Fujitsu UTY-VBGX Instruction Manual

Fujitsu UTY-VBGX Instruction Manual

Bacnet gateway for vrf system

Quick Links

BACnet Gateway for VRF System
UTY-VBGX
INSTRUCTION MANUAL
Issue Date: 03/2021
r1.4.0 eng
PART No.
9708569239-02
Table of Contents
loading

Summary of Contents for Fujitsu UTY-VBGX

  • Page 1 BACnet Gateway for VRF System UTY-VBGX INSTRUCTION MANUAL Issue Date: 03/2021 r1.4.0 eng PART No. 9708569239-02...
  • Page 2 All trademarks and trade names used in this document are acknowledged to be the copyright of their respective holders. BACnet is a trademark or registered trademark of the American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. 2/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 3 This “CONFIGURATION TOOL of BACnet GATEWAY for VRF SYSTEM” License Agreement (“LICENSE AGREEMENT”) is a legal agreement between you and Fujitsu General Limited (“FGL”) for the use of CONFIGURATION TOOL for VRF BACnet GATEWAY products consisting of computer software and online, electronic and/or printed documentation (collectively “SOFTWARE PRODUCT” or “SOFTWARE”).
  • Page 4 This LICENSE AGREEMENT shall be agreed based on the English language. The text in other language is made for reference purpose only and if there are any discrepancies between the English text and the text in other language, the English text shall prevail. 4/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 5 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Gateway for the integration of Fujitsu air conditioning systems in BACnet/IP enabled monitoring and control systems. Order Code: UTY-VBGX Model supporting up to 128 indoor units. 5/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 6: Table Of Contents

    Batch_Operation_Setting (Binary Output Object Type) ..............37 5.3.8 Batch_OperationMode_Setting (Multistate Output Object Type) ............39 5.3.9 Batch_FanSpeed_Setting (Multistate Output Object Type) ..............41 5.3.10 Batch_RC_Prohibition_Setting (Multistate Output Object Type) ............43 6/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 7 5.3.47 IU_rr_uu_AirFlowDirHZ_Setting (Multistate Output Object Type) ............. 116 5.3.48 IU_rr_uu_RC_Prohibit_Setting (Multistate Output Object Type) ............118 5.3.49 OU_rr_uu_Error_Status (Binary Input Object Type) ................. 119 5.3.50 OU_rr_uu_ErrorCode_Status (Multistate Input Object Type) ............121 7/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 8 7 Set-up process and troubleshooting ......................... 142 Pre-requisites ............................142 Set-up procedure ............................142 LEDs status and push buttons ........................143 8 Configuration Tool for BACnet Gateway (UTY-VBGX) ..................144 Introduction ..............................144 Welcome screen ............................144 Connection ..............................145 Configuration .............................
  • Page 9 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng 9/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 10: Description

    BACnet Gateway for VRF System. The aim of this integration is to monitor and control your Fujitsu VRF air conditioning system, remotely, from your Control Center using any commercial SCADA or monitoring software that includes a BACnet/IP driver. To do it so, the BACnet Gateway for VRF System allows BACnet/IP communication, acting as a server, allowing polling or subscription requests (COV).
  • Page 11: Functionality

    Number of refrigerant systems that can be controlled through UTY- Number of Refrigerant systems VBGX 5000 Number of FGL control and status objects available into UTY-VBGX. Number of Objects The number of Indoor Units and Outdoor Units may vary on each project. These parameters can be configured through Configuration Tool (See section 8).
  • Page 12: Protocol Implementation Conformance Statement

    MS/TP master (Clause 9), baud rate(s): MS/TP slave (Clause 9), baud rate(s): Point-To-Point, EIA 232 (Clause 10), baud rate(s): Point-To-Point, modem, (Clause 10), baud rate(s): LonTalk, (Clause 11), medium: _____ Other: 12/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 13: Device Address Binding

    ISO 10646 (UCS-4) JIS X 0208 2.7 Gateway If this product is a communication gateway, describe the types of non-BACnet equipment/network(s) that the gateway supports: Fujitsu VRF Air Conditioning Network. 13/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 14: Bacnet Interoperability Building Blocks Supported (Bibbs)

