Specifications - Fujitsu ARXG36KMLA Design & Technical Manual

Duct type refrigerant r32 inverter
Hide thumbs Also See for ARXG36KMLA:
Table of Contents

1. Specifications

Type
Model name
Power supply
Power supply intake
Available voltage range
Rated
Cooling
Min.—Max.
Capacity
Rated
Heating
Min.—Max.
Rated
Cooling
Max.
Input power
Rated
Heating
Max.
Cooling
Current
Rated
Heating
Cooling
Power factor
Heating
EER
Cooling
COP
Heating
Moisture removal
Cooling
Maximum operating current *1
Heating
Cooling
Airflow rate
Fan
Heating
Type × Q'ty
Motor output
Static pressure range
Cooling
Sound pressure level *2
Heating
Cooling
Sound power level
Heating
Dimensions (H × W × D)
Fin pitch
Heat exchanger type
Rows × Stages
Pipe type
Fin type
Material
Enclosure
Color
Net
Dimensions
(H × W × D)
Gross
Net
Weight
Gross
Liquid
Size
Connection pipe
Gas
Method
Material
Drain port
Size
Cooling
Operation range
Heating
Remote control (Option)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Standard static pressure; 36 type: 47 Pa, 45 type: 60 Pa
– Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
• *2: Sound pressure level:
– Measured values in manufacturer's anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *3: Available on Google Play
store or on App Store
kW
Btu/h
kW
Btu/h
kW
Btu/h
kW
Btu/h
kW
A
%
kW/kW
L/h (pints/h)
A
HIGH
MED
LOW
QUIET
3
m
/h
HIGH
MED
LOW
QUIET
W
Pa
HIGH
MED
LOW
QUIET
dB (A)
HIGH
MED
LOW
QUIET
HIGH
dB (A)
mm
mm
kg
mm (in)
mm
°C
%RH
°C
®
. Optional WLAN adapter is also required. For details, refer to the setting manual.
- 2 -
Inverter heat pump
ARXG36KMLA
3N 400 V ~ 50 Hz
Outdoor unit
342—457 V
9.5
32,400
2.8—11.2
9,600—38,200
10.8
36,900
2.7—12.7
9,200—43,300
2.97
4.29
2.88
4.66
5.7
5.6
75.4
75.1
3.20
3.75
3.0 (5.3)
10.5
10.5
1,900
1,620
1,270
980
2,100
1,620
1,270
980
Sirocco × 2
197
30 to 150
39
35
30
26
42
35
30
26
65
70
294 × 1,000 × 39.9
1.40
3 × 14
Copper
Aluminum
Steel sheet
270 × 1,135 × 700
300 × 1,320 × 790
38
45
Ø9.52 (3/8)
Ø15.88 (5/8)
Flare
Steel
Ø35.7 (I.D.), Ø38.1 (O.D.)
18 to 32
80 or less
16 to 30
Wired remote controller, Wireless remote controller, Mobile app*3 (FGLair
ARXG45KMLA
12.1
41,300
4.0—13.0
13,600—44,300
13.5
46,100
4.2—15.2
14,300—51,800
4.22
5.03
3.84
4.79
7.7
7.1
79.6
78.2
2.87
3.52
4.0 (7.0)
14.0
14.0
2,100
1,750
1,350
1,070
1,750
1,350
1,070
42
38
32
28
42
38
32
28
68
70
294 × 1,000 × 53.2
4 × 14
39
47
)