Electrical Characteristics - Fujitsu ARXG12KHTAP Design & Technical Manual

Air conditioner duct type
Hide thumbs Also See for ARXG12KHTAP:
Table of Contents

10. Electrical characteristics

Model name
Voltage
Power
supply
Frequency
Max operating current *1
Starting current
Circuit breaker current
Wiring
Power cable
spec.
Cross-sectional area
Connection
*2
cable *3
Limited wiring length
Model name
Voltage
Power
supply
Frequency
Max operating current *1
Starting current
Circuit breaker current
Wiring
Power cable
spec.
Cross-sectional area
Connection
*2
cable *3
Limited wiring length
*1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de-
vices complied to the regional standard.
*3: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
AOYG12KBTB
V
Hz
A
9.7
A
4.8
A
2
mm
2
mm
m
AOYG18KBTB
V
Hz
A
12.1
A
7.1
A
2
mm
2
mm
m
- 69 -
AOYG14KBTB
230 ~
50
10.2
5.8
13
1.5
1.5
26
AOYG22KBTB
230 ~
50
12.6
8.2
16
1.5
1.5
31
10. Electrical characteristics
Table of Contents
loading

Table of Contents