    AE-ESUM-A Alarm and Event-Enrollment Summary-A GetEnrollmentSummary AE-ESUM-B Alarm and Event-Enrollment Summary-B GetEnrollmentSummary AE-INFO-A Alarm and Event-Information–A GetEventInformation AE-INFO-B Alarm and Event-Information–B GetEventInformation LifeSafetyOperation ConfirmedEventNotification AE-LS-A Alarm and Event-LifeSafety–A UnconfirmedEventNotification AcknowledgeAlarm 14/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 15: Scheduling Bibbs

    (support DS-RP-B and either DM-TS-B or DM-UTC-B) CreateObject DeleteObject SCHED-AVM-A Scheduling-Advanced View and Modify-A ReadProperty WriteProperty ReadProperty SCHED-VM-A Scheduling-View and Modify-A WriteProperty ReadProperty SCHED-WS-A Scheduling-Weekly Schedule-A WriteProperty ReadProperty WriteProperty SCHED-WS-I-B Scheduling-Weekly Schedule Internal-B TimeSynchronization UTCTimeSynchronization 15/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 16: Trending Bibbs

    DM-TM-A Device Management - Text Message–A UnconfirmedTextMessage ConfirmedTextMessage DM-TM-B Device Management - Text Message–B UnconfirmedTextMessage Device Management DM-TS-A TimeSynchronization TimeSynchronization–A Device Management DM-TS-B TimeSynchronization TimeSynchronization–B Device Management DM-UTC-A UTCTimeSynchronization UTCTimeSynchronization–A 16/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 17 Initialize-Routing-Table-Ack DM-DDB-B Device Management-Automatic Network DM-ANM-A Mapping-A DM-DDB-A DS-RP-A Device Management-Automatic Device DM-ADM-A Mapping-A DM-ADM-A TimeSynchronization Device Management-Automatic Time DM-ATS-A UTCTimeSynchronization Synchronization-A DM-ATS-A TimeSynchronization Device Management-Manual Time DM-MTS-A Synchronization-A UTCTimeSynchronization 17/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 18: Network Security Bibbs

    Network Security-Key Server Request-Master-Key Set-Master-Key NS-SD NS-DMK-A Request-Key-Update Update-Key-Set Update-Distribution-Key NS-TKS Network Security-Temporaty Key Server Request-Master-Key Set-Master-Key NS-SD NS-DMK-A NS-SD NS-SR Network Security-Secure Router NS-ED NS-SP Network Security-Security Proxy NS-SR 18/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 19: Service Types

    ConfirmedPrivateTransfer Management ConfirmedTextMessage Services ReinitializeDevice VtOpen Virtual Terminal VtClose Services VtData Authenticate Security Services RequestKey I-Am I-Have UnconfirmedCOVNotification UnconfirmedEventNotification UnconfirmedPrivateTransfer UnconfirmedTextMessage Unconfirmed TimeSynchronization Services UtcTimeSynchronization Who-Has Who-Is LifeSafetyOperation SubscribeCOVProperty GetEventInformation 19/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 20: Objects

    OU_rr_uu_ForcedOff_Status Gateway_ES_Setting Batch_Operation_Setting IU_rr_uu_Operation_Setting Binary-Output IU_rr_uu_ThermostatOFF_Setting IU_rr_uu_Reset_Filter_Setting IU_rr_uu_TempLimValid_Setting OU_rr_uu_ForcedOff_Setting Binary-Value Calendar Command Device UTY-VBGX Event-Enrollment File Group Loop Gateway_ErrorCode_Status IU_rr_uu_OperationMode_Status IU_rr_uu_FanSpeed_Status IU_rr_uu_AirFlowDirVT_Status IU_rr_uu_AirFlowDirHZ_Status Multistate-Input IU_rr_uu_RC_Prohibit_Status IU_rr_uu_ErrorCode_Status IU_rr_uu_Managed_Mode_Status OU_rr_uu_ErrorCode_Status OU_rr_uu_CapacitySave_Status OU_rr_uu_LowNoiseOp_Status 20/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 21 Event-Log Global-Group Trend-Log-Multiple Load-Control Structured-View Access-Door Timer Access-Credential Access-Point Access-Rights Access-User Access-Zone Credential-Data-Input Network-Security Bitstring-Value CharacterString-Value Date-Pattern-Value Date-Value Datetime-Pattern-Value Datetime-Value Integer-Value Large-Analog-Value Octetstring-Value Positive-Integer-Value Time-Pattern-Value Time-Value Notification-Forwarder Alert-Enrollment Channel Lighting-Output 21/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 22: Member Objects

