Equipment Manual 12/2007 Edition SINAMICS S120 Chassis Power Units Liquid Cooled sinamics...
Page 3
System Overview Line-Side Power Components SINAMICS S120 Power Modules Chassis Power Units Liquid Cooled Equipment Manual Line Modules Motor Modules Motor-Side Power Components Cabinet Design and EMC Cooling circuit and coolant properties Maintenance and servicing (GH7), Edition 12/2007 6SL3097-2AM00-0BP4 List of Abbreviations...
Page 4
Siemens. This product can only function correctly and safely if it is transported, stored, set up, and installed correctly, and operated and maintained as recommended.
Page 5
All obligations entered into by Siemens result from the respective contract of sale that contains the complete and sole valid warranty arrangements. These contractual warranty provisions are neither extended nor curbed as a result of the statements made in this documentation.
Page 6
Internet Address Up-to-date information about our products can be found on the Internet at the following address: http://www.siemens.com/motioncontrol You can find information on SINAMICS S120 at: http://www.siemens.com/sinamics Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 7
(via protective conductors, for example) or the measuring probe is briefly discharged before measurements are taken with an isolated measuring device (for example, touching a bare metal housing). Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 8
Order No. 6FC5297- AD30-0AP . Caution Operating the equipment in the immediate vicinity (< 1.5 m) of mobile telephones with a transmitter power of > 1 W may lead to incorrect operation. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 9
4) established that these risks do not exceed the specified limit values. For more information about residual risks of the Power Drive System components, see the relevant chapters in the technical user documentation. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 10
• Place barriers around hazardous areas. • Take measures, e.g. using shields, to reduce electromagnetic fields at their source. Make sure that personnel are wearing the appropriate protective gear. • Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
The SINAMICS range of drives ....................1-1 SINAMICS S120 drive system...................... 1-3 Technical specifications........................ 1-7 Structure of a drive system with SINAMICS S120 chassis liquid cooled ........1-9 1.4.1 Structure of a drive system with SINAMICS S120 and Power Module ........1-9 1.4.2...
Page 12
Interface description ........................5-4 5.3.1 Overview............................5-4 5.3.2 Connection example ........................5-8 5.3.3 DC link/motor connection......................5-8 5.3.4 Terminal block X9 ......................... 5-9 5.3.5 Terminal block X41 ........................5-9 Chassis Power Units Liquid Cooled VIII SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 13
Overcurrent protection by line fuse or circuit-breaker ..............7-12 7.4.4 Line contactor ..........................7-12 Arrangement of components and equipment ................7-13 7.5.1 General ............................7-13 7.5.2 Drive line-up..........................7-13 Horizontal installation ......................... 7-14 Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 14
9.4.27 Replacing the Power Supply Board, Basic Line Module, frame size GBL ......... 9-57 Reforming the DC link capacitors ....................9-59 List of Abbreviations ..........................10-1 10.1 List of Abbreviations ........................10-1 Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
The SINAMICS range of drives Application SINAMICS is the new range of converters from Siemens designed for industrial mechanical and plant engineering applications. SINAMICS offers solutions for all drive tasks: • Simple pump and fan applications in the process industry.
Page 16
The different SINAMICS versions can be easily combined with each other. SINAMICS is part of the Siemens "Totally Integrated Automation" concept. Integrated SINAMICS systems covering configuration, data storage, and communication at automation level ensure low-maintenance solutions with the SIMATIC, SIMOTION, and SINUMERIK control systems.
SINAMICS S120 drive system Modular system for sophisticated drive tasks SINAMICS S120 solves complex drive tasks for a wide range of industrial applications and is, therefore, designed as a modular system. Users can choose from many different harmonized components and functions to create a solution that best meets their requirements.
Page 18
Inter-axis connections can be established within a Control Unit and easily configured in the STARTER commissioning tool using a mouse. Simple technological tasks can be carried out by the SINAMICS S120 Control Unit itself. For complex numerical or motion-control tasks, high-performance SIMOTION D modules are used instead.
Page 19
• Supplementary system components that enhance functionality and offer different interfaces for encoders and process signals. The SINAMICS S120 components were developed for installation in cabinets. They have the following features and characteristics: • Easy to handle, simple installation and wiring •...
Page 20
Control cabinets with liquid cooling are easy to implement as hermetically sealed units with degrees of protection of IP54 or above. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
1.3 Technical specifications Technical specifications Technical specifications Unless explicitly specified otherwise, the following technical specifications are valid for all the following components of the SINAMICS S120 Liquid Cooled drive system. Table 1-1 General technical specifications Electrical data Line connection voltage 380 V 3 AC –10 % to 480 V 3 AC +10 % (-15 % <...
Page 22
EN 61800-5-1, EN 60204-1, EN 61800-3, EN 60146-1-1 Approvals cULus (File Nos.: E192450 and E214113), some approvals in preparation (only up to 600 V 3 AC) in packaging for transportation Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
System Overview 1.4 Structure of a drive system with SINAMICS S120 chassis liquid cooled Structure of a drive system with SINAMICS S120 chassis liquid cooled 1.4.1 Structure of a drive system with SINAMICS S120 and Power Module Fig. 1-4 Basic structure of a drive system with SINAMICS S120 and Power Module...
System Overview 1.4 Structure of a drive system with SINAMICS S120 chassis liquid cooled 1.4.2 Structure of a drive system with SINAMICS S120 and regulated infeed Fig. 1-5 Structure of a drive system with SINAMICS S120 and regulated infeed Chassis Power Units Liquid Cooled...
System Overview 1.4 Structure of a drive system with SINAMICS S120 chassis liquid cooled 1.4.3 Structure of a drive system with SINAMICS S120 and unregulated infeed Fig. 1-6 Basic structure of a drive system with SINAMICS S120 (unregulated infeed) Chassis Power Units Liquid Cooled...
Page 26
System Overview 1.4 Structure of a drive system with SINAMICS S120 chassis liquid cooled Chassis Power Units Liquid Cooled 1-12 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
The connection lines to the Power Module must be kept as short as possible (max. 5 m). Caution Using line reactors not approved by SIEMENS for SINAMICS: - Can damage/destroy Power Module. - Line harmonics that may interfere with or damage other loads connected to the same line supply.
Line-Side Power Components 2.1 Line reactors for Power Modules 2.1.3 Dimension drawing Fig. 2-1 Dimension drawing: Line reactor for Power Modules Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
The connection lines to the Line Module must be kept as short as possible (max. 5 m). Caution Using line reactors not approved by SIEMENS for SINAMICS: - Can damage/destroy Line Modules. - Line harmonics that may interfere with or damage other loads connected to the same line supply.
