PLEASE LEAVE THIS MANUAL WITH THE UNIT AFTER INSTALLATION
This cylinder is manufactured and approved in accordance with EN 12897 : 2006
Thank-you for purchasing the PAW unvented hot water cylinder.
The PAW is an unvented hot water cylinder in capacities 200 and 300 litres. Its energy efficiency as defined by standing
heat losses is the best in its class and will save the householder significant energy costs over the lifetime of the cylinder.
This manual gives detailed advice for installation and should be read carefully prior to fitting any unvented unit. PAW cylin-
ders are not suitable for gravity fed primary systems. In known hard water regions, precautions should be taken to prevent
limescale formation in hot water cylinders, in accordance with Building Regulation Part L, Domestic Heating Compliance
Guide.
This cylinder must be installed by a competent person and be installed in compliance with the Installation and Maintenance
Instructions, all current legislation, codes of practice and regulations governing the installation of unvented hot water cylin-
ders in force at the date of installation.
PLEASE READ THIS MANUAL BEFORE INSTALLATION AND LEAVE WITH THE UNIT.
THE MANUAL AND ATTACHED LOGBOOK SERVE AS THE CYLINDER GUARANTEE.
Installation Manual
PAW-TD20C1E5-UK
PAW-TD30C1E5-UK
PAW-TD30C1E5HI-UK
Contents
1. General information ........................... 2
3. Pipe connections ............................... 4
5. Draining and Flushing ........................ 5
6. Electrical installation .......................... 5
7. Safety and Servicing .......................... 9
8. Fault finding ..................................... 10
10. Warranty .......................................... 12
11. Log book .......................................... 13
Page no.
1
Table of Contents
loading

Summary of Contents for Panasonic PAW-TD20C1E5-UK

  • Page 1: Table Of Contents

    PLEASE LEAVE THIS MANUAL WITH THE UNIT AFTER INSTALLATION Installation Manual PAW-TD20C1E5-UK PAW-TD30C1E5-UK PAW-TD30C1E5HI-UK Contents Page no. 1. General information ......2 2. Preparation of installation area ..4 3. Pipe connections ....... 4 4. Commissioning and filling up ..... 5 5.
  • Page 2: General Information

    1. General information 1.1 Health and Safety regulations Handling Operations Regulations 1992 defines manual handling as: “any transporting or supporting of a load (includ- ing the lifting, putting down, pushing, pulling, carrying or moving thereof) by hand or bodily force” The Regulations set no specific requirements such as weight limits.
  • Page 3 General Layout PAW-TD20C1E5-UK PAW-TD30C1E5-UK PAW-TD30C1E5HI-UK No. Key Return HP 3/4” BSP (Flow Boiler 3/4” BSP) Flow HP 3/4” BSP (Return Boiler 3/4” BSP) Pressure Reducing Valve Multibloc (2.1 bar) includes Item 4 Expansion Relief Valve (8 bar) Temperature and Pressure Relief Valve...
  • Page 4: Preparation Of Installation Area

    2. Preparation of installation area 2.1 Positioning the unit The PAW cylinder should be fitted level on a hard surface with sufficient load strength to take the full weight of the cylinder (see technical data table page 11). The unit has 3 built-in adjustable feet to allow fine adjustment of the water heater.
  • Page 5: Commissioning And Filling Up

    3.6 Primary Flow and Return and Motorised valve 3.6.1 The heat pump/boiler primary flow and return connections should be made connections 1 & 2. The motorized valve can be connected to either the primary flow or return pipe. The primary flow and return fittings are 3/4’’ BSP female.
  • Page 6 6.2 Motorised valve To comply with regulations governing the installation of indirect unvented cylinders, a motorised valve must be fitted in the primary pipework. The motorised valve will act as a positive energy cut-out should the additional cylinder thermal cut-out operate. The motorised valve will also control the temperature of the domestic stored water via the additional cylinder thermostat.
  • Page 7 S-plan Wiring PAW cylinders can be Wiring for Standard Heat pump fitted with all types of boilers and heat pumps operating using room and cylinder thermostats. Cylinder Please follow upper diagram: Zone Valve (DHW) Zone Valve (Htg) Room Thermostat (supplied) ‘Wiring for Standard Heat Pump’.
  • Page 8 Y-plan Wiring PAW cylinders can be fitted with all types of boilers and Wiring for Standard Heat pump heat pumps operating using room and cylinder thermostats. Please follow upper diagram: Mid Position Valve Cylinder Thermostat (supplied) Zone Valve (DHW) Room ‘Wiring for Standard Heat Pump’.
  • Page 9: Safety And Servicing

    7. Safety and servicing Maintenance must be carried out by a competent person. 7.1 Safety Cut-out The safety cut-out operates if: 1. Wiring is incorrect. 2. The immersion heater thermostat or additional cylinder thermostat fails. 3. Thermostat is set too high. 4.
  • Page 10: Fault Finding

    8. Fault Finding Guide FAULT POSSIBLE CAUSE SOLUTION No water flow from hot taps. 1. Mains supply off. 1. Check and open stopcock. 2. Strainer blocked. 2. Turn off water supply. Remove strainer and clean (see Servicing Procedure page 10). Water from hot taps is cold.
  • Page 11: Technical And Performance Specs

    Technical data PAW- PAW- PAW- Description Unit TD20C1E5-UK TD30C1E5-UK TD30C1E5HI-UK Actual capacity of the water tank at 20°C Outer diameter of the tank Height of the appliance 1270 1750 1750 Gross weight of the appliance Net weight of appliance once filled with sanitary water Material of element incoloy 825 incoloy 825...
  • Page 12: Warranty

    Warranty 1. Scope The Distributor warrants for 2 years from the date of purchase, that the Product will: i) conform to specification, ii) be free from defects in materials and workmanship, subject to conditions below. The warranty only applies to Products purchased by a consumer, that has been installed for private use and that has been sold by the Distributor or a designated retailer where the Products have been originally sold by the Distributor.
  • Page 13: Log Book

    The code of practice for the installation, commissioning & servicing of mains pressure hot water storage Installation,Commissioning Installation,Commissioning and Service Record Log Book and Service Record Log Book CUSTOMER DETAILS NAME ADDRESS TEL No. IMPORTANT 1. Please, keep the Log Book in a safe place for future reference. 2.
  • Page 14 APPLIANCE & TIME CONTROL DETAILS MANUFACTURER MODEL CAPACITY litres SERIAL No. TYPE UNVENTED TIME SWITCH TIME CONTROL PROGRAMMER COMMISSIONING PROCEDURE INFORMATION BOILER PRIMARY SETTINGS (INDIRECT HEATING ONLY) ALL BOILERS IS THE PRIMARY A SEALED OR OPEN VENTED SYSTEM? SEALED OPEN WHAT IS THE INDIRECT HEAT SOURCE FLOW TEMPERATURE? ALL MAINS PRESSURISED SYSTEMS WHAT IS INCOMING STATIC COLD WATER PRESSURE AT THE INLET TO THE...
  • Page 15 SERVICE INTERVAL RECORD It is recommended that your hot water system is serviced regularly and that your service engineer completes the appropriate Service Interval Record below. SERVICE PROVIDER Before completing the appropriate Service Interval Record below, please ensure you have carried out the service as described in the manufacturer’s instructions and in compliance with all relevant codes of practice.