    IU_rr_uu_HeatTempLoLim_Setting 15rruu IU_rr_uu_HeatTempHiLim_Setting 16rruu IU_rr_uu_Exists_Status 10rruu IU_rr_uu_Operation_Status 11rruu IU_rr_uu_ThermostatOFF_Status 12rruu IU_rr_uu_FilterSign_Status 13rruu IU_rr_uu_Emergency_Status 14rruu IU_rr_uu_Error_Status 15rruu IU_rr_uu_TempLimValid_Status 16rruu IU_rr_uu_Operation_Setting 10rruu IU_rr_uu_ThermostatOFF_Setting 11rruu IU_rr_uu_Reset_Filter_Setting 12rruu IU_rr_uu_TempLimValid_Setting 13rruu IU_rr_uu_OperationMode_Status 10rruu IU_rr_uu_FanSpeed_Status 11rruu 22/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 23: Type: Outdoor Unit

    Multistate Outputs and Multistate Values, it cannot be read the whole array at once, so “Array Index” must be specified in order to obtain the text of the corresponding state. 23/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 24 Forced thermo off not supported not supported Outdoor low noise not supported not supported operation Error monitoring Error state, code ok (5U.1 only for some model) 24/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 25: Fujitsu Ac Gateway (Device Object Type)

    Active_VT_Sessions List of BACnetVTSession Local_Date Date Current date Local_Time Time Current time UTC_Offset INTEGER Daylight_Savings_Status BOOLEAN APDU_Segment_Timeout Unsigned 3000 APDU_Timeout Unsigned 3000 Number_of_APDU_ Unsigned Retries Time_Synchronization_ List of BACnetRecipient Recipients 25/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 26 List of BACnetRecipient Recipients UTC_Time_ Synchronization_ List of BACnetRecipient Recipients Time_Synchronization_ Unsigned Interval Align_Intervals BOOLEAN Interval_Offset Unsigned Product number of BACnet Serial_Number CharacterString serial BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString 26/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 27: Gateway_Es_Status (Binary Input Object Type)

    Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned 27/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 28 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 28/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 29: Gateway_Es_Setting (Binary Output Object Type)

    BACnetPriorityArray BACnetPriorityArray Relinquish_Default BACnetBinaryPV INACTIVE (0) Time_Delay Unsigned Notification_Class Unsigned Feedback_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString 29/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 30 BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured Note. Gateway_ES_Setting may only be set from one unit at a time, within one VRF network. 30/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 31: Gateway_Error_Status (Binary Input Object Type)

    Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned 31/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 32 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 32/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 33: Gateway_Errorcode_Status (Multistate Input Object Type)

    CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 33/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 34 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Gateway Error Code table Gateway Error Code can be interpreted using the values in the following correspondence table. Pesent_Value Description No Error Hardware Error 34/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 35: Batch_Settemp_Setting (Analog Output Object Type)

    Notification_Class Unsigned High_Limit REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN 35/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 36 INSTRUCTION MANUAL r1.4.0 eng BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 36/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 37: Batch_Operation_Setting (Binary Output Object Type)

    BACnetPriorityArray BACnetPriorityArray Relinquish_Default BACnetBinaryPV INACTIVE (0) Time_Delay Unsigned Notification_Class Unsigned Feedback_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString 37/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 38 INSTRUCTION MANUAL r1.4.0 eng Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 38/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 39: Batch_Operationmode_Setting (Multistate Output Object Type)

    CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 39/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 40 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Operation Mode settings table Mode commands can be set using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Cool Heat Auto 40/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 41: Batch_Fanspeed_Setting (Multistate Output Object Type)

    CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 41/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 42 Fan Speed settings table Fan Speed commands can be set using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Pesent_Value Contents displayed in State_Text Quiet High Med-Low Med-High Auto 42/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 43: Batch_Rc_Prohibition_Setting (Multistate Output Object Type)

    CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 43/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 44 REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN 44/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 45 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 45/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 46 REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN 46/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 47 They may have values different from the actual room temperature in some cases like when the operation mode is changed. When using this data for operation control as in setting operation mode and temperature, beware of the above and use it at the discretion of the user. 47/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 48 REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN 48/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 49 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 49/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 50 REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN 50/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 51 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 51/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 52 REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN 52/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 53 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 53/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 54 REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN 54/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 55 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 55/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 56 REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN 56/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 57 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 57/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 58 REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN 58/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 59 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured. 59/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 60 Notification_Class Unsigned High_Limit REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN 60/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 61 INSTRUCTION MANUAL r1.4.0 eng BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 61/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 62 V-II or later Series: Value obtained by scanning Fahrenheit Centigrade Fahrenheit Centigrade 10.5 18.5 11.5 19.5 12.5 20.5 13.5 21.5 14.5 22.5 15.5 23.5 16.5 24.5 17.5 25.5 26.5 27.5 28.5 29.5 62/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 63 Notification_Class Unsigned High_Limit REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN 63/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 64 INSTRUCTION MANUAL r1.4.0 eng BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 64/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 65 Notification_Class Unsigned High_Limit REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN 65/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 66 INSTRUCTION MANUAL r1.4.0 eng BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 66/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 67 Notification_Class Unsigned High_Limit REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN 67/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 68 INSTRUCTION MANUAL r1.4.0 eng BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured. 68/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 69 Notification_Class Unsigned High_Limit REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN 69/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 70 INSTRUCTION MANUAL r1.4.0 eng BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 70/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 71 Notification_Class Unsigned High_Limit REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN 71/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 72 INSTRUCTION MANUAL r1.4.0 eng BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 72/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 73 Notification_Class Unsigned High_Limit REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN 73/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 74 INSTRUCTION MANUAL r1.4.0 eng BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 74/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 75 Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned 75/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 76 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 76/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 77 Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned 77/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 78 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 78/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 79 Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned 79/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 80 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 80/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 81 Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned 81/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 82 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 82/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 83 Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned 83/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 84 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 84/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 85 Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned 85/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 86 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 86/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 87 Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned 87/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 88 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 88/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 89 BACnetPriorityArray BACnetPriorityArray Relinquish_Default BACnetBinaryPV INACTIVE (0) Time_Delay Unsigned Notification_Class Unsigned Feedback_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString 89/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 90 INSTRUCTION MANUAL r1.4.0 eng Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 90/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 91 BACnetPriorityArray BACnetPriorityArray Relinquish_Default BACnetBinaryPV INACTIVE (0) Time_Delay Unsigned Notification_Class Unsigned Feedback_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString 91/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 92 INSTRUCTION MANUAL r1.4.0 eng Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 92/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 93 BACnetPriorityArray BACnetPriorityArray Relinquish_Default BACnetBinaryPV INACTIVE (0) Time_Delay Unsigned Notification_Class Unsigned Feedback_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString 93/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 94 INSTRUCTION MANUAL r1.4.0 eng Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 