Siemens SIMATIC S7-1500 Manual
Hide thumbs Also See for SIMATIC S7-1500:

Quick Links

Table of Contents
loading

Summary of Contents for Siemens SIMATIC S7-1500

  • Page 2 CPU 1511-1 PN (6ES7511-1AK02-0AB0) Preface S7-1500 / ET 200MP Documentation Guide SIMATIC Product overview Connecting up S7-1500 CPU 1511-1 PN Interrupts, error messages, (6ES7511-1AK02-0AB0) diagnostics and system alarms Equipment Manual Technical specifications Dimensional drawing 05/2021 A5E40869673-AB...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Preface

    Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats.
  • Page 5 This information is provided by the Siemens Industry Online Support in the Internet (https://support.industry.siemens.com). Industry Mall The Industry Mall is the catalog and order system of Siemens AG for automation and drive solutions on the basis of Totally Integrated Automation (TIA) and Totally Integrated Power (TIP).
  • Page 6: Table Of Contents

    S7-1500 / ET 200MP Documentation Guide ................... 6 Product overview ........................... 8 New functions ........................8 Area of application of the SIMATIC S7-1500 CPUs ............... 10 Hardware properties ......................19 Firmware functions ......................21 Operating and display elements ..................25 2.5.1...
  • Page 7: S7-1500 / Et 200Mp Documentation Guide

    This arrangement enables you to access the specific content you require. Basic information The System Manual and Getting Started describe in detail the configuration, installation, wiring and commissioning of the SIMATIC S7-1500 and ET 200MP systems. The STEP 7 online help supports you in the configuration and programming. Device information Product manuals contain a compact description of the module-specific information, such as properties, wiring diagrams, characteristics and technical specifications.
  • Page 8 S7-1500 / ET 200MP Documentation Guide Manual Collection S7-1500/ET 200MP The Manual Collection contains the complete documentation on the SIMATIC S7-1500 automation system and the ET 200MP distributed I/O system gathered together in one file. You can find the Manual Collection on the Internet (https://support.industry.siemens.com/cs/ww/en/view/86140384).
  • Page 9: Product Overview

    Secure PG/HMI communi- With STEP 7 and WinCC as of Version Secure and standardized crea- Communication func- cation V17, SIMATIC S7-1500 CPUs and ET tion or assignment of PLC tion manual 200 CPUs from firmware version 2.9 communication certificates (https://support.industr support innovated and standardized y.siemens.com/cs/ww/...
  • Page 10 CPU into an existing IT tion manual configuration via a DHCP server. network without having to (https://support.industr make additional changes to y.siemens.com/cs/ww/ The CPU uses a client ID for identifi- the PROFINET interface. en/view/59192925) cation on the DHCP server. The following parameters can be obtained: •...
  • Page 11: Area Of Application Of The Simatic S7-1500 Cpus