Line-Side Power Components 2.2 Line reactors for Basic Line Modules 2.2.3 Dimension drawing Mounting hole Fig. 2-2 Dimension drawing: line reactor for Basic Line Modules Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 32
6SL3000- 0CH33-4AA0 0CH36-0AA0 0CH41-2AA0 0CH41-6AA0 12.5 18 x 14 152.5 152.5 hmax 232.5 84.5 60.5 60.5 Dimensions n1 and n2 correspond to the drill hole spacing Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
The DC link discharge time hazard warning must be affixed to the component in the relevant local language. Notice The cooling clearances above, below, and in front of the component, which are specified in the dimension drawings, must be observed. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Power input -X1 (L1, L2, L3) Power output -X2 (U2, V2, W2) PE connection Fig. 2-4 Interface overview for Active Interface Module, frame size GI Chassis Power Units Liquid Cooled 2-10 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 37
Line-Side Power Components 2.3 Active Interface Modules Fig. 2-5 Interface overview for Active Interface Module, frame size HI Chassis Power Units Liquid Cooled 2-11 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 38
-K4 -X609 Connection bracket for interference-suppression Power output -X2 PE connection Power input -X1 capacitor Fig. 2-6 Interface overview for Active Interface Module, frame size JI Chassis Power Units Liquid Cooled 2-12 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Line-Side Power Components 2.3 Active Interface Modules 2.3.3.2 Sample connection Fig. 2-7 Interface overview for Active Interface Module, frame size GI Chassis Power Units Liquid Cooled 2-13 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
M10 / 25 Nm for ring cable lugs to DIN 46234 • Frame size HI / JI: M12 / 50 Nm for ring cable lugs to DIN 46234 • Chassis Power Units Liquid Cooled 2-14 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Active Interface Modules of frame size JI and HI require a signal on terminal X609:11 and 12 to control the fans. If this signal is not present during operation, the fans do not rotate and the module is shut down on overtemperature. Chassis Power Units Liquid Cooled 2-15 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Component recognition via LED is activated (p0144) orange Note: The two options depend on the LED status when module recognition is activated via p0144 = 1. Red / orange Chassis Power Units Liquid Cooled 2-16 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Dimension drawing frame size GI The mandatory cooling clearances are indicated by the dotted line. Side view Rear view Fig. 2-9 Dimension drawing for Active Interface Module, frame size GI Chassis Power Units Liquid Cooled 2-17 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 44
Dimension drawing frame size HI The mandatory cooling clearances are indicated by the dotted line. Side view Rear view Fig. 2-10 Dimension drawing for Active Interface Module, frame size HI Chassis Power Units Liquid Cooled 2-18 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 45
Dimension drawing frame size JI The mandatory cooling clearances are indicated by the dotted line. Side view Rear view Fig. 2-11 Dimension drawing for Active Interface Module, frame size JI Chassis Power Units Liquid Cooled 2-19 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Removing the connection bracket to the noise suppression capacitor (example: frame size JI) Warning Failing to remove the connection bracket for the interference-suppression capacitor on a non-grounded system/IT system can cause significant damage to the unit. Chassis Power Units Liquid Cooled 2-20 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
1.00 0.95 0.90 0.85 1000 2000 3000 4000 Site altitude in m above sea level Fig. 2-14 Current correction factor K as a function of site altitude Chassis Power Units Liquid Cooled 2-23 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 50
1, the rated current can be used in the calculation. If the multiplication result is <1, the rated current must be multiplied by this value to yield the maximum permissible continuous current. Chassis Power Units Liquid Cooled 2-24 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Power Module must be connected to a Control Unit via DRIVE-CLiQ. The open-loop and closed-loop control functions are stored in the Control Unit. Fig. 3-1 Overview of Power Modules in chassis format Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 52
The fans are switched on and off as a function of several factors (e.g. heat sink temperature, ambient temperature, output current, duty cycle, ...) which means that fan operating cycles cannot be calculated directly. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Other than that the following measures must be taken in accordance with EN 61800-5-1: Either protective ground conductor cross sections ≥ 10 mm² Cu or installation of a second protective ground conductor of the same cross section as the first one. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
U2 V2 W2 PE DRIVE-CLiQ 24 V DC connecting cable for supplying a CU310 Control Unit integrated in the Power Module Fig. 3-4 Wiring diagram for the Power Module Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
When the STO (Safe Torque Off) or SS1 (Safe Stop 1) function is activated via terminals, a 24 V DC supply must be connected to terminal -X9:7 and terminal -X9:8 must be connected to ground. Upon removal, pulse suppression is activated. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Reserved, do not use Reserved, do not use Receive data - Reserved, do not use Reserved, do not use + (24 V) Power supply M (0 V) Electronic ground Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
The warning information on the components must be carefully observed! Cause and rectification of faults The following reference contains information about the cause and rectification of faults: Reference: /IH1/ SINAMICS S120 Commissioning Manual Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Dimension drawing, frame size FL The cooling clearances to be maintained are indicated by the dotted line. Front view Side view Fig. 3-5 Dimension drawing of Power Module, frame size FL Chassis Power Units Liquid Cooled 3-10 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 61
Dimension drawing, frame size GL The cooling clearances to be maintained are indicated by the dotted line. Front view Side view Fig. 3-6 Dimension drawing of Power Module, frame size GL Chassis Power Units Liquid Cooled 3-11 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Screw coupling points for mechanical support The Power Modules are provided with screw coupling points at the top and bottom so that they can be connected to modules mounted adjacently. Chassis Power Units Liquid Cooled 3-12 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Removing the connection bracket for the interference-suppression capacitor Warning Failing to remove the connection bracket for the interference-suppression capacitor on a non-grounded system/IT system can cause significant damage to the unit. Chassis Power Units Liquid Cooled 3-13 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
This value applies to the water coolant option; for other coolant types, see Chapter 8. In order to build a UL-approved system, it is absolutely essential to use the specified fuses. Chassis Power Units Liquid Cooled 3-14 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
The base load current for a high overload (IH) is based on a duty cycle of 150% for 60 s or 160% for 10 s. 10 s 1.6 * I 1.5 * I 60 s 300 s Fig. 3-10 High overload Chassis Power Units Liquid Cooled 3-15 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Derating factors 3.7.2.1 Derating factors as a function of coolant temperature SINAMICS S120 Liquid Cooled units are designed for cooling by H O or by an O / Antifrogen N mixture. An H O / Antifrogen N mixture must contain between 20 % and 45 % Antifrogen N.
