Quick Links

EKM-E Ether-Mon Key DE-211
INSTALLATION AND SETUP GUIDE

TABLE OF CONTENTS

Product Specifications .............................................................................................................................................
Package Checklist .............................................................................................................................................
LED Indicators .............................................................................................................................................
DIP Switch Pre and Post Configuration .........................................................................................................................................
Ethernet Configuration .............................................................................................................................................
Connecting the E10039 to a PC ............................................................................................................................................. 13
EZ7 RS485 Wiring Typical Installation ........................................................................................................................................... 29
Correct Daisy Chain Configuration ................................................................................ 29
2-Wire RS-485 Terminal Block Wiring .......................................................................... 31
EZ7 RS485 Wiring ................................................................................................................. 32
Typical Cable Part Numbers ............................................................................................................................................. 33
Enabling Termination Resistor ........................................................................................ 34
Compliance Notice ............................................................................................................................................. 34
Building
Introduction .............................................................................................................................................
Features .............................................................................................................................................
Wall Mount .............................................................................................................................................
TECHNICAL REFERENCE MANUAL
2
2
2
3
5
5
7
8
9
31-00160-01
Table of Contents
loading

Summary of Contents for Honeywell E-Mon E10039

  • Page 1: Table Of Contents

    Correct Daisy Chain Configuration ................29 2-Wire RS-485 Terminal Block Wiring ................31 EZ7 RS485 Wiring ......................... 32 Typical Cable Part Numbers ............................. 33 Enabling Termination Resistor ..................34 Honeywell E-Mon Recommends Enabling the Built-In 120 Ω Terminator ..34 Compliance Notice ............................. 34 31-00160-01...
  • Page 2: Introduction

    EKM-E ETHER-MON KEY DE-211 INTRODUCTION Honeywell E-Mon E10039 / NPort Express DE-211 provides a data communications solution for connecting Windows to asynchronous serial devices over a TCP/IP Ethernet. You may connect your Windows host to a native RS-485 serial port, through TCP/IP Ethernet.
  • Page 3: Package Checklist

    EKM-E ETHER-MON KEY DE-211 PACKAGE CHECKLIST • 1 A/C 120 volt to 12 VDC Power Adapter 0.5 A • 1 E10039 (EKM-E) NPort Express DE-2111 • NP21103 DB25 terminal block kit for RS-485 (Installed on E10039) • RJ-45 Patch Cable •...
  • Page 4 EKM-E ETHER-MON KEY DE-211 Fig. 2. 31-00160—01...
  • Page 5: Led Indicators

    EKM-E ETHER-MON KEY DE-211 LED INDICATORS E10039 NPort Express’s top panel contains five LED indicators, as described in the following table. Table 1. LED Name LED Color LED Function Power is on. Power is off, or power error condition exists. Link Orange 10 Mbps Ethernet connection.
  • Page 6 EKM-E ETHER-MON KEY DE-211 2. Insert the two screw heads through the large parts of the keyhole shaped apertures, and then slide the NPort Express downward, as indicated. Fig. 4. 3. For added stability, simply tighten the two screws. Fig. 5. 31-00160—01...
  • Page 7: Dip Switch Pre And Post Configuration

    EKM-E ETHER-MON KEY DE-211 DIP SWITCH PRE AND POST CONFIGURATION IMPORTANT! Before powering up the E10039 turn all 4 dip switches to Off (down postion). Fig. 6. 1. Plug the power supply in Ethernet Key. The Red PWR and Green Ready LED light should illuminate as shown below. Fig.
  • Page 8: Ethernet Configuration

    EKM-E ETHER-MON KEY DE-211 ETHERNET CONFIGURATION Default IP address 192.168.127.254 MAC Address see the back of the case Fig. 8. 31-00160—01...
  • Page 9: Installing The Moxa Software "Nport Utility

    INSTALLING THE MOXA SOFTWARE “NPORT UTILITY” You may use Telnet or install the Moxa software CD to configure the E10039 Static IP address and network settings as required for Honeywell E-MonEnergy software. Use the supplied Moxa software CD or download from the following link: http://www.emon.com/~/media/downloads/manuals/dssetup.ashx?la=en...
  • Page 10 EKM-E ETHER-MON KEY DE-211 1. Open or extract from the downloaded zip file “dssetup”. Fig. 11. 2. Open the software installer and click Run at this pop up window. Fig. 12. 31-00160—01...
  • Page 11 EKM-E ETHER-MON KEY DE-211 3. Click Next >. Fig. 13. 4. Select Configuration and Management Tools (deselect COM Port Mapping Tools). 5. Click Next >. Fig. 14. 31-00160—01...
  • Page 12 EKM-E ETHER-MON KEY DE-211 6. Click Next >. Fig. 15. 7. Click Next >. Fig. 16. 31-00160—01...
  • Page 13: Connecting The E10039 To A Pc

    EKM-E ETHER-MON KEY DE-211 8. Close / Exit the Configurator software window when it appears. Fig. 17. CONNECTING THE E10039 TO A PC 9. For this step, you will need a Cross-over Ethernet cable to connect your PC to the E10039. A Cross-over cable is not, the same as the Patch cable that came with the E10039 Ether-Mon key.
  • Page 14 EKM-E ETHER-MON KEY DE-211 10. Plug one end of the Cross-over cable into the LAN Ethernet port of your PC and the other end into the Ethernet RJ-45 port of the E10039 Ether-Mon key. Fig. 19. 11. The Orange Link LED should blink as it is acquiring the network and then light up solid. Fig.
  • Page 15 EKM-E ETHER-MON KEY DE-211 12. Open your PC Control Panel, click Network and Internet. Fig. 