Error Code [6600]; Error Code [6601]; Error Code [6602]; Error Code [6603] - Mitsubishi Electric PURY-M200YNW-A1 Service Handbook

Hide thumbs Also See for PURY-M200YNW-A1:
[7-8 Error Code Definitions and Solutions: Codes [6000 - 6999] ]
7-8-3

Error Code [6600]

1. Error code definition
Address overlaps
2. Error definition and error detection method
An error in which signals from more than one indoor units with the same address are received
Detail code 001: Detection of overlapped address in centralized control system
Detail code 002: Detection of overlapped address in indoor unit system
The address and attribute that appear on the remote controller indicate the controller that detected the error.
3. Cause, check method and remedy
(1)
Two or more of the following have the same address:
Outdoor units, HBCs, indoor units, LOSSNAY units,
controllers such as ME remote controllers.
6600 "01" appears on the remote controller
Unit #01 detected the error.
Two or more units in the system have 01 as their ad-
dress.
(2)
Signals are distorted by the noise on the transmission
line.
7-8-4

Error Code [6601]

1. Error code definition
Polarity setting error
2. Error definition and error detection method
The error detected when transmission processor cannot distinguish the polarities of the M-NET transmission line.
3. Cause, check method and remedy
(1)
No voltage is applied to the M-NET transmission line
that AE-200E/AG-150A/GB-50ADA/PAC-
YG50ECA/BAC-HD150 are connected to.
(2)
M-NET transmission line to which AE-200/AG-150A/
GB-50ADA/PAC-YG50ECA/BAC-HD150 are con-
nected is short-circuited.
(3)
When two or more power supplies are connected to
the M-NET
62
- chapter 7
Cause
Cause
Check method and remedy
Find the unit that has the same address as that of the error
source.
Once the unit is found, correct the address. Then, turn
off the outdoor units, indoor units, HBCs, and
LOSSNAY units, keep them all turned off for at least
five minutes, and turn them back on.
When air conditioning units are operating normally despite
the address overlap error
Check the transmission wave shape and noise on the
transmission line.
Refer to the following page(s). [8-4 Checking Transmission
Waveform and for Electrical Noise Interference]
Check method and remedy
Check if power is supplied to the M-NET transmission
line of the AE-200E/AG-150A/GB-50ADA/PAC-
YG50ECA/BAC-HD150, and correct any problem found.
BS_07_M