Maximum ambient temperature at 90 % current load Maximum ambient temperature at 100 % current load Fig. 3-13 Maximum ambient temperature as a function of installation altitude Chassis Power Units Liquid Cooled 3-17 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
88 % 1TE35-0AA0 78 % Note For pulse frequencies in the range between the specified fixed values, the relevant derating factors can be determined by linear interpolation. Chassis Power Units Liquid Cooled 3-18 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
500 V 3 AC –10 % to 690 V 3 AC +10 % (-15 % < 1 min) (47 to 63 Hz) • Suitable for TN, TT, and IT supply systems • Operating status and error status via LEDs Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
They are suitable for applications in which no regenerative energy is present or in which energy is exchanged between the motor-side and regenerative axes in the DC link. Fig. 4-1 Overview of Basic Line Modules Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 71
(i.e. different supply systems are not permitted). • A derating factor of 7.5 % must be taken into consideration, regardless of the number of modules connected in parallel. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Other than that the following measures must be taken in accordance with EN 61800-5-1: Either protective ground conductor cross sections ≥ 10 mm² Cu or installation of a second protective ground conductor of the same cross section as the first one. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
675 V to 932 V DC • Connecting thread M12 / 50 for ring cable lugs to DIN 46234 PE connection Connecting thread M12 / 50 for ring cable lugs to DIN 46234 Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Max. connectable cross-section 1.5 mm Note A cable harness is used to connect terminals -X41:1 and -X41:2 to terminals -X9:8 and -X9:7. 4.2.3.6 Terminal block X42 Reserved, do not use! Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
The seals for the screwed connections can be used only once when the cooling circuit is first assembled. The seals must be replaced if the circuit is disassembled and assembled again. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
The warning information on the components must be carefully observed! Cause and rectification of faults The following reference contains information about the cause and rectification of faults: Reference: /IH1/ SINAMICS S120 Commissioning Manual Chassis Power Units Liquid Cooled 4-10 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
The cooling clearances to be maintained are indicated by the dotted line. Front view Side view Fig. 4-5 Dimension drawing of Basic Line Module, frame size FBL Chassis Power Units Liquid Cooled 4-11 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 80
The cooling clearances to be maintained are indicated by the dotted line. Front view Side view Fig. 4-6 Dimension drawing of Basic Line Module, frame size GBL Chassis Power Units Liquid Cooled 4-12 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
If several modules are mounted adjacent to one another, they can be interconnected via the screw coupling points. When a single module is installed, lateral support can be provided by means of reinforcing plates inserted between the module and the cabinet. Chassis Power Units Liquid Cooled 4-13 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Removing the connection bracket for the interference-suppression capacitor Warning Failing to remove the connection bracket for the interference-suppression capacitor on a non-grounded system/IT system can cause significant damage to the unit. Chassis Power Units Liquid Cooled 4-14 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
This value applies to the water coolant option; for other coolant types, see Chapter 8. In order to build a UL-approved system, it is absolutely essential to use the specified fuses. Chassis Power Units Liquid Cooled 4-15 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 84
This value applies to the water coolant option; for other coolant types, see Chapter 8. In order to build a UL-approved system, it is absolutely essential to use the specified fuses. Chassis Power Units Liquid Cooled 4-16 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
4.2.7.1 Derating factors Derating factors as a function of coolant temperature SINAMICS S120 Liquid Cooled units are designed for cooling by H O or by an O / Antifrogen N mixture. An H O / Antifrogen N mixture must contain between 20 % and 45 % Antifrogen N.
Page 86
Maximum ambient temperature at 90 % current load Maximum ambient temperature at 100 % current load Fig. 4-11 Maximum ambient temperature as a function of installation altitude Chassis Power Units Liquid Cooled 4-18 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Active Line Module of frame size GXL. Active Interface Modules in these frame sizes have degree of protection IP20; Active Line Modules in these frame sizes have degree of protection IP00. Chassis Power Units Liquid Cooled 4-19 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 88
The fans are switched on and off as a function of several factors (e.g. heat sink temperature, ambient temperature, output current, duty cycle, ...) which means that fan operating cycles cannot be calculated directly. Chassis Power Units Liquid Cooled 4-20 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Either protective ground conductor cross sections ≥ 10 mm² Cu or installation of a second protective ground conductor of the same cross section as the first one. Chassis Power Units Liquid Cooled 4-21 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Line Modules 4.3 Active Line Modules 4.3.3 Interface description 4.3.3.1 Overview Fig. 4-15 Active Line Module, frame size GXL Chassis Power Units Liquid Cooled 4-22 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 91
-X402 Electronic fan -X401 -X400 Line connection (U1, V1, W1) PE connection Ventilation hose Coolant connection A / B Fig. 4-16 Active Line Module, frame size HXL Chassis Power Units Liquid Cooled 4-23 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 92
Line Modules 4.3 Active Line Modules Fig. 4-17 Active Line Module, frame size JXL Chassis Power Units Liquid Cooled 4-24 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Connection lugs: d = 13mm (M12 / 50Nm) for ring cable lugs to DIN 46234 PE connection Connection lugs: d = 13mm (M12 / 50Nm) for ring cable lugs to DIN 46234 Chassis Power Units Liquid Cooled 4-25 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Max. connectable cross-section 1.5mm Note A cable harness is used to connect terminals -X41:1 and -X41:2 to terminals -X9:8 and - X9:7. 4.3.3.6 Terminal block X42 Reserved, do not use! Chassis Power Units Liquid Cooled 4-26 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
The seals for the screwed connections can be used only once when the cooling circuit is first assembled. The seals must be replaced if the circuit is disassembled and assembled again. Chassis Power Units Liquid Cooled 4-27 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Cause and rectification of faults The following reference contains information about the cause of faults and how they can be rectified: References: /IH1/ SINAMICS S120 Commissioning Manual Chassis Power Units Liquid Cooled 4-28 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Dimension drawing for frame size GXL The mandatory cooling clearances are indicated by the dotted line. Front view Side view Fig. 4-19 Dimension drawing for Active Line Module, frame size GXL Chassis Power Units Liquid Cooled 4-29 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 98
Dimension drawing for frame size HXL The mandatory cooling clearances are indicated by the dotted line. Front view Side view Fig. 4-20 Dimension drawing for Active Line Module, frame size HXL Chassis Power Units Liquid Cooled 4-30 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 99
Dimension drawing for frame size JXL The mandatory cooling clearances are indicated by the dotted line. Front view Side view Fig. 4-21 Dimension drawing for Active Line Module, frame size JXL Chassis Power Units Liquid Cooled 4-31 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Screw coupling points for mechanical support The Active Line Modules are provided with screw coupling points at the top and bottom so that they can be connected to modules mounted adjacently. Chassis Power Units Liquid Cooled 4-32 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
This value applies to the water coolant option; for other coolant types, see Chapter 8. In order to build a UL-approved system, it is absolutely essential to use the specified fuses. Chassis Power Units Liquid Cooled 4-33 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 102
This value applies to the water coolant option; for other coolant types, see Chapter 8. In order to build a UL-approved system, it is absolutely essential to use the specified fuses. Chassis Power Units Liquid Cooled 4-34 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
4.3.6.1 Derating factors Derating factors as a function of coolant temperature SINAMICS S120 Liquid Cooled units are designed for cooling by H O or by an O / Antifrogen N mixture. An H O / Antifrogen N mixture must contain between 20 % and 45 % Antifrogen N.
