Troubleshooting Without Error Code; Indoor Unit-No Power - Fujitsu AUXG07KVLA Manual

2-unit multi-split type
Hide thumbs Also See for AUXG07KVLA:
Table of Contents

3. Troubleshooting without error code

3-1. Indoor unit—No power
Forecast of cause
Attention
An indoor unit and an outdoor unit are connected, and a power supply has be connected to an in-
door unit.
Check point 1. Check installation condition
Is the circuit breaker on or off?
Check loose or removed connection cable.
-> If abnormal condition is found, correct it by referring to the installation manual or the "DESIGN &
TECHNICAL MANUAL".
Check point 2. Check external cause at indoor and outdoor (voltage drop or noise)
Instant drop: Check if there is a large load electric apparatus in the same circuit.
Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
Check point 3. Check electrical components
Check the voltage of power supply.
Check if AC 198 to 264 V appears at outdoor unit terminal 1—2.
-> If no, go to
"Check point 1"
Check fuse in filter PCB.
If fuse is open, check if the wiring between terminal and filter PCB is loose, and replace fuse.
Check varistor in filter PCB.
If varistor is defective, there is a possibility of an abnormal power supply.
Check the correct power supply and replace varistor.
Upon checking the normal power supply, replace varistor.
3-1. Indoor unit—No power
and
"Check point
2".
End
- (03-58) -
Power supply failure
External cause
Electrical components defective
3. Troubleshooting without error code
+
-