    SIMATIC S7-1500 is the modular control system for a wide variety of automation applications in discrete automation. SIMATIC S7-1500 is the cost-effective and convenient solution for a broad range of tasks and offers the following advantages: • Modular, fanless design •...
  • Page 12 High industrial suitability due to the high resistance to EMC, shock and vibration enable universal use of the SIMATIC S7-1500, S7-1500R/H and S7-1500T automation systems. Performance segments of the CPUs The CPUs can be used for smaller and mid-range applications, as well as for the high-end range of machine and plant automation.
  • Page 13 Product overview 2.2 Area of application of the SIMATIC S7-1500 CPUs Performance segment PROFIBUS PROFINET PROFINET Basic Work Pro- interfaces IO RT/IRT IO RT PROFINET memory cessing interfaces interface functional- time for bit oper- ations CPU 1518- Standard CPU for high-...
  • Page 14 Product overview 2.2 Area of application of the SIMATIC S7-1500 CPUs Table 2- 3 Compact CPUs Performance segment PROFIBUS PROFINET PROFINET Basic Work Pro- interfaces IO RT/IRT IO RT PROFINET memory cessing time for interfaces interface functional- bit oper- ations CPU 1511C-1 PN Compact CPU for small 1.175 MB...
  • Page 15 Product overview 2.2 Area of application of the SIMATIC S7-1500 CPUs Performance segment PROFIBUS PROFINET PROFINET Basic Work Pro- interfaces IO RT/IRT IO RT PROFINET memory cessing interfaces interface functional- time for bit oper- ations CPU 1518F- Fail-safe CPU for high-...
  • Page 16 Product overview 2.2 Area of application of the SIMATIC S7-1500 CPUs Performance segment PROFIBUS PROFINET PROFINET Basic Work Pro- interfaces IO RT/IRT IO RT PROFINET memory cessing interfaces interface functional- time for bit oper- ations CPU 1518T- Technology CPU for...
  • Page 17 For effective commissioning, diagnostics and fast optimization of drives and controls, the SIMATIC S7-1500 controller series offers extensive trace functions for all CPU tags. In addition to drive integration, the SIMATIC S7-1500 controller series has a PID compact closed-loop controller; easy-to-configure blocks allow automatic optimization of the controller parameters for optimum control quality.
  • Page 18 Product overview 2.2 Area of application of the SIMATIC S7-1500 CPUs Other technology functions Technology modules also implement functions such as high-speed counting, position detection, measuring functions and pulse generators (PTO, PWM and frequency output). With the CPU 1511C-1 PN and CPU 1512C-1 PN compact CPUs, these functions are already integrated and can be implemented without additional technology modules.
  • Page 19 DIN rail is implemented in the rail of the SIMATIC S7-1500. The CPUs of the SIMATIC S7-1500 product series can be expanded centrally and in a modular fashion with signal modules. Space-saving expansion enables flexible adaptation to each application.
  • Page 20: Hardware Properties

    Product overview 2.3 Hardware properties Hardware properties Article number 6ES7511-1AK02-0AB0 View of the module The following figure shows a CPU 1511-1 PN. Figure 2-1 CPU 1511-1 PN Note Protective film Note that a protective film is attached to the display of the CPU when shipped from the factory.
  • Page 21 CPU 1511-1 PN has the following technical properties: Property Description Additional information CPU display All CPUs of the SIMATIC S7-1500 product series feature • S7-1500, ET 200MP system man- a display with plain text information. The display pro- vides information on order numbers, firmware version (http://support.automation.sieme...
  • Page 22: Firmware Functions

    The system automatically generates the messages for Diagnostics function manual nostics the system diagnostics and outputs these messages via (https://support.industry.siemens.co a programming device/PC, HMI device, the Web server m/cs/ww/en/view/59192926) or the integrated display. System diagnostics infor- mation is also available when the CPU is in STOP mode.
  • Page 23 RT (real time) RT prioritizes PROFINET IO telegrams over standard PROFINET function manual telegrams. This ensures the required determinism in the (https://support.industry.siemens.co automation technology. In this process the data is m/cs/ww/en/view/49948856) transferred via prioritized Ethernet telegrams. IRT (isochronous real time) A reserved bandwidth within the send clock is available for IRT data.
  • Page 24 S7-1500 CPUs support the controlled positioning and S7-1500T Motion Control function traveling of axes via S7-1500 Motion Control functions manuals by means of the following technology objects: (https://support.industry.siemens.co m/cs/ww/en/view/109751049) Speed-controlled axes, positioning axes, synchronized axes, external encoders, cams, cam tracks and measur- ing inputs.
  • Page 25 Know-how protection The know-how protection protects user blocks against S7-1500, ET 200MP system manual unauthorized access and modifications. (https://support.industry.siemens.co m/cs/ww/en/view/59191792) Copy protection Copy protection links user blocks to the serial number of the SIMATIC memory card or to the serial number of the CPU.
  • Page 26: Operating And Display Elements

    Product overview 2.5 Operating and display elements Operating and display elements 2.5.1 Front view of the CPU with closed front panel The following figure shows the front view of the CPU 1511-1 PN. ① LEDs for the current operating mode and diagnostics status of the CPU ②...
  • Page 27 200MP (http://support.automation.siemens.com/WW/view/en/59191792) system manual. Reference You will find detailed information on the individual display options, a training course and a simulation of the available menu commands in the SIMATIC S7-1500 Display Simulator (https://support.industry.siemens.com/cs/ww/en/view/109761758). CPU 1511-1 PN (6ES7511-1AK02-0AB0) Equipment Manual, 05/2021, A5E40869673-AB...
  • Page 28: Front View Of The Cpu Without Front Panel And View From Below

