
1
3
(–)
(–)
CLASS A OPTIONAL WIRING
(+)
1
One FireLite Place
Northford, CT 06472
Phone: 203.484.7161
CAUTION: Do not loop wire under
terminal 1 or 2. Break wire run to
supervise connections.
+
+
+
+
2
2
RA
RA
1
1
3
3
I56-6525-000
11/15/2017
C0129-10
loading

Summary of Contents for Honeywell FIRE-LITE ALARMS H365

  • Page 1 INSTALLATION AND MAINTENANCE INSTRUCTIONS H365, H365-IV, H365R, H365R-IV, H365HT, and H365HT-IV One FireLite Place Northford, CT 06472 Intelligent Programmable Temperature Sensors Phone: 203.484.7161 SPECIFICATIONS Operating Voltage Range: 15 to 32 Volts DC Peak Operating Current @ 24 VDC: 200 uA (one communication every 5 seconds with green LED blink on communication) Maximum Alarm Current: 2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on) Maximum Current:...
  • Page 2 – Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. – Consult the dealer or an experienced radio/TV technician for help. FireLite ® and LiteSpeed ® are registered trademarks of Honeywell International, Inc. I56-6525-000 ©2017 FireLite. 11/15/2017...

This manual is also suitable for:

Fire-lite alarms h365-ivFire-lite alarms h365rFire-lite alarms h365r-ivFire-lite alarms h365htFire-lite alarms h365ht-iv