Siemens SIMATIC ET 200SP HA Equipment Manual

Siemens SIMATIC ET 200SP HA Equipment Manual

Hide thumbs Also See for SIMATIC ET 200SP HA:

Quick Links

SIMATIC
ET 200SP HA
DQ 16x24VDC/0.5A
Equipment Manual
6DL1132-6BH00-0PH1
6DL1132-6BH00-0EH1
10/2021
A5E39265993-AD
Security information
Preface
2D Matrix code (QR code /
EAN code)
Product overview
Terminal
Parameters
Displays and interrupts
Technical specifications
Parameters, diagnostics
messages and address
space
1
2
3
4
5
6
7
8
A
Table of Contents
loading

Summary of Contents for Siemens SIMATIC ET 200SP HA

  • Page 1 Security information Preface 2D Matrix code (QR code / EAN code) SIMATIC Product overview ET 200SP HA DQ 16x24VDC/0.5A Terminal Parameters Equipment Manual Displays and interrupts Technical specifications Parameters, diagnostics messages and address space 6DL1132-6BH00-0PH1 6DL1132-6BH00-0EH1 10/2021 A5E39265993-AD...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    Table of contents Security information..........................5 Preface ..............................7 2D Matrix code (QR code / EAN code) ....................9 Product overview ..........................11 I/O module......................... 11 Accessories ........................12 Output disable switch ......................13 Pulling the I/O module in runtime..................13 Terminal blocks........................
  • Page 4 Table of contents Technical specifications ........................29 Parameters, diagnostics messages and address space ............... 37 Parameter assignment ....................... 37 Parameter assignment and structure of the module/channel parameters......38 Diagnostics messages ......................40 Maintenance events......................42 Address space ........................42 Tables Table A-1 Address space of the DQ 16x24VDC/0.5A HA ................
  • Page 5: Security Information

    Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber...
  • Page 6 Security information DQ 16x24VDC/0.5A Equipment Manual, 10/2021, A5E39265993-AD...
  • Page 7: Preface

    Preface Validity of the documentation This equipment manual describes the following I/O modules: System family I/O module Article No. SIMATIC Distributed I/O System ET 200SP DQ 16x24VDC/0.5A 6DL1132-6BH00-0PH1 SIMATIC Distributed I/O System ET 200SP DQ 16x24VDC/0.5A 6DL1132-6BH00-0EH1 It complements the system manual for the ET 200SP HA Distributed I/O System. Functions that generally relate to the system are described in this manual.
  • Page 8 Preface DQ 16x24VDC/0.5A Equipment Manual, 10/2021, A5E39265993-AD...
  • Page 9: Matrix Code (Qr Code / Ean Code)

    The 2D matrix code on the product is a coded representation of the product-specific article number. Access to product-related information For reading the 2D matrix code, SIEMENS offers an app for mobile use. Information about the app and the download can be found on the Internet: "Mobile use via app (https://support.industry.siemens.com/cs/ww/en/sc/2067)".
  • Page 10 2D Matrix code (QR code / EAN code) DQ 16x24VDC/0.5A Equipment Manual, 10/2021, A5E39265993-AD...
  • Page 11: Product Overview

    Product overview I/O module Definition The DQ 16x24VDC/0.5A I/O module is a digital output module with 16 power outputs for process control. In addition to the technical specifications, this module has the following properties: • Suitable for solenoid valves, DC contactors, and indicator lights •...
  • Page 12: Accessories

    Product overview 4.2 Accessories Description The I/O module consists of the following components: 16 x2 4V DC /0 ,5 DI AG M T 1 DQ .0 + DQ .1+ 3 DQ .2+ DQ .3 + 5 DQ .4 + DQ .5 + 7 DQ .6 + DQ .7+ 9 DQ .0 +...
  • Page 13: Output Disable Switch

    Product overview 4.4 Pulling the I/O module in runtime • Reference identification label • Shield connector • Terminal blocks Output disable switch Definition The output disable switch switches the I/O module load-free. NOTICE Dangerous plant conditions possible (disconnect the load) If you want to pull the I/O module in runtime, you have to press the output disable switch for 3 seconds for the I/O module to be load free (deenergized).
  • Page 14: Terminal Blocks

    Product overview 4.5 Terminal blocks Terminal blocks Definition The terminal blocks provide the process terminals (push-in terminals) for components such as devices to be connected. Description The following terminal blocks are available for the I/O module: Article number Color Description 6DL1193-6TP00-0DH1 6DL1193-6TP00-0BH1 Dark...
  • Page 15: Terminal

    Terminal Pin assignment Definition The pin assignment provides information about the arrangement and marking of the connections when wiring a connector. Note The M terminals are intended exclusively for the 1 or 2-wire connection system. You may not use these terminals as the ground terminals for other devices in the system. Ensure that the total current does not exceed 2A for each M terminal.
  • Page 16: Sample Connection Scheme For 1-Wire Connection

