• Thank you for purchasing this Samsung air conditioner.
• Before operating this unit, please read this manual carefully and retain it for future reference.
DB68-07310A-03
Table of Contents
loading

Summary of Contents for Samsung AC Series

  • Page 1 Air conditioner Installation manual • Thank you for purchasing this Samsung air conditioner. • Before operating this unit, please read this manual carefully and retain it for future reference. DB68-07310A-03...
  • Page 2: Table Of Contents

    Contents PREPARATION Safety precautions ......................3 Preparation for outdoor unit installation.
  • Page 3: Safety Precautions

    In order to prevent electric shocks, fires or injuries, always stop the unit, disable the protection switch and contact SAMSUNG’s technical support if the unit produces smoke, if the power cable is hot or damaged or if the unit is very noisy.
  • Page 4 Safety precautions Installing the unit IMPORTANT: When installing the unit, always remember to connect first the refrigerant tubes, then the electrical lines. Always disassemble the electric lines before the refrigerant tubes. Upon receipt, inspect the product to verify that it has not been damaged during transport. If the product appears damaged, DO NOT INSTALL it and immediately report the damage to the carrier or retailer (if the installer or the authorized technician has collected the material from the retailer.) After completing the installation, always carry out a functional test and provide the instructions on how to operate the air...
  • Page 5: Preparation For Outdoor Unit Installation

    Preparation for outdoor unit installation The air conditioner uses R-410A refrigerant. A Type: AC048MXQFGC/AC060MXQFGC (Unit : mm) B Type: AC036MXQFEC/AC042MXQFEC C Type: AC030MXQFEC English...
  • Page 6 Preparation for outdoor unit installation D Type: AC018MXQFEC E Type: AC024MXQFEC F Type: AC012MXQFEC 6 English...
  • Page 7: Deciding On Where To Install The Outdoor Unit

    Air Guide Duct (This product is not Stereo provided by Samsung) 200mm If the outdoor unit is installed at a height, ensure that its base is firmly fixed in position. Make sure that the water dripping from the drain hose runs away correctly and safely.
  • Page 8 7. Check the condition of the product periodically. - Check the installation site every 3 months and perform anti-corrosion treatment such as R-Pro supplied by SAMSUNG (Code : MOK-220SA) or commercial water repellent grease and wax, etc., based on the product condition.
  • Page 9 Outdoor unit Outdoor Sea breeze unit Outdoor unit Protection wall Outdoor unit Sea breeze Sea breeze Outdoor unit Protection wall should be constructed with a solid material that can block the sea breeze and the height and width of the wall should be 1.5 times larger than the size of the outdoor unit.
  • Page 10 Deciding on where to install the outdoor unit Space Requirements for Outdoor Unit When installing 1 outdoor unit ❋ When the air outlet is opposite the wall ❋ When the air outlet is towards the wall 2000 or more 300 or more 600 or more ❋...
  • Page 11 300 or more 600 or more 600 or more 600 or more ❋ When 3 sides of the outdoor unit are blocked by the wall 300 or more 300 or more 600 or more 600 or more ❋ When front and rear side of the outdoor unit is towards the wall ❋...
  • Page 12: Outdoor Unit Installation

    Outdoor unit installation The outdoor unit must be installed on a rigid and stable base to avoid any increase in the noise level and vibration, particularly if the outdoor unit is to be installed in a location exposed to strong winds or at a height, the unit must be fixed to an appropriate support(wall or ground).
  • Page 13 Outdoor Unit Support Outdoor Unit Outdoor Unit Anchor bolt Support Base Surface OUTDOOR UNIT INSTALLED ON THE WALL BY RACK Designed to cut off residual Ensure the wall will be able to suspend the weight of rack and outdoor unit ; vibration from Install the rack close to the column as much as possible ;...
  • Page 14: Connecting The Cable