    View of the CPU 1511-1 PN (without front panel) – front Note Removing the display Only remove the display if it is faulty. You can find information on removing and replacing displays in the S7-1500, ET 200MP system manual (https://support.industry.siemens.com/cs/ww/en/view/59191792). CPU 1511-1 PN (6ES7511-1AK02-0AB0) Equipment Manual, 05/2021, A5E40869673-AB...
  • Page 29: Rear View Of The Cpu

    Product overview 2.5 Operating and display elements ① Slot for the SIMATIC memory card ② PROFINET IO interface (X1) with 2 ports ③ Connection for supply voltage ④ Fixing screw Figure 2-5 View of the CPU 1511-1 PN – bottom 2.5.3 Rear view of the CPU The following figure shows the connection elements on the back of the CPU 1511-1 PN.
  • Page 30: Operating Mode Buttons

    2. Press the operating mode button STOP until the SIMATIC memory card): the S7-1500/ET 200MP system manual RUN/STOP LED lights up for the 2nd time and re- (https://support.industry.siemens.com/ mains continuously lit (this takes three seconds). cs/ww/den/view/59191792). After this, release the button.
  • Page 31: Connecting Up

    Connecting up This section provides information on the terminal assignment of the individual interfaces and the block diagram of the CPU 1511-1 PN. 24 V DC supply voltage (X80) The connector for the power supply is plugged in when the CPU ships from the factory. The following table shows the signal names and the descriptions of the pin assignment of the 24 V DC supply voltage.
  • Page 32 You need a screwdriver (max. blade width 2.5 mm) to remove the PROFINET plug. Remove display You can find a description of how to remove and replace the display in the S7-1500, ET 200MP (http://support.automation.siemens.com/WW/view/en/59191792) system manual. Reference You can find additional information on the topics of "Connecting the CPU" and "Accessories/spare parts"...
  • Page 33 Connecting up Assignment of the MAC addresses The CPU 1511-1 PN has a PROFINET interface with two ports. The PROFINET interface itself has a MAC address, and each of the two PROFINET ports has its own MAC address. The CPU 1511-1 PN therefore has three MAC addresses in total. The MAC addresses of the PROFINET ports are needed for the LLDP protocol, for example for the neighborhood discovery function.
  • Page 34 Connecting up Block diagram The following figure shows the block diagram of the CPU 1511-1 PN. ① CPU with control and operating mode X80 24 V DC Infeed of supply voltage buttons ② Display 24 V DC supply voltage ③ Electronics Ground ④...
  • Page 35: Interrupts, Error Messages, Diagnostics And System Alarms

    The status and error displays of the CPU 1511-1 PN are described below. You will find additional information on "Interrupts" in the STEP 7 online help. You can find additional information on the topics of "Diagnostics" and "System alarms" in the Diagnostics (http://support.automation.siemens.com/WW/view/en/59192926) function manual. Status and error display of the CPU LED display The figure below shows the LED display of the CPU 1511-1 PN.
  • Page 36 Interrupts, error messages, diagnostics and system alarms 4.1 Status and error display of the CPU Meaning of the RUN/STOP, ERROR and MAINT LEDs The CPU 1511-1 PN has three LEDs to signal the current operating status and diagnostics status. The following table shows the meaning of the various combinations of colors for the RUN/STOP, ERROR and MAINT LEDs.
  • Page 37 Interrupts, error messages, diagnostics and system alarms 4.1 Status and error display of the CPU Meaning of LINK RX/TX LED Each port has a LINK RX/TX LED. The table below shows the various "LED scenarios" of the ports for the CPU 1511-1 PN. Table 4- 2 Meaning of the LEDs LINK TX/RX LED...
  • Page 38 Interrupts, error messages, diagnostics and system alarms 4.1 Status and error display of the CPU Meaning of the STOP ACTIVE LED The following table shows the meaning of the STOP ACTIVE LED for the CPU 1511-1 PN. Table 4- 3 Meaning of the LEDs STOP ACTIVE LED Meaning...
  • Page 39: Technical Specifications