94/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 95 BACnetPriorityArray BACnetPriorityArray Relinquish_Default BACnetBinaryPV INACTIVE (0) Time_Delay Unsigned Notification_Class Unsigned Feedback_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString 95/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 96 INSTRUCTION MANUAL r1.4.0 eng Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 96/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 97 CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 97/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 98 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Operation Mode status table Mode status can be read using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Cool Heat Auto 98/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 99 CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 99/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 100 Fan Speed status table Fan speed status can be read using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Pesent_Value Contents displayed in State_Text Quiet High Med-Low Med-High Auto 100/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 101 CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 101/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 102 INSTRUCTION MANUAL r1.4.0 eng Air Flow Dir VT status table Vertial Air Flow direction status can be red using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Swing 102/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 103 CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 103/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 104 INSTRUCTION MANUAL r1.4.0 eng Air Flow Dir HZ status table Horizontal Air Flow Direction status can be read using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Swing 104/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 105 CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 105/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 106 CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 106/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 107 Pesent_Value Contents displayed in State_Text Normal Indicates setting to master indoor unit. Master Indicates setting to managed indoor unit by master Slave indoor unit. Indicates setting to managed indoor unit by outdoor External unit. 107/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 108 CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 108/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 109 INSTRUCTION MANUAL r1.4.0 eng NOTE: For the error content, refer to the “Error content table (section 12.1)” using the Present_Value of the appropriate series. Error contents may be added without prior notice. 109/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 110 CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 110/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 111 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Operation Mode settings table Mode commands can be set using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Cool Heat Auto 111/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 112 CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 112/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 113 Fan Speed settings table Fan speed commands can be set using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Pesent_Value Contents displayed in State_Text Quiet High Med-Low Med-High Auto 113/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 114 CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 114/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 115 INSTRUCTION MANUAL r1.4.0 eng Air Flow Dir VT settings table Vertial Air Flow Direction commands can be set using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Swing 115/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 116 CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 116/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 117 INSTRUCTION MANUAL r1.4.0 eng Air Flow Dir HZ settings table Horizontal Air Flow Direction commands can be set using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Swing 117/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 118 CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 118/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 119 Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned 119/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 120 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 120/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 121 CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 121/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 122 INSTRUCTION MANUAL r1.4.0 eng NOTE: For the error content, refer to the “Error content table (section 12.1)” using the Present_Value of the appropriate series. Error contents may be added without prior notice. 122/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 123 Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned 123/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 124 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 124/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 125 CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 125/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 126 Capacity Save status table Capacity Save status can be read using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Pesent_Value Contents displayed in State_Text Not set 100% 126/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 127 CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 127/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 128 Capacity Save setting table Capacity Save can be set using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Pesent_Value Contents displayed in State_Text Not set 100% 128/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 129 BACnetPriorityArray BACnetPriorityArray Relinquish_Default BACnetBinaryPV INACTIVE (0) Time_Delay Unsigned Notification_Class Unsigned Feedback_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp BACnetArray[3] of Event_Message_Texts CharacterString BACnetArray[3] of Event_Message_Texts_Config CharacterString 129/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 130 INSTRUCTION MANUAL r1.4.0 eng Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured. 130/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 131 CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 131/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 132 E:Simultaneously controlled through external input of outdoor unit. If this value is set, the actual low noise operation will also depend on the external input signal connected to the outdoor unit. 132/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 133 CharacterString Event_Detection_Enable BOOLEAN BACnetObjectPropertyRefer Event_Algorithm_Inhibit_Ref ence Event_Algorithm_Inhibit BOOLEAN Time_Delay_Normal Unsigned Reliability_Evaluation_Inhibit BOOLEAN BACnetArray[N] of Property_List BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString * Only available when specific object has a Notification Class configured 133/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 134 Low Noise Operating commands can be set using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Pesent_Value Contents displayed in State_Text Level2-Ability Stop Level3-Quiet Level1-Quiet Level3-Ability Level1-Ability Level2-Quiet 134/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 135 Object_Name CharacterString "NotificationClass_0" ~ "NotificationClass_9" Object_Type BACnetObjectType NOTIFICATION_CLASS (15) Description CharacterString Notification_Class Unsigned Priority BACnetARRAY[3] of Unsigned Ack_Required BACnetEventTransitionBits Recipient_List BACnetLIST of BACnetDestination Property_List BACnetArray[N] of BACnetArray[N] BACnetPropertyIdentifier Profile_Name CharacterString 135/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 136 Install a leakage circuit breaker to power supply cable in accordance with the related laws and regulations and electric company standards. Use a power source exclusively for this unit. Never share the power source with other electrical equipment. Doing so will cause fire and electric shock. 