Technical Specifications
Power supply
Self-Contained: 230-240V 50Hz
Slave: 220-240V AC / 176-275V DC
Autonomy
Commissioning time
Ambient temperature
Self-Contained: +5°C ... +35°C Slave: 0°C ... +40°C
Protection class
Degree of protection
IP42/IP20 (below ceiling/above ceiling)
Battery
NiMH 4,8V - 2,0Ah (Self Contained)
Lightsource
Compliance
EN 60598-1, EN 60598-2.22, VDE 0711, IEC 62034, EN 62386-202
ENGLISH
Carefully read this instruction leaflet before installing or using the luminaire. This leaflet
provides important information about the correct installation, use, maintenance and dis-
posal of this product.
Please observe the following guidelines:
1. The luminaire should only be installed by qualified personnel and installation must be
in accordance with European installation requirements HD 60364 and additional
local regulations.
2. This product may not be modified in any way what so ever or used for a purpose or in an
environment other than for which it is designed. Failling to observe these guidelines
will invalidate the warranty and the CE-compliance of this product.
3. The luminaire is suitable for indoors use only.
4. Before installing the luminaire, the supply must be isolated.
5. The lightsource in this luminare is not replaceable; when the luminaire reaches end of
life the whole luminaire shall be replaced.
INSTALLING AND CONNECTING
The luminaire should be connected to the voltage equivalent to that indicated on the
type label. The surface mounted luminaire is fitted with a terminal block suitable
for loop-in-loop-out connection. For further information on the different connection
possibilities, see the instructions in this instruction leaflet.
SELF-TESTING
All self contained versions of this luminaire are equipped with an automatic self-testing
system that continuously monitors battery operation, the light source(s) and the electronics.
The amber LED's will indicate when one of these components is not working properly.
To prevent all luminares to start the test sequence at the same time, an odd and even function
is available. All even luminares start the test sequence as normal; all odd luminares start
the test sequence 24 hours later. The luminaire can also be tested manually with the
test button. When pushing the button previous errors will be "reset" and the battery will
supply the LED's. After 5 seconds an eventual error will be displayed. The test schedule
can be reset by pushing the test button for 10 seconds. For more detailed information on
the different testing schedule and meaning of the indications, see further in this
instruction leaflet.
05
We reserve the right to make technical changes or modify the contents of this document
without prior notice. With regard to purchase orders, the agreed particulars shall prevail.
ABB AG does not accept any responsibility whatsoever for potential errors or possible
lack of information in this document.
We reserve all rights in this document and in the subject matter and illustrations contained
therein. Any reproduction, disclosure to third parties or utilization of its contents – in whole
or in parts – is forbidden without prior written consent of ABB AG.
Copyright© 2017 ABB. All rights reserved.
Recessed
Self-Contained: 230-240V 50Hz
Slave: 220-240V AC / 176-275V DC
3 hours
60 hours
Self-Contained: +5°C ... +35°C Slave: 0°C ... +40°C
II
NiMH 4,8V - 2,0Ah (Self Contained)
2 LED's (2 x 0, 85W = 1,9W)
EN 60598-1, EN 60598-2.22, VDE 0711, IEC 62034, EN 62386-202
LUMINAIRES POWERED FROM CENTRAL BATTERY SYSTEMS
These luminaires are not equipped with their own integrated testing function. They are
tested by means of the central battery system to which the luminaire is connected.
CT-NAVEO-LUMINARES
Central test luminaires (CT-Naveo / CIS) are supplied under a separate part code and are
fitted with a test system PCB (COM-Box).
DALI LUMINAIRES
Self-Contained luminaires fitted with a DALI communication module are supplied
under a separate article number and have a configurable autotest (not equal to self test).
SLAVE LUMINAIRES WITH LTC
Slave type luminares for Emex / Sentara central emergency power systems are supplied
under a separate part code and are fitted with an LTC PCB (COM-Box).
BATTERY
A fault will occur when test results for duration no longer meets the
requirements indicated for the luminaire. The batteries must then be replaced.
Please see the label on the batteries for the type required. Given the technical
life of the battery, it is recommended to replace them after 4 years. When the
battery is replaced and the mains supply restored, the amber LED indicating
a battery failure will disappear after a successful duration test. Used batteries
must be replaced or disposed of as household chemical waste.
PLEASE NOTE!
Constant voltage is required and the batteries must be sufficiently charged for emergency
lighting to function properly. Failure to observe this requirement can damage the
batteries, the lightsource or in worst-case scenario, the luminaires electronics.
INSPECTION AND MAINTENANCE
Emergi-lite strongly advises annual inspection of your emergency lighting installation.
KM 655958
Surface Mounted
3 hours
60 hours
II
IP54
2 LED's (2 x 0, 85W = 1,9W)
loading