    Terminal 5.2 Sample connection scheme for 1-wire connection Description The pin assignment is structured as follows: Terminal Assignment Terminal Assignment Description DQ a/DQ.0+ DQ a/DQ.1+ DQ a /DQ.n+: Output signal, channel n (0…7) DQ b /DQ.n+: Output signal, channel n (8…15) DQ a/DQ.2+ DQ a/DQ.3+ M: Ground...
  • Page 17: Sample Connection Scheme For 2-Wire Connection

    Terminal 5.4 Schematic circuit diagram Sample connection scheme for 2-wire connection Example Schematic circuit diagram Definition A block diagram contains the schematic representation of individual function blocks. Description The circuit diagram for the I/O module is structured as follows: The supply voltage L+ must be applied to the I/O module at the start of a firmware update and during the firmware update.
  • Page 18 Terminal 5.4 Schematic circuit diagram DQ 16x24VDC/0.5A Equipment Manual, 10/2021, A5E39265993-AD...
  • Page 19: Parameters

    Parameters Parameter types Definition You define and thereby influence the functions supported by the module operation of the I/O module via the parameter types. Module/channel parameters Definition Module/channel parameters are specific parameters whose configuration can affect the entire module or channels. Note Each configuration change resets the corresponding reaction.
  • Page 20: Explanation Of The Module/Channel Parameters

    Parameters 6.3 Explanation of the module/channel parameters Parameters Value range Default Parameter re‐ Efficiency range assignment in Channel activated Enabled Channel • Enabled (Page 22) • Disabled Reaction to CPU STOP Shutdown Channel • Shutdown (Page 22) • Keep last value •...
  • Page 21: Diagnostics Short-Circuit To L

    Parameters 6.3 Explanation of the module/channel parameters Description Both redundant modules measure simultaneously and independently in the process. Both redundant modules form diagnostics, interrupts and process values. 6.3.3 Diagnostics short-circuit to L+ Definition When the digital output is enabled, you can enable diagnostics that report a digital output short circuit to L+.
  • Page 22: Channel Activated

    Parameters 6.3 Explanation of the module/channel parameters 6.3.7 Channel activated Definition Specifies whether a channel is activated or deactivated. 6.3.8 Reaction to CPU STOP Definition Specifies the behavior of the digital output as a reaction to CPU stop or to failure of communication between the interface module and CPU.
  • Page 23 Parameters 6.3 Explanation of the module/channel parameters The potential group also ends if there is a black terminal block next to it. Black terminal blocks are fed individually and cannot be included in potential groups. You can find additional information on the configuration of the potential group in the system manual SIMATIC;...
  • Page 24 Parameters 6.3 Explanation of the module/channel parameters DQ 16x24VDC/0.5A Equipment Manual, 10/2021, A5E39265993-AD...
  • Page 25: Displays And Interrupts

    Displays and interrupts Status and error displays Definition The LED displays are status and error indicators. Diagnostics messages and maintenance events, as well as their possible causes or solutions are described in the diagnostics messages and maintenance events. Diagnostics messages (Page 40). Description The following figure explains the LED displays of the I/O module.
  • Page 26: Leds

    Displays and interrupts 7.2 LEDs LEDs 7.2.1 DIAG LED Definition The DIAG LED provides you diagnostic information. Description The diagnostic display of the DIAG LED is as follows: DIAG LED Meaning The power supply of the ET 200SP HA is disrupted or switched off. Module is not configured.
  • Page 27: Pwr Led

    Displays and interrupts 7.2 LEDs 7.2.3 PWR LED Definition The PWR LED provides you status information about supply voltage L+. Description The PWR LED indicates the following status: PWR LED Meaning Supply voltage L+ missing. Supply voltage L+ present. 7.2.4 Channel status / fault LEDs Definition The channel status and channel fault LEDs provide you information about the status and faults...
  • Page 28: Interrupts

    Displays and interrupts 7.3 Interrupts Interrupts Definition A diagnostics interrupt is an alarm that reports activated events of a device status to the system operator with the appropriate operating authorization (maintenance and service). Description The I/O module generates a diagnostics interrupt at the following events: •...
  • Page 29: Technical Specifications