136/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 137 There is the danger of suffocation if children play with the original plastic bags. Do not insert articles into the slit parts of this unit. Doing so will cause trouble, heating, or electric shock. 137/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 138 Connect a mini-type B USB cable from your computer to the gateway to allow communication between the Configuration Software and the gateway. Remember that Ethernet connection is also allowed for configuration. 138/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 139 - Install the disconnect switch to the easily accessible location. - Check that an appropriate fuse (1.25A) is set. - Before connecting cables, turn off the power of the VRF units connected to the gateway. 139/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 140 LAN of the building, contact the network administrator and make sure traffic on the port used is allowed through all the LAN path. The BACnet Gateway for VRF System comes with DHCP functionality enabled by default. 140/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 141 Use the LON connector in the left bottom corner of the gateway in order to connect the VRF network to the UTY- VBGX. Remember to follow all safety precautions indicated by Fujitsu. Modifying some other parameters can affect proper communication.
  • Page 142 10. Open the Fujitsu Communication Viewer window and check that there is communication activity, some RX frames. This means that the communication with the VRF network is OK. In case of no communication activity, check that the VRF network is operative and well configured and check also the communication cable used to connect both systems.
  • Page 143 Service led of LON port. LED_8 (green) Device has IP address (after DHCP or manually assigned). Button Description PUSH_A Sends I-Am msg on bacnet-ip side. PUSH_B Service pin of LON port. 143/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 144 8.2 Welcome screen From the welcome screen, access is granted to: the Fujitsu General Limited Website, start a new project, load a previous project from our computer or get the current project running on the gateway. Figure 8.1 Welcome screen 1.
  • Page 145 IP connection are: IP: 192.168.100.246 / Password: admin If installing more than one BACnet Gatewy for VRF System, connect them one by one and assign an IP to each of them in case DHCP is not available. 145/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 146 8. Time: Press “Set” set current PC time to the gateway. Check “Time sync on project download” to synchronise time when downloading project to the gateway. 9. Security configuration if exists, is for maintenance purpose only, and is not to be edited. 146/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 147 1. Device Name: Device BACnet name and description (Device UTY-VBGX by default). 2. Device Instance: Device BACnet number (144 by default, if more than one UTY-VBGX is present, this have to be a unique number for each BACnet Gateway for VRF System).
  • Page 148 2. Temperature Mode: Enter the desired temperature units to be used (Celsius or Faherenheit). 3. Add Air Unit Manually: Use this option to introduce units manually in the configuration. Figure 8.8 Add units manually 148/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 149 1. Signal number: Configuration Tool internal reference. 2. Active: Indicates if the signal is currently active for this configuration. If not, it will not be considered by the tool when downloading it to the gateway. 149/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 150 IMPORTANT: It is required that the ethernet link of this gateway is established and active, in order to send and configure the IP addresses. Otherwise, IP addresses will not be set by the "Send". 150/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 151 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng 151/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 152 8.7 Diagnostic Use this setting to check the current communication status of the gateway on both: BACnet and FGL. Communication with the box, the BACnet side and the Fujitsu system can be check using the viewer available. Figure 8.12 Diagnostic tool 1.
  • Page 153 Check the current signal values on both: BACnet and VRF network side (connection to the VRF network and/or BACnet client is required). The Signals Viewer can be used even though only one system is connected to the gateway, BACnet or Fujitsu AC. Therefore, it becomes convenient for supervision and testing the system.
  • Page 154 1 x Power 1 x Error Operational 0°C to +46°C temperature Operational 5% to 95%, non-condensing humidity Preservation -10°C to +60°C Temperature Protection IP20 (IEC60529). RoHS conformity Compliant with RoHS directive (2002/95/CE). 154/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 155 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng 11 Dimensions [mm] 155/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 156 BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng 12 Annex 12.1 Error codes Below you can find a list of error codes from Fujitsu air conditioning system. V-II or laterf Series Present_Valu Error Code Error Description Serial communication error between indoor/outdoor units...
  • Page 157 Outdoor unit pressure error 1 Outdoor unit pressure error 2 Outdoor unit heat exchanger temperature error Suction temperature abnormal Poor refrigerant circulation Current overload error Outdoor unit special operation error 157/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 158 System tool interface error System tool environment error RB unit error Branch boxes error Total heat exchanging, ventilation unit error Domestic hot water unit error Zone control interface error DX-Kit error 158/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...
  • Page 159 -/TR/TP/MD/-/-/- -/-/TP/MD/-/-/- -/TR/TP/MD/-/-/FL -/-/TP/MD/-/-/FL -/TR/TP/MD/-/ON/- -/-/TP/MD/-/ON/- -/TR/TP/MD/-/ON/FL -/-/TP/MD/-/ON/FL -/TR/TP/MD/OP/-/- -/-/TP/MD/OP/-/- -/TR/TP/MD/OP/-/FL -/-/TP/MD/OP/-/FL -/TR/TP/MD/OP/ON/- -/-/TP/MD/OP/ON/- -/TR/TP/MD/OP/ON/FL -/-/TP/MD/OP/ON/FL ALL/-/-/-/-/-/- -/TR/-/-/-/-/- Note: “ON” and “OP” may not be set at the same time. 159/159 Copyright© 2021 Fujitsu General Limited - All rights reserved...

Table of Contents