Huawei NetCol5000-C065 Quick Manual

Huawei NetCol5000-C065 Quick Manual

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C065:

Quick Links

NetCol5000-C065 In-row Chilled Water
Smart Cooling Product
Quick Guide (Russia, Skoltech)
Issue: 01
Date: 2021-01-08
1
Overview
2
Preparing Materials
Materials
Fuse, combined hexagon head bolts M12x90, OT ground terminal of the power
Configured with
cable to the indoor unit, and single cord end terminal of the power cable to the
the Equipment
indoor unit, cable tie
Humidifier water
inlet pipe
Chilled water inlet
Engineering
and outlet pipes
Procurement
Cables
Others
Model
Power system
Net weight (full configuration) About 222 kg
Dimension (mm)
(H x W x D)
(1) Electric control box
(3) Main control board
(5) Temperature and humidity
sensor
(7) Chilled water outlet pipe
(9) Drainpipe
(11) Chilled water valve
actuator
(13) Heat exchanger
Rigid pipe: G 3/4-inch rigid pipe connector with internal
threads (plastic materials such as PA66, or metal materials
are recommended), and rigid pipe (withstand pressure ≥
0.7 MPa)
Seamless steel pipe with a G 1–1/2 inch external threaded
connector or aluminum plastic pipe with an inner diameter
of 41 mm.
Power cable (3x6.0 mm²), teamwork networking and
monitoring cables, and equipotential cable (≥ 16 mm²)
Indoor unit base, thermal insulation foam, and thermal
insulation foam glue
1
NetCol5000-C065
220 V AC to 240 V AC, 1 PH,
50/60 Hz, dual power supplies
2000 x 600 x 1200
(2) PSU
(4) Differential pressure switch
(6) Wet film humidifier
(8) Water pan
(10) Water pump
(12) Chilled water inlet pipe
Copyright © Huawei Technologies Co., Ltd. 2021.
All rights reserved.
loading

Summary of Contents for Huawei NetCol5000-C065

  • Page 1 41 mm. Power cable (3x6.0 mm²), teamwork networking and Cables monitoring cables, and equipotential cable (≥ 16 mm²) Indoor unit base, thermal insulation foam, and thermal Others insulation foam glue Copyright © Huawei Technologies Co., Ltd. 2021. All rights reserved.
  • Page 2: Installing The Equipment

    Preparing an Indoor Unit Base Unit: mm 1. Shock absorption bars (EPDM rubber, 5 mm thick) need to be installed between the ground and the base. 2. The base should be at least 250 mm in height. The base bearing capacity must be at least 2 t.
  • Page 3 1. The equipment has been injected with 0.2–0.6 MPa of nitrogen before delivery. If no nitrogen is discharged, contact Huawei technical support. 2. You can open or close the exhaust valve using a flat- head screwdriver.
  • Page 4 Installing Cabinets Side by Side Securing the Equipment Front Rear Installing Pipes Pipe Layout 1. A 1:100 tilt should be reserved for the main drainpipe and humidifier water inlet pipe. 2. Keep a clearance of at least 25 mm between pipes. Secure the pipes to supports every a certain distance.
  • Page 5 Drainpipe Layout Secure the drainpipe properly. Connecting the Humidifier Water Inlet Pipe Connection method G 3/4 inch reserved connector with outer screw thread G 3/4 inch adapter with inner screw thread Note1 Matched with the adapter, the pressure resistance should be at least 0.7 MPa Note 1: 1.
  • Page 6 Connecting the Chilled Water Inlet and Outlet Pipes Aluminum plastic pipe (1) G 1–1/2 inch port with inner threads (reserved device port) (2) Direct connection of external teeth (3) Sealing ring (4) Nut (5) Aluminum plastic pipe with an inner diameter of 41 mm Seamless steel pipe (1) G 1–1/2 inch port with inner...
  • Page 7 ( Optional) Leakage Test with Nitrogen • If the pressure has fallen, apply soapy water on the pipes, especially pipe joints, to check for leakages. Rectify the leakages if any. • If the pressure is stable, wrap all pipes and connectors with thermal insulation foam. •...
  • Page 8 Installing Cables Connecting the Equipotential Ground Cable and Power Cable 1. When routing the cables, wrap the section of all signal cables inside the smart cooling product with the corrugated pipes and route them out of the corresponding cable holes so that the strong- and weak-current cables are separated.
  • Page 9 2. Set the DIP switches on the T/H sensors. DIP Switch ID Name Address Cold aisle 1 temp/humid Cold aisle 2 temp/humid Cold aisle 3 temp/humid Cold aisle 4 temp/humid Cold aisle 5 temp/humid Hot aisle 1 temp/humid Hot aisle 2 temp/humid Hot aisle 3 temp/humid Hot aisle 4 temp/humid Hot aisle 5 temp/humid...
  • Page 10 • All smart cooling products in a teamwork group must be of the same model. • Do not directly connect the first and the last smart cooling products to form a ring network. • A maximum of 32 smart cooling products can be networked in one group. The teamwork cable between two adjacent smart cooling products must not exceed 10 m.
  • Page 11 (Optional) Connecting the Monitoring Network Cable The smart cooling product supports both RS485 monitoring and FE monitoring. Connecting the FE monitoring cable (SNMP/Modbus-TCP protocol) The FE monitoring and FE teamwork use the same network cable. Connect the FE monitoring cable in the same process of connecting the FE teamwork network cable. RS485 Monitoring Network Cable (Modbus-RTU Protocol) 1.
  • Page 12: Verifying The Installation

    Verifying the Installation No. Check Item Check Result All water pipes are properly and securely installed, and free from leakage, □ Passed □ Failed blockage, and sharp turns. The liquid level detector is level. The water pan is free from foreign matter such as cable remains and thermal insulation foam.
  • Page 13 Temperature and Humidity Settings Set Temperature and humidity control type, Control point temperature setpoint, and Control point humidity setpoint as required on site. Path: Settings > System Settings > Common Settings or Settings > System Settings > T/H Sensor. (Optional) Setting the Indoor Fan Control Type If a micro differential pressure sensor is installed and the pressure difference control is required, set Air-side difference pressure sensor type to 0–50 Pa, and set the Indoor fan control type to Pressure diff ctrl.
  • Page 14 The table uses 8 smart cooling products in CAN teamwork as an example. Teamwork group no. Air conditioner address Enable teamwork CAN resistor Teamwork function Enable Enable Enable Enable Enable Item Networking mode Number of air conditioners in this group Number of running 6 (2 air conditioners in...
  • Page 15 Tap Start on the home screen. • Download the Service Expert app from After tapping Yes, the barcode and the Huawei app store and runs on Android. verification code are shown on the screen. Apply for permission after downloading the app.
  • Page 16 If the floor water overflow alarm is generated, the smart cooling product will shut down by default. If you do not need to stop the smart cooling product, contact Huawei technical support engineers to evaluate risks. After the risk is accepted, choose Settings > System Settings >...