Page 104
Maximum ambient temperature at 90 % current load Maximum ambient temperature at 100 % current load Fig. 4-25 Maximum ambient temperature as a function of installation altitude Chassis Power Units Liquid Cooled 4-36 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Module must be connected to a Control Unit via DRIVE-CLiQ. The open-loop and closed- loop control functions are stored in the Control Unit. Fig. 5-1 Overview of Motor Modules (chassis) Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 106
The fans are switched on and off as a function of several factors (e.g. heat sink temperature, ambient temperature, output current, duty cycle, ...) which means that fan operating cycles cannot be calculated directly. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Other than that the following measures must be taken in accordance with EN 61800-5-1: Either protective ground conductor cross sections ≥ 10 mm² Cu or installation of a second protective ground conductor of the same cross section as the first one. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Motor Modules 5.3 Interface description Interface description 5.3.1 Overview Fig. 5-2 Motor Module, frame size FXL Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 109
Motor Modules 5.3 Interface description Fig. 5-3 Motor Module, frame size GXL Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 110
Control Interface Board -X402 Electronic fan -X401 -X400 Motor connection (U2, V2, W2) PE connection Ventilation hose Coolant connection A / B Fig. 5-4 Motor Module, frame size HXL Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 111
Motor Modules 5.3 Interface description Fig. 5-5 Motor Module, frame size JXL Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Connection lugs: d = 13 mm (M12 / 50 Nm) for ring cable lugs to DIN 46234 PE connection Connection lugs: d = 13 mm (M12 / 50 Nm) for ring cable lugs to DIN 46234 Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
The KTY temperature sensor must be connected with the correct polarity. Note A cable harness is used to connect terminals -X41:1 and -X41:2 to terminals -X9:8 and -X9:7. 5.3.6 Terminal block X42 Reserved, do not use! Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
The seals for the screwed connections can be used only once when the cooling circuit is first assembled. The seals must be replaced if the circuit is disassembled and assembled again. Chassis Power Units Liquid Cooled 5-10 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Cause and rectification of faults The following reference contains information about the cause of the faults and how they can be resolved: Reference: /IH1/ SINAMICS S120 Commissioning Manual Chassis Power Units Liquid Cooled 5-11 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Dimension drawing, frame size FXL The cooling clearances to be maintained are indicated by the dotted line. Front view Side view Fig. 5-7 Dimension drawing of Motor Module, frame size FXL Chassis Power Units Liquid Cooled 5-12 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 117
Dimension drawing, frame size GXL The cooling clearances to be maintained are indicated by the dotted line. Front view Side view Fig. 5-8 Dimension drawing of Motor Module, frame size GXL Chassis Power Units Liquid Cooled 5-13 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 118
Dimension drawing, frame size HXL The cooling clearances to be maintained are indicated by the dotted line. Front view Side view Fig. 5-9 Dimension drawing of Motor Module, frame size HXL Chassis Power Units Liquid Cooled 5-14 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 119
Dimension drawing, frame size JXL The cooling clearances to be maintained are indicated by the dotted line. Front view Side view Fig. 5-10 Dimension drawing of Motor Module, frame size JXL Chassis Power Units Liquid Cooled 5-15 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Screw coupling points for mechanical support The Motor Modules are provided with screw coupling points at the top and bottom so that they can be connected to modules mounted adjacently. Chassis Power Units Liquid Cooled 5-16 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
This value applies to the water coolant option; for other coolant types, see Chapter 8. In order to build a UL-approved system, it is absolutely essential to use the specified fuses. Chassis Power Units Liquid Cooled 5-17 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 122
This value applies to the water coolant option; for other coolant types, see Chapter 8. In order to build a UL-approved system, it is absolutely essential to use the specified fuses. Chassis Power Units Liquid Cooled 5-18 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 123
This value applies to the water coolant option; for other coolant types, see Chapter 8. In order to build a UL-approved system, it is absolutely essential to use the specified fuses. Chassis Power Units Liquid Cooled 5-19 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 124
This value applies to the water coolant option; for other coolant types, see Chapter 8. In order to build a UL-approved system, it is absolutely essential to use the specified fuses. Chassis Power Units Liquid Cooled 5-20 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
The base load current for a high overload (IH) is based on a duty cycle of 150% for 60 s or 160% for 10 s. 10 s 1.6 * I 1.5 * I 60 s 300 s Fig. 5-13 High overload Chassis Power Units Liquid Cooled 5-21 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Derating factors 5.6.2.1 Derating factors as a function of coolant temperature SINAMICS S120 Liquid Cooled units are designed for cooling by H O or by an O / Antifrogen N mixture. An H O / Antifrogen N mixture must contain between 20 % and 45 % Antifrogen N.
Maximum ambient temperature at 90 % current load Maximum ambient temperature at 100 % current load Fig. 5-16 Maximum ambient temperature as a function of installation altitude Chassis Power Units Liquid Cooled 5-23 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
1TG41-3AA0 1200 1270 79 % Note For pulse frequencies in the range between the specified fixed values, the relevant derating factors can be determined by linear interpolation. Chassis Power Units Liquid Cooled 5-24 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 129
Maximum output frequencies achieved by increasing the pulse frequency Pulse frequency Maximum output frequency [kHz] [Hz] 1.25 Due to the closed-loop control, the maximum output frequency is limited to 300 Hz. Chassis Power Units Liquid Cooled 5-25 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Motor Modules, 675 V - 1080 V DC Order number Power [kW] Output current [A] Minimum line length [m] 6SL3325-1TG31-0AA0 6SL3325-1TG31-5AA0 6SL3325-1TG32-2AA0 6SL3325-1TG33-3AA0 6SL3325-1TG35-8AA0 6SL3325-1TG38-1AA0 6SL3325-1TG41-0AA0 1000 1025 6SL3325-1TG41-3AA0 1200 1270 Chassis Power Units Liquid Cooled 5-26 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
This reduces the output current of the Power Modules or Motor Modules (see section 3.7.2.4 or 5.6.2.4) When a sinusoidal filter is used, the available output voltage decreases by 15%. Fig. 6-1 Sinusoidal filter Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
- Outgoing cable to the load 1U2, 1V2, 1W2. Non-observance may damage the sinusoidal filter. Caution Using sinusoidal filters not approved by SIEMENS for SINAMICS can damage/destroy the Power Modules or Motor Modules. Caution The surface temperature of the sinusoidal filters may exceed 80°C.
