Mitsubishi Electric PAC-SH63AG-E Series Manual

Air protect

Quick Links

Air Protect Guide
Photo
Dimensions
200
25
155
Hole
Hole
Hole
* Air Guide prevents reverse rotation of outdoor unit fan when it enters low speed rotation mode with fan controller being operated.
It is also used for protection of fan when strong winds, such as a typhoon, wind blowing through tall buildings, etc., directly strike the air outlet.
In addition, installation of this product is necessary when cooling opetation is to be performed in outdoor tempreture of -5℃ or lower (down to -15℃).
Note the followings when installing this guide:
1) Be sure not to use "upward discharge" in a place where snowing is possible. Snow may accumulate in the guard, which could damage the fan, etc.
2) Attaching this unit will decrease the performance (by 2-3%) and increase noise from outdoor unit (by approx. 1-2 dB).
3) Do not use "upward discharge" when there are any obstacles at the back and on both sides of outdoor unit (air is taken in from top of unit):
This could cause a short cycle.
4) To eliminate the influence of external wind, be sure to install the unit with its back facing to wall.
5) Do not install this unit in a place where wind directly blows to the back of the unit.
(for cooling at -15 )
Unit: mm (inch)
588
(Installation pitch of board B and outdoor unit)
559
CAUTION
* model change from PAC-SG57AG-E from Sep 2005
Descriptions
Enables operation even when the outside temperature is low.
Protect the unit from cold wind.
Applicable Models
PUZ-ZM60VHA type
PUZ-ZM71VHA type
[R32 type]
Specifications
Color (Munsell)
Surface treatment
Exterior
Material
Weight
Accessory name x Qty.
4-φ7hole
Outdoor unit installation side
PAC-SH63AG-E *
PUHZ-ZRP60HA2
PUHZ-ZRP71VHA2
1 piece required
PUHZ-SHW112VHA
PUHZ-SHW112YHA
PUHZ-SHW140YHA
2 pieces required
[R410A type]
Ivory (3.0Y 7.8/1.1)
Acrylic resin coating
Alloy hot-dip zinc-coated carbon steel
sheet
3.3kg
Washer faced screw (M5x15) x 4
plated>
D2-251
loading

Summary of Contents for Mitsubishi Electric PAC-SH63AG-E Series

  • Page 1 Air Protect Guide PAC-SH63AG-E * (for cooling at -15 ) * model change from PAC-SG57AG-E from Sep 2005 Descriptions Photo Enables operation even when the outside temperature is low. Protect the unit from cold wind. Applicable Models PUZ-ZM60VHA type PUHZ-ZRP60HA2 ■...
  • Page 2 Air Protect Guide for cooling at -15 PAC-SH63AG-E How to Use / How to Install SAFETY PRECAUTIONS ●Carefully read this section ‘Safety Precautions’, and securely install the optional parts. ●Be sure to observe the cautions described here: They include critical contents for safety. ●The following indications show the classifications for danger, and possible consequences following incorrect handling.
  • Page 3 Air Protect Guide for cooling at -15 PAC-SH63AG-E 2 Requirements of space for installation 3 Installation procedure D2-253...

This manual is also suitable for:

Puz-zm60vha seriesPuz-zm71vha seriesPuhz-zrp60ha2Puhz-zrp71vha2Puhz-shw112vhaPuhz-shw112yha ... Show all