    Technical specifications The following table shows the technical specifications as of 05/2021. You will find a data sheet including daily updated technical specifications on the Internet (https://support.industry.siemens.com/cs/ww/en/pv/6ES7511-1AK02-0AB0/td?dl=en). Article number 6ES7511-1AK02-0AB0 General information Product type designation CPU 1511-1 PN HW functional status...
  • Page 40 Technical specifications Article number 6ES7511-1AK02-0AB0 Memory Number of slots for SIMATIC memory card SIMATIC memory card required Work memory 150 kbyte • integrated (for program) 1 Mbyte • integrated (for data) Load memory 32 Gbyte • Plug-in (SIMATIC Memory Card), max. Backup •...
  • Page 41 Technical specifications Article number 6ES7511-1AK02-0AB0 • Number of asynchronous error OBs • Number of synchronous error OBs • Number of diagnostic alarm OBs Nesting depth • per priority class Counters, timers and their retentivity S7 counter 2 048 • Number Retentivity adjustable –...
  • Page 42 Technical specifications Article number 6ES7511-1AK02-0AB0 I/O address area 32 kbyte; All inputs are in the process image • Inputs 32 kbyte; All outputs are in the process image • Outputs per integrated IO subsystem 8 kbyte Inputs (volume) – 8 kbyte Outputs (volume) –...
  • Page 43 Technical specifications Article number 6ES7511-1AK02-0AB0 Interfaces Number of PROFINET interfaces 1. Interface Interface types Yes; X1 • RJ 45 (Ethernet) • Number of ports • integrated switch Protocols Yes; IPv4 • IP protocol • PROFINET IO Controller • PROFINET IO Device •...
  • Page 44 Technical specifications Article number 6ES7511-1AK02-0AB0 Update time for IRT 250 μs to 4 ms; Note: In the case of IRT with for send cycle of 250 µs – isochronous mode, the minimum update time of 625 µs of the isochronous OB is decisive 500 μs to 8 ms;...
  • Page 45 Technical specifications Article number 6ES7511-1AK02-0AB0 Number of connections 96; via integrated interfaces of the CPU and con- • Number of connections, max. nected CPs / CMs • Number of connections reserved for ES/HMI/web • Number of connections via integrated inter- faces •...
  • Page 46 Technical specifications Article number 6ES7511-1AK02-0AB0 • LLDP Yes; Optional • Encryption Web server Yes; Standard and user pages • HTTP Yes; Standard and user pages • HTTPS OPC UA Yes; "Small" license required • Runtime license required • OPC UA Client Application authentication –...
  • Page 47 Technical specifications Article number 6ES7511-1AK02-0AB0 Number of sessions, max. – 50 000 Number of accessible variables, max. – 10 000 Number of registerable nodes, max. – Number of subscriptions per session, – max. 100 ms Sampling interval, min. – 500 ms Publishing interval, min.
  • Page 48 Technical specifications Article number 6ES7511-1AK02-0AB0 Status/control • Status/control variable Inputs/outputs, memory bits, DBs, distributed • Variables I/Os, timers, counters • Number of variables, max. 200; per job of which status variables, max. – 200; per job of which control variables, max. –...
  • Page 49 Technical specifications Article number 6ES7511-1AK02-0AB0 • Positioning axis Number of positioning axes at motion – control cycle of 4 ms (typical value) Number of positioning axes at motion – control cycle of 8 ms (typical value) Controller Yes; Universal PID controller with integrated op- •...
  • Page 50 405 g General technical specifications You can find information on the general technical specifications, such as standards and approvals, electromagnetic compatibility, protection class, etc., in the S7-1500, ET 200MP (http://support.automation.siemens.com/WW/view/en/59191792) system manual. CPU 1511-1 PN (6ES7511-1AK02-0AB0) Equipment Manual, 05/2021, A5E40869673-AB...
  • Page 51: Dimensional Drawing

    Dimensional drawing This section includes a dimensional drawing of the module on a mounting rail and a dimensional drawing with the front panel open. Always observe the specified dimensions for installation in cabinets, control rooms, etc. Dimensional drawings for CPU 1511-1 PN Figure A-1 Dimensional drawing of CPU 1511-1 PN, front and side views CPU 1511-1 PN (6ES7511-1AK02-0AB0)
  • Page 52 Dimensional drawing Figure A-2 Dimensional drawing of CPU 1511-1 PN, side view with front panel open CPU 1511-1 PN (6ES7511-1AK02-0AB0) Equipment Manual, 05/2021, A5E40869673-AB...

Table of Contents