The connecting cables to the Power Module or Motor Module must be kept as short as possible (max. 5 m). Caution When using motor reactors that SIEMENS has not approved for SINAMICS, then these can thermally damage the reactor. Caution The surface temperature of the motor reactors can exceed 80 °C.
Motor-Side Power Components 6.2 Motor reactors 6.2.3 Dimension drawing Mounting hole Type 1 Type 2 Fig. 6-3 Dimension drawing of motor reactor Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 137
2AE38-4AA0 2AE41-0AA0 2AE41-4AA0 Connection type Type 1 Type 1 Type 1 Type 1 hmax 84.5 84.5 79.5 94.5 Dimensions n1 and n2 correspond to the drill hole spacing Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 138
2AH38-1AA0 2AH41-1AA0 2AH41-3AA0 Connection type Type 1 Type 1 Type 1 Type 1 hmax 134.5 79.5 94.5 94.5 Dimensions n1 and n2 correspond to the drill hole spacing Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
- PE Max. permissible cable 300 (shielded) length between motor 450 (unshielded) reactor and motor Degree of protection IP00 IP00 IP00 IP00 Dimensions Width Height Depth Weight, approx. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 140
- PE Max. permissible cable 300 (shielded) length between motor 450 (unshielded) reactor and motor Degree of protection IP00 IP00 IP00 IP00 Dimensions Width Height Depth Weight, approx. Chassis Power Units Liquid Cooled 6-10 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
When a dv/dt filter with Voltage Peak Limiter is used, the pulse frequency of the Power Modules or Motor Module must not exceed 2.5 kHz or 4 kHz. Setting a higher pulse frequency could cause irreparable damage to the dv/dt filter. Chassis Power Units Liquid Cooled 6-11 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
• cable to the dv/dt reactor to 1U2, 1V2, 1W2. Failure to connect the terminals correctly could damage the voltage limiting network. Caution dv/dt filters with Voltage Peak Limiter that SIEMENS has not approved for SINAMICS might sustain thermal damage when used in a SINAMICS unit. Caution The surface temperature of the dv/dt reactors can exceed 80 °C.
Interface description Fig. 6-4 Overview of voltage limiting network interfaces, type 1 DCPS, DCNS 1U2, 1V2, 1W2 Fig. 6-5 Overview of voltage limiting network interfaces, type 2 Chassis Power Units Liquid Cooled 6-14 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 145
Motor-Side Power Components 6.3 dv/dt filter with Voltage Peak Limiter Fig. 6-6 Overview of voltage limiting network interfaces, type 3 Chassis Power Units Liquid Cooled 6-15 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Motor Motor Module DC link DCPS DCNS Voltage limiting network Fig. 6-8 Connecting the dv/dt filter with Voltage Peak Limiter for versions with two dv/dt reactors Chassis Power Units Liquid Cooled 6-16 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 147
2 x 120 Note The connections should be kept as short as possible. The maximum cable length for the specified connections is 5 m in each case. Chassis Power Units Liquid Cooled 6-17 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Motor-Side Power Components 6.3 dv/dt filter with Voltage Peak Limiter 6.3.5 Dimension drawing of dv/dt reactor Mounting hole Fig. 6-9 Dimension drawing of dv/dt reactor Chassis Power Units Liquid Cooled 6-18 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 149
10.5 x 14 10.5 x 14 152.5 152.5 hmax M12 (15 x 22) M12 (15 x 22) Dimensions n1 and n2 correspond to the drill hole spacing Chassis Power Units Liquid Cooled 6-19 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 150
14 x 18 152.5 hmax M12 (15 x 22) M12 (15 x 22) M12 (15 x 22) Dimensions n1 and n2 correspond to the drill hole spacing Chassis Power Units Liquid Cooled 6-20 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
6.3.6 Dimension drawing of voltage limiting network Fig. 6-10 Dimension drawing of voltage limiting network, type 1 Fig. 6-11 Dimension drawing of voltage limiting network, type 2 Chassis Power Units Liquid Cooled 6-21 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 152
Motor-Side Power Components 6.3 dv/dt filter with Voltage Peak Limiter Fig. 6-12 Dimension drawing of voltage limiting network, type 3 Chassis Power Units Liquid Cooled 6-22 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 153
Supply voltage: 500 V – 690 V 6SL3000-2DH31-0BA0 Type 1 6SL3000-2DH31-5BA0 Type 1 6SL3000-2DH32-2BA0 Type 2 6SL3000-2DH33-3BA0 Type 2 6SL3000-2DH35-8BA0 Type 3 6SL3000-2DH38-1BA0 Type 3 6SL3000-2DH41-3BA0 Type 3 Chassis Power Units Liquid Cooled 6-23 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Terminal 70 mm² Terminal 70 mm² - PE Terminal 35 mm² Terminal 35 mm² Degree of protection IP00 IP00 IP00 IP00 Dimensions Width Height Depth Weight, approx. Chassis Power Units Liquid Cooled 6-24 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 155
Width Height 1312.5 1312.5 1312.5 1312.5 Depth Weight, approx. Two dv/dt reactors are required for these Motor Modules. The technical specifications provided apply to one dv/dt reactor. Chassis Power Units Liquid Cooled 6-25 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 157
For versions with 2 dv/dt reactors, the cable lengths specified in the table must not be doubled. Two dv/dt reactors are required for these Motor Modules. The technical specifications provided apply to one dv/dt reactor. Chassis Power Units Liquid Cooled 6-27 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 158
Motor-Side Power Components 6.3 dv/dt filter with Voltage Peak Limiter Chassis Power Units Liquid Cooled 6-28 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
7.1.1 General The modular concept of SINAMICS S120 allows a wide range of potential device combinations. For this reason, it is impossible to describe each individual combination. This section instead aims to provide some basic information and general rules on the basis of which special device combinations can be physically constructed and to ensure electromagnetic compatibility.
Safety regulations governing shock protection must be observed. See also EN 60204-1. Caution To ensure that the entire system works properly, you are advised to use the original Siemens accessories from catalog D21.1. Before commissioning, check the tightening torque of all the terminal screws.