    Technical specifications Technical specifications of the DQ 16x24VDC/0.5A HA Article number 6DL1132-6BH00-0PH1 General information Product type designation DQ 16x24VDC/0.5A HA Firmware version V1.0 • FW update possible Usable terminal block TB type H1, M1 and N0 Color code for module-specific color identifica‐ CC02 tion plate Product function...
  • Page 30 Technical specifications Article number 6DL1132-6BH00-0PH1 Digital outputs, parameterizable Short-circuit protection Yes; Ensure sufficient low-resistance cable routing to the sensor/actuator in order to attain the re‐ sponse threshold. Depending on the cable cross- section used, there may be constraints regarding the usable length of cable. •...
  • Page 31 Technical specifications Article number 6DL1132-6BH00-0PH1 Cable length 1 000 m • shielded, max. 600 m • unshielded, max. Interrupts/diagnostics/status information Diagnostics function Diagnoses • Monitoring the supply voltage Yes; channel by channel • Wire-break Yes; channel by channel • Short-circuit to M Yes;...
  • Page 32 Technical specifications Article number 6DL1132-6BH00-0EH1 General information Firmware version V1.0 • FW update possible Usable terminal block TB type H1 and M1 Color code for module-specific color identifica‐ CC02 tion plate Engineering with V8.0 • SPPA-T3000 can be configured/integrated from version Operating mode •...
  • Page 33 Technical specifications Article number 6DL1132-6BH00-0EH1 • on lamp load, max. Load resistance range 48 Ω • lower limit 12 kΩ • upper limit Output current 0.7 mA; Test current for wire-break diagnostics; this • for signal "0" residual current, max. value is doubled in the case of IO redundancy Output delay with resistive load 50 µs...
  • Page 34 Technical specifications Article number 6DL1132-6BH00-0EH1 Yes; green PWR LED • Monitoring of the supply voltage (PWR-LED) Yes; green LED • Channel status display Yes; red LED • for channel diagnostics Yes; green/red DIAG LED • for module diagnostics Potential separation Potential separation channels •...
  • Page 35 Technical specifications Note You can avoid the derating by deactivating channels 8 to 16. Test current for signal state "0" Note If the "Check for wire break" parameter is activated, a test current flows, even if the signal state for the output is "0" (singular mode: Approx. 700 μA, redundant operation: approx. 1.4 mA). Cycle time The cycle time describes the time slice in which signals from the inputs are acquired and processed.
  • Page 36 Technical specifications DQ 16x24VDC/0.5A Equipment Manual, 10/2021, A5E39265993-AD...
  • Page 37: Parameters, Diagnostics Messages And Address Space

    Parameters, diagnostics messages and address space Parameter assignment Parameter assignment in the user program You can reconfigure individual channels of the module in RUN without this having an effect on the other channels. Changing parameters in RUN The parameters are transferred to the module with the "WRREC" instruction via data record 128. Output parameter STATUS If errors occur when transferring parameters with the "WRREC"...
  • Page 38: Parameter Assignment And Structure Of The Module/Channel Parameters

    Parameters, diagnostics messages and address space A.2 Parameter assignment and structure of the module/channel parameters Parameter assignment and structure of the module/channel parameters Structure of data record 128 Data record 128 has a length of 44 bytes. It contains the channel parameters of the 16 channels. DQ 16x24VDC/0.5A Equipment Manual, 10/2021, A5E39265993-AD...
  • Page 39 Parameters, diagnostics messages and address space A.2 Parameter assignment and structure of the module/channel parameters Header information and module parameters The following figure shows the configuration of the header information and module parameters. DQ 16x24VDC/0.5A Equipment Manual, 10/2021, A5E39265993-AD...
  • Page 40: Diagnostics Messages

    Parameters, diagnostics messages and address space A.3 Diagnostics messages Channel parameters Each channel parameter block contains the cable parameters for the digital output (4 bytes). The following figure shows the configuration of the channel parameters for channels 0 to 15. x = 12 + (channel number * 2);...
  • Page 41 Parameters, diagnostics messages and address space A.3 Diagnostics messages entire module. Only the corresponding digital output is affected by diagnostics messages, which refer to individual channels. Diagnostics Error Assign‐ Meaning Remedy message code ment Wire break Channel Actuator connection has impedance too high Use another type of actuator or wiring, for example, use conduc‐...
  • Page 42: Maintenance Events

    Parameters, diagnostics messages and address space A.5 Address space Maintenance events Maintenance events A maintenance event is generated for each maintenance required identified. The MT LED lights up on the module. Maintenance messages have no direct effect on the function of the module or digital outputs. Maintenance Error Assign‐...
  • Page 43: Table A-1 Address Space Of The Dq 16X24Vdc/0.5A Ha

    Parameters, diagnostics messages and address space A.5 Address space Address space The following figure shows the mapping of the address space of the DQ 16x24VDC/0.5A HA. Table A-1 Address space of the DQ 16x24VDC/0.5A HA IB x + AB x + QDI7 QDI6 QDI5...
  • Page 44 Parameters, diagnostics messages and address space A.5 Address space DQ 16x24VDC/0.5A Equipment Manual, 10/2021, A5E39265993-AD...