    Connecting the cable Two electronic cables must be connected to the outdoor unit. The connection cord between indoor unit and outdoor unit. The power cable between outdoor unit and auxiliary circuit breaker. Specially for Russian and European market, before installation, the supply authority should be consulted to determine the supply system impendance to ensure compliance.
  • Page 15 Power Cable Specifications The power cable is not supplied with air conditioner. - Select the power supply cable in accordance with relevant local and national regulations. - Wire size must comply with the applicable local and national code. - Specifications for local wiring power cord and branch wiring are in compliance with local cord. Single Phase Model Outdoor Units...
  • Page 16 Connecting the cable Between Indoor unit and Outdoor unit Connection Cable Specifications(Common in use) Power supply Communation Cable Power supply Max/Min(V) Indoor Power Cable 1Φ, 220 - 240V, 50Hz ±10% 2.5mm² , 3wires 0.75mm² , 2wires ❋ Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC66 / CENELEC H07RN-F) When installing the indoor unit in a computer room or net work room, use the double shielded (Tape aluminum / polyester braid + copper ) cable of FROHH2R type.
  • Page 17 Wiring Diagram of Power Cable When using ELB for 1 phase and 3 phase 1 phase 1(L) 2(N) Cable tie Electrical Power Supply Indoor Power component box MCCB Main power cable Communication cable MCCB 3 phase 1(L) 2(N) L1(R) L2(S) L3(T) Indoor Unit Cable tie...
  • Page 18 Connecting the cable Silence mode controller wiring diagram Outdoor unit Silence Mode Controller Silence Mode is a function that reduces noise at night. For more information how to set mode, refer to page 32. 1 phase (Duct Type) Indoor Unit Outdoor Unit 1(L) 2(N) 1(L) 2(N)
  • Page 19 Connecting the Power Terminal Connect the cables to the terminal board using the compressed ring terminal. Cover a solderless ring terminal and a connector part of the power cable and then connect it. Silver solder Nominal Nominal Standard Standard Standard Min.
  • Page 20: Wiring Work

    Wiring Work How to connect your extended power cables 1. Prepare the following tools. Tools Crimping pliers Connection sleeve (mm) Insulation tape Contraction tube (mm) Spec MH-14 20xØ6.5 (HxOD) Width 19 mm 70xØ8.0 (LxOD) Shape 2. As shown in the figure, peel off the shields from the rubber and wire of the (Unit: mm) Power cable power cable.
  • Page 21 5. Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation tape. Method 1 Method 2 Insulation tape Insulation tape 40 mm 35 mm 6. Apply heat to the contraction tube to contract it. Method 1 Method 2 Contraction tube...
  • Page 22: Connecting The Refrigerant Pipe

    Connecting the refrigerant pipe Refrigerant piping system Maximum allowable length Items Single installation AC036MXQFEC AC024MXQFEC AC042MXQFEC Applicable outdoor unit models AC012MXQFEC AC018MXQFEC AC030MXQFEC AC048MXQFGC AC060MXQFGC Main pipe (L 20 m 30 m 50 m 75 m Max. height difference between 15 m 20 m 30 m...
  • Page 23: Adding Refrigerant (R-410A)

    Adding refrigerant (R-410A) The outdoor unit is loaded with sufficient refrigerant for the standard piping. Thus, refrigerant must be added if the piping is lengthened. This operation can only be performed by a qualified refrigeration specialist. For quantity of adding refrigerant, refer to page 20.
  • Page 24: Connecting Up And Removing Air In The Circuit

    Connecting up and removing air in the circuit • When installing, make sure there is no leakage. When recovering the refrigerant, ground the compressor first before removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor CAUTION works with the service valve open, the pipe inhales the air and it makes the pressure inside of the refrigerant cycle abnormally high.
  • Page 25 5. Purge the air from the system using vacuum pump for about 10 minutes. Close the valve of the low pressure side of manifold gauge clockwise. Make sure that pressure gauge shows -0.1MPa(-76cmHg) after about 10 minutes. This procedure is very important to avoid a gas leak. B(liquid) A(gas) Turn off the vacuum pump.
  • Page 26: Cutting/Flaring The Pipes

    Cutting/Flaring the pipes 1. Make sure that you have the required tools available. (pipe cutter, reamer, flaring tool and pipe holder) 2. If you wish to shorten the pipes, cut it with a pipe cutter, taking care to ensure that the cut edge remains at a 90° angle with the side of the pipe.
  • Page 27: Connecting The Drain Hose To The Outdoor Unit