Degrees of protection provided by enclosures (IP code) EN 61800–3 Adjustable speed electrical power drive systems Part 3: EMC product standard including specific test methods UL 508C Power conversion equipment Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
It specifies requirements for converters with operating voltages of less than 1000 V. Different environments and categories are defined depending on where the system is installed. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 163
Rated voltage <1000 V; use in environment 2 only. • Category C4: Rated voltage ≥1000 V or for rated currents ≥400 A in complex systems in environment 2. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
EMC planning The Basic Line Module infeeds when combined with the appropriate line reactor comply with the interference emission limits stipulated in EN 61800-3 for the second environment (industrial). Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 165
EMC measures address not only environmental influences outside the cabinet but also the effect of the devices within the cabinet. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Unshielded cables can be used within a zone. All bus and signal cables that leave the cabinet must be shielded. Fig. 7-4 Dividing a drive system into zones Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Connect to cabinet enclosure on both sides ensuring good conductivity and Shielding bus maximum contact area! Cable propping bar Fig. 7-5 Shield connection for motor cable at cabinet inlet Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 168
Shielding effects can also be achieved by grounding reserve cores at both ends. If the SINAMICS S120 chassis components are supplied externally with 230 V AC and 24 V DC, these supplies must not be used for multiple consumers that are physically separated from each other in different cabinets.
Contactors, relays, solenoid valves, electrical operating hour counters, and so on in the cabinet must be connected to anti-interference elements. RC elements, diodes, or varistors can be used for this purpose. They must be connected on the appropriate coil. Chassis Power Units Liquid Cooled 7-11 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
The shielding between the motor and the Power Module or Motor Module must not be interrupted by additional components (e.g. fuses, contactors, reactors, or filters). Automation devices and SINAMICS S120 devices should be connected to different power supply networks. If only a joint supply is available, the automation devices used should be isolated from the supply by means of isolating transformers.
If the mounting surface comprises more than one mounting plate, these must be connected conductively over the greatest possible surface area. If the components are installed individually, they must be grounded individually too. Chassis Power Units Liquid Cooled 7-13 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Cabinet Design and EMC 7.6 Horizontal installation Horizontal installation SINAMICS S120 Liquid Cooled units can operate in a vertical position with the unit resting on its rear panel. To prevent heat concentrations inside the units in this mounting position, an external fan needs to be installed which is capable of removing heated air from the devices.
Page 173
If the specified fan is not available, an alternative fan can be used provided that its characteristic is higher than that of the minimum fan recommended. Data sheets for the recommended minimum fan with characteristic are available on request from EBM-Papst. Chassis Power Units Liquid Cooled 7-15 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 174
The coolant connection must be designed to prevent any coolant leakage into the unit. It is advisable to empty the coolant hoses before connecting them and to plug the heatsink before removing the coolant hoses. Chassis Power Units Liquid Cooled 7-16 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
The materials used comply with the minimum requirements stipulated in Section 8.3. 3. Semi-open cooling circuit Oxygen can be transferred to the coolant only via the pressure compensator, otherwise as for 1. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 176
• To prevent blockages and corrosion, it is advisable to install an additional flushback filter in the circuit (so that residues can be rinsed out when the system is running). Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
T primary inlet T primary Inspection glass return Dirt trap, ≤ 100 µm Heat exchanger, copper T secondary Fig. 8-1 Recommendations for a closed cooling circuit Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 178
Ideally stainless steel, but a copper heat exchanger can be used as an alternative in closed circuits. 11. Bypass valve May be necessary to protect against condensation. 12. Coolant See Section 8.2 Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
>3 m protected metals Hose Dirt trap, ≤ 100 µm Fig. 8-2 Recommendations for an open cooling circuit Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
The maximum differential pressure across a heatsink is 200 kPa; higher differential pressures significantly increase the risk of cavitation and abrasion (Fig. 8-4). Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 182
• The risk of cavitation and abrasion increases as a result of the high total volumetric flow. • It is not possible to connect SINAMICS S120 in series because the total volumetric flow inherent to any constellation of series connection requires system pressures in the 600 kPa range or above.
Page 183
Differential pressure as a function of volumetric flow for Basic Line Module, frame size FBL Fig. 8-6 Differential pressure as a function of volumetric flow for Basic Line Module, frame size GBL Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 184
FXL Fig. 8-8 Differential pressure as a function of volumetric flow for Power Module frame size GL, Active Line Module, and Motor Module, frame size GXL Chassis Power Units Liquid Cooled 8-10 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 185
Differential pressure as a function of volumetric flow for Active Line Module, Motor Module, frame size HXL Fig. 8-10 Differential pressure as a function of volumetric flow for Active Line Module, Motor Module, frame size JXL Chassis Power Units Liquid Cooled 8-11 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
This eliminates potential differences and thus the risk of electrochemical corrosion. A PE bar must be installed in every cabinet (including the recooling system) and the individual bars then interconnected. Chassis Power Units Liquid Cooled 8-12 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
This value is too high for the heatsinks which may sustain serious damage if inhibitors are not added! Note We recommend that use is made of Nalco's services (Manufacturer: Nalco) for analyzing the water quality at the plant site. Chassis Power Units Liquid Cooled 8-13 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Inhibitors can be used only in water with the properties defined in Section 8.2 which must not contain any magnesium carbonate. Control kits can be ordered from Nalco to check the inhibitor concentration. Chassis Power Units Liquid Cooled 8-14 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 189
Biocides and Antifrogen N must not be mixed. Antifrogen N has a biocidal effect even at the minimum required concentration of >20 %. Chassis Power Units Liquid Cooled 8-15 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
PE/EPDM supplied by Telle) Seals Pipes, valves Use of Viton, AFM34, EPDM is recommended. and fittings Hose connections Pipe-hose Secure with clips conforming to DIN2817, available, e.g. from Telle. transition Chassis Power Units Liquid Cooled 8-16 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
0 m. Degrees of protection SINAMICS S120 Liquid Cooled units have degree of protection IP20 with the exception of the electrical connections (overall degree of protection IP00).
Page 192
0.0187 0.10 Motor Module JXL, 1025 A (690 V) 0.0210 0.11 Motor Module JXL, 1270 A (690 V) 0.0236 0.12 Recommended fan: Supplied by EBM-Papst, type W2E200-HH38-01 Chassis Power Units Liquid Cooled 8-18 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
8.6 Connection system Connection system The electrical connections on the SINAMICS S120 Liquid Cooled units must be made with cables of the cross-section stipulated in the technical specifications for the relevant device. The coolant connection is made using 3/4'' couplings.
