Safety Devices - Fujitsu Airstage V-II Design & Technical Data

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V-II:
Table of Contents
3393

SAFETY DEVICES

Safety device
Fuse (Main PCB)
Protector (INV PCB)
INV
COMP
Compressor
Protector
CONST
COMP
High Pressure Protection
Low Pressure Protection
AJ
A72LALH
AJ
A90LALH
Temperature protection
- (03 - 48) -
AJ
108LALH
AJ
AC 250V 3.15A
AC 500V 15A
AC 500V 25A
Overcurrent protection
-
Off : 110°C
Temperature protection
Off:155°C±5(0A)
Minimum operation current
On:14.4A(120°C)
Off:20.0A(120°C)
Over current protection
3 - 10sec 59.0A
Off : 4.2MPa
On : 3.2MPa
Off : 0.05MPa
126LALH
AJ
144LALH
On : 80°C
On:80°C±11(0A)