    Performing leak tests LEAK TEST WITH NITROGEN (before opening valves) In order to detect basic refrigerant leaks, before recreating the vacuum and recirculating the R-410A, it’s responsable of installer to pressurize the whole system with nitrogen (using a cylinder with pressure reducer) at a pressure above 40 bar (gauge).
  • Page 28: Refrigerant Pipe Work

    Refrigerant pipe work Once you have checked that there are no leaks in the system, you can insulate the piping and hose. 1. To avoid condensation problems, place an insulator around each refrigerant pipe. • When insulate the pipe, be sure to overlap the insulation. •...
  • Page 29: Pump Down Procedure

    Using service valve To Open the Service Valve 1. Open the body cap and turn the spindle counterclockwise by using a hexagonal wrench. Spindle Flare nut 2. Turn it until the spindle is stopped. • Do not apply excessive force to the service valve and always use special instruments.
  • Page 30: Checking Correct Grounding

    Checking correct grounding If the power distribution circuit does not have a grounding or the grounding does not comply with specifications, an grounding electrode must be installed. The corresponding accessories are not supplied with the air conditioner. 1. Select an grounding electrode that complies with the specifications given in the illustration.
  • Page 31: Testing Operations

    Testing operations 1. Check the power supply between the outdoor unit and the auxiliary circuit breaker. 1 phase power supply : L, N 3 phase power supply : R, S, T, N 2. Check the indoor unit. 1) Check that you have connected the power and communication cables correctly. (If the power cable and communication cables one mixed up or connected incorrectly, the PCB will be damaged.) 2) Check that the thermistor sensor, drain pump/hose, and display are connected correctly.
  • Page 32 Testing operations Display contents SEG1 SEG2 SEG3 SEG4 Main micom version Year (Dec) Month (Hex) Date (Tens digit) Date (Units digit) After short push 1 Inverter micom version Year(Dec) Month (Hex) Date (Tens digit) Date (Units digit) long After short push 2 E2P version Year(Dec) Month (Hex)
  • Page 33: Troubleshooting

    Troubleshooting The table below give indication about self diagnostic routine. Some of error code requires activities exclusively for Authorized Service Center. Outdoor unit The table below list the self-diagnostic routines. For some of error codes, you must contact an authorized service centre. If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER PCB.
  • Page 34 Troubleshooting Error Meaning Remarks Code 1. Check the range of temperature limited for heating Heating operation restricted at outdoor temperature over operation E440 Theat_high value (default:30°C) 2.Check the outdoor temperature sensor 1. Check the range of temperature limited for cooling Cooling operation restricted at outdoor temperature below operation E441...
  • Page 35: Packing And Unpacking Guide

    Packing and unpacking guide Outdoor unit Packing the unit as below procedure 1. Fix the outdoor unit and the wood palette by 4 screws. 2. Put the cushion-top onto the outdoor unit. 3. Put the packing case from the top of set. 4.
  • Page 36 Product specification MODEL AC030MXQFEC AC036MXQFEC AX042MXQFEC CLIMATES CLASS 28200 Btu/h 23000 Btu/h 33500 Btu/h 29500 Btu/h 38000 Btu/h 35700 Btu/h COOLING RATED CAPACITY 8.26 kW 6.74 kW 9.82 kW 8.65 kW 11.14 kW 10.46 kW HEATING RATED VOLTAGE & FREQUENCY 220 - 240 V ~ 50 Hz 220 - 240 V ~ 50 Hz 220 - 240 V ~ 50 Hz...
  • Page 37 MODEL AC048MXQFGC AC060MXQFGC CLIMATES CLASS 44000 Btu/h 39000 Btu/h 52000 Btu/h 47000 Btu/h COOLING RATED CAPACITY 12.90 kW 11.43 kW 15.24 kW 13.77 kW HEATING RATED VOLTAGE & FREQUENCY 380 - 415 V 3N ~ 50 Hz 380 - 415 V 3N ~ 50 Hz COOLING 5.6A 6.7A...