Page 194
Cooling circuit and coolant properties 8.7 Commissioning, service Chassis Power Units Liquid Cooled 8-20 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
When the external power supply or the external 230 V AC auxiliary supply is connected, dangerous voltages are still present in the components even when the main circuit-breaker is open. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
The actual intervals at which maintenance procedures are to be performed depend on the installation conditions (cabinet environment) and the operating conditions. Siemens offers its customers support in the form of a service contract. For further details, contact your regional office or sales office.
When securing connections for current-carrying parts (DC link, motor connections, busbars), you must observe the following tightening torques. Table 9-1 Tightening torques for connecting current-carrying parts Screw Torque 6 Nm 13 Nm 25 Nm 50 Nm Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Caution The busbars and coolant connections which stick out of the module must never be used as handles or support surfaces when the units are transported. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
9.4.1 Replacing the Control Interface Board, Power Module, frame size FL Replacing the Control Interface Board Fig. 9-1 Replacing the Control Interface Board, Power Module, frame size FL Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 200
When dealing with connectors with a lock, make sure that the locking lever is securely engaged once connected. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
9.4.2 Replacing the Control Interface Board, Power Module, frame size GL Replacing the Control Interface Board Fig. 9-2 Replacing the Control Interface Board, Power Module, frame size GL Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 202
When dealing with connectors with a lock, make sure that the locking lever is securely engaged once connected. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
9.4.3 Replacing the Control Interface Board, Motor Module, frame size FXL Replacing the Control Interface Board Fig. 9-3 Replacing the Control Interface Board, Motor Module, frame size FXL Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 204
When dealing with connectors with a lock, make sure that the locking lever is securely engaged once connected. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-10 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Replacing the Control Interface Board, Active Line Module and Motor Module, frame size GXL Replacing the Control Interface Board Fig. 9-4 Replacing the Control Interface Board, Active Line Module and Motor Module, frame size Chassis Power Units Liquid Cooled 9-11 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 206
When dealing with connectors with a lock, make sure that the locking lever is securely engaged once connected. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-12 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Replacing the Control Interface Board, Active Line Module and Motor Module, frame size HXL Replacing the Control Interface Board Fig. 9-5 Replacing the Control Interface Board, Active Line Module and Motor Module, frame size Chassis Power Units Liquid Cooled 9-13 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 208
When dealing with connectors with a lock, make sure that the locking lever is securely engaged once connected. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-14 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Replacing the Control Interface Board, Active Line Module and Motor Module, frame size JXL Replacing the Control Interface Board Fig. 9-6 Replacing the Control Interface Board, Active Line Module and Motor Module, frame size Chassis Power Units Liquid Cooled 9-15 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 210
When dealing with connectors with a lock, make sure that the locking lever is securely engaged once connected. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-16 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Replacing the Control Interface Board, Basic Line Module, frame size FBL Replacing the Control Interface Board Fig. 9-7 Replacing the Control Interface Board, Basic Line Module, frame size FBL Chassis Power Units Liquid Cooled 9-17 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 212
When dealing with connectors with a lock, make sure that the locking lever is securely engaged once connected. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-18 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Replacing the Control Interface Board, Basic Line Module, frame size GBL Replacing the Control Interface Board Fig. 9-8 Replacing the Control Interface Board, Basic Line Module, frame size GBL Chassis Power Units Liquid Cooled 9-19 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 214
When dealing with connectors with a lock, make sure that the locking lever is securely engaged once connected. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-20 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Maintenance and servicing 9.4 Replacing components 9.4.9 Replacing the fan, Power Module, frame size FL Replacing the fan Fig. 9-9 Replacing the fan, Power Module, frame size FL Chassis Power Units Liquid Cooled 9-21 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 216
The tightening torques specified in Table 9-1 must be observed. Carefully re-establish the plug connections and ensure that they are secure. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-22 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Maintenance and servicing 9.4 Replacing components 9.4.10 Replacing the fan, Power Module, frame size GL Replacing the fan Fig. 9-10 Replacing the fan, Power Module, frame size GL Chassis Power Units Liquid Cooled 9-23 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 218
The tightening torques specified in Table 9-1 must be observed. Carefully re-establish the plug connections and ensure that they are secure. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-24 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Maintenance and servicing 9.4 Replacing components 9.4.11 Replacing the fan, Motor Module, frame size FXL Replacing the fan Fig. 9-11 Replacing the fan, Motor Module, frame size FXL Chassis Power Units Liquid Cooled 9-25 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 220
The tightening torques specified in Table 9-1 must be observed. Carefully re-establish the plug connections and ensure that they are secure. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-26 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Replacing the fan, Active Line Module and Motor Module, frame size GXL Replacing the fan Fig. 9-12 Replacing the fan, Active Line Module and Motor Module, frame size GXL Chassis Power Units Liquid Cooled 9-27 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 222
The tightening torques specified in Table 9-1 must be observed. Carefully re-establish the plug connections and ensure that they are secure. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-28 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Replacing the fan, Active Line Module and Motor Module, frame size HXL Replacing the fan Fig. 9-13 Replacing the fan, Active Line Module and Motor Module, frame size HXL Chassis Power Units Liquid Cooled 9-29 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 224
The tightening torques specified in Table 9-1 must be observed. Carefully re-establish the plug connections and ensure that they are secure. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-30 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Replacing the fan, Active Line Module and Motor Module, frame size JXL Replacing the fan Fig. 9-14 Replacing the fan, Active Line Module and Motor Module, frame size JXL Chassis Power Units Liquid Cooled 9-31 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 226
The tightening torques specified in Table 9-1 must be observed. Carefully re-establish the plug connections and ensure that they are secure. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-32 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
9.4 Replacing components 9.4.15 Replacing the fan, Basic Line Module, frame size FBL Replacing the fan Fig. 9-15 Replacing the fan, Basic Line Module, frame size FBL Chassis Power Units Liquid Cooled 9-33 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 228
The tightening torques specified in Table 9-1 must be observed. Carefully re-establish the plug connections and ensure that they are secure. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-34 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
9.4 Replacing components 9.4.16 Replacing the fan, Basic Line Module, frame size GBL Replacing the fan Fig. 9-16 Replacing the fan, Basic Line Module, frame size GBL Chassis Power Units Liquid Cooled 9-35 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 230
