Honeywell Gamewell Velociti AMM-4F Installation And Maintenance Instructions

Honeywell Gamewell Velociti AMM-4F Installation And Maintenance Instructions

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
Velociti
Series
®
AMM-4F Monitor Module
Specifications
Normal Operating Voltage:
Maximum Current Draw:
Average Operating Current:
EOL Resistance:
Maximum IDC Wiring Resistance:
Maximum IDC Voltage:
Maximum IDC Current:
Temperature Range:
Humidity:
Dimensions:
Accessories:
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The AMM-4F Monitor Module is intended for use in intelligent, two-wire sys-
tems, where the individual address of each module is selected using the built-
in rotary switches. It provides either a 2-wire or 4-wire fault tolerant initiating
device circuit (IDC) for normally open contact fire alarm and supervisory de-
vices, or either normally open or normally closed security devices. The mod-
ule has a panel controlled LED indicator.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Gamewell-FCI system control panel (list available from Gamewell-FCI).
FIGURE 1. CONTROL AND INDICATORS:
15 to 32 VDC
5.0 mA (LED on)
375µA (Velociti Mode); 350µA (CLIP Mode); 600µA; (communicating IDC shorted)
47K Ohms
1,500 Ohms
11 Volts
450µA
32°F to 120°F (0°C to 49°C)
10% to 93% Non-condensing
4
1
˝ H x 4˝ W x 1
1
˝ D (Mounts to a 4˝ square by 2
2
4
SMB500 Electrical Box
C1067-00
1
˝ deep box.)
8
MOUNTING
The AMM-4F mounts directly to 4-inch square electrical boxes (see Figure 2).
The box must have a minimum depth of 2
cal boxes (SMB500) are available from Gamewell-FCI.
FIGURE 2. MODULE MOUNTING:
NOTE: For UL Listed security installations, the AMM-4F must be mounted
within the control panel enclosure.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. This module is intended for power limited wiring only.
1.
Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2.
Set the address on the module per job drawings.
3.
Secure module to electrical box (supplied by installer), shown in Figure 2.
1
12 Clintonville Road, Northford, CT 06472
(203) 484-7161; Fax: (203) 484-7118
www.gamewell-fci.com
1
inches. Surface mounted electri-
8
ISOLATED
QUADRANT
I56-3553-003
C1066-00
02-10
loading

Summary of Contents for Honeywell Gamewell Velociti AMM-4F

  • Page 1 INSTALLATION AND MAINTENANCE INSTRUCTIONS Velociti Series ® 12 Clintonville Road, Northford, CT 06472 (203) 484-7161; Fax: (203) 484-7118 AMM-4F Monitor Module www.gamewell-fci.com Specifications Normal Operating Voltage: 15 to 32 VDC Maximum Current Draw: 5.0 mA (LED on) Average Operating Current: 375µA (Velociti Mode);...
  • Page 2 INSTALL CONTACT CLOSURE DEVICES PER ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED MANUFACTURER’S INSTALLATION INSTRUCTIONS. C1022-00 Velociti ® , Gamewell-FCI ® , System Sensor ® , and Honeywell ® are registered trademarks of Honeywell International, Inc. I56-3553-003 ©2017 Honeywell. 02-10...