The tightening torques specified in Table 9-1 must be observed. Carefully re-establish the plug connections and ensure that they are secure. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-36 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
9.4 Replacing components 9.4.17 Replacing the fan, Active Interface Module, frame size GI Replacing the fan Fig. 9-17 Replacing the fan Active Interface Module, frame size GI Chassis Power Units Liquid Cooled 9-37 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 232
The tightening torques specified in Table 9-1 must be observed. Carefully re-establish the plug connections and ensure that they are secure. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-38 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
9.4 Replacing components 9.4.18 Replacing the fan, Active Interface Module, frame size HI Replacing the fan Fig. 9-18 Replacing the fan Active Interface Module, frame size HI Chassis Power Units Liquid Cooled 9-39 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 234
The tightening torques specified in Table 9-1 must be observed. Carefully re-establish the plug connections and ensure that they are secure. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-40 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
9.4 Replacing components 9.4.19 Replacing the fan, Active Interface Module, frame size JI Replacing the fan Fig. 9-19 Replacing the fan Active Interface Module, frame size JI Chassis Power Units Liquid Cooled 9-41 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 236
The tightening torques specified in Table 9-1 must be observed. Carefully re-establish the plug connections and ensure that they are secure. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-42 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Replacing the Power Supply Board, Power Module, frame size FL Replacing the Power Supply Board Fig. 9-20 Replacing the Power Supply Board, Power Module, frame size FL Chassis Power Units Liquid Cooled 9-43 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 238
The tightening torques specified in Table 9-1 must be observed. Carefully re-establish the plug connections and ensure that they are secure. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-44 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Replacing the Power Supply Board, Power Module, frame size GL Replacing the Power Supply Board Fig. 9-21 Replacing the Power Supply Board, Power Module, frame size GL Chassis Power Units Liquid Cooled 9-45 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 240
The tightening torques specified in Table 9-1 must be observed. Carefully re-establish the plug connections and ensure that they are secure. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-46 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Replacing the Power Supply Board, Motor Module, frame size FXL Replacing the Power Supply Board Fig. 9-22 Replacing the Power Supply Board, Motor Module, frame size FXL Chassis Power Units Liquid Cooled 9-47 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 242
The tightening torques specified in Table 9-1 must be observed. Carefully re-establish the plug connections and ensure that they are secure. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-48 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Replacing the Power Supply Board, Active Line Module and Motor Module, frame size GXL Replacing the Power Supply Board Fig. 9-23 Replacing the Power Supply Board, Active Line Module and Motor Module, frame size Chassis Power Units Liquid Cooled 9-49 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 244
The tightening torques specified in Table 9-1 must be observed. Carefully re-establish the plug connections and ensure that they are secure. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-50 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Replacing the Power Supply Board, Active Line Module and Motor Module, frame size HXL Replacing the Power Supply Board Fig. 9-24 Replacing the Power Supply Board, Active Line Module and Motor Module, frame size Chassis Power Units Liquid Cooled 9-51 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 246
The tightening torques specified in Table 9-1 must be observed. Carefully re-establish the plug connections and ensure that they are secure. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-52 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Replacing the Power Supply Board, Active Line Module and Motor Module, frame size JXL Replacing the Power Supply Board Fig. 9-25 Replacing the Power Supply Board, Active Line Module and Motor Module, frame size Chassis Power Units Liquid Cooled 9-53 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 248
The tightening torques specified in Table 9-1 must be observed. Carefully re-establish the plug connections and ensure that they are secure. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-54 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Replacing the Power Supply Board, Basic Line Module, frame size FBL Replacing the Power Supply Board Fig. 9-26 Replacing the Power Supply Board, Basic Line Module, frame size FBL Chassis Power Units Liquid Cooled 9-55 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 250
The tightening torques specified in Table 9-1 must be observed. Carefully re-establish the plug connections and ensure that they are secure. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-56 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Replacing the Power Supply Board, Basic Line Module, frame size GBL Replacing the Power Supply Board Fig. 9-27 Replacing the Power Supply Board, Basic Line Module, frame size GBL Chassis Power Units Liquid Cooled 9-57 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 252
The tightening torques specified in Table 9-1 must be observed. Carefully re-establish the plug connections and ensure that they are secure. The screwed connections for the protective covers must only be tightened by hand. Chassis Power Units Liquid Cooled 9-58 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
The DC link capacitors are reformed by applying the rated voltage without load for at least 30 minutes at room temperature. Type plate Fig. 9-28 Type plate for an Motor Module Chassis Power Units Liquid Cooled 9-59 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 254
Table 9-2 Year and month of manufacture Character Year of manufacture Character Month of manufacture 2005 1 to 9 January to September 2006 October 2007 November 2008 December Chassis Power Units Liquid Cooled 9-60 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Control Interface Board Computerunterstützte numerische Steuerung Computer Numerical Control Konnektorausgang Connector Output CO/BO Konnektor-/Binektorausgang Connector/Binector Output Mittelkontakt eines Wechselkontaktes Medium contact of a change-over contact Kommunikationsprozessor Communications Processor Chassis Power Units Liquid Cooled 10-1 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 256
Function diagram Firmware Firmware Global-Control-Telegramm (Broadcast- Global Control Telegram (Broadcast- Telegramm) Telegramm) Gerätestammdatei: beschreibt die Merkmale Device master file: describes the features of a eines PROFIBUS-Slaves PROFIBUS slave Chassis Power Units Liquid Cooled 10-2 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 257
National Electrical Manufacturers Association America) Nullmarke Zero Mark Schliesser Normaly Open contact Original Equipment Manufacturer Original Equipment Manufacturer Busstecker für Lichtleiter Optical Link Plug Option Module Interface Option Module Interface Chassis Power Units Liquid Cooled 10-3 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Voltage Sensing Module Variables Drehmoment Variable Torque Werkzeugmaschine Machine tool Erweiterbare Auszeichnungssprache Extensible Markup Language (Standardsprache für Web-Publishing und Dokumentenmanagement) Zwischenkreis DC link PROFIBUS Zustandswort PROFIBUS statusword Chassis Power Units Liquid Cooled 10-5 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 260
List of Abbreviations 10.1 List of Abbreviations Chassis Power Units Liquid Cooled 10-6 SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 262
Active Line Modules ........4-21 Overload capability Basic Line Modules ........4-4 Motor Modules ..........5-21 dv/dt filter with Voltage Peak Limiter .... 6-13 low overload ..........5-21 EMC..............7-2 Chassis Power Units Liquid Cooled SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4...
Page 263
Technical Specifications Dimension Drawing ........6-3 Sinusoidal filter..........6-4 Sinusoidal Filter ........... 6-1 Tightening torques..........9-3 Structure of a drive system with SINAMICS S120 Type plate............9-59 chassis liquid cooled..........1-9 Voltage limiting network System Overview..........1-1 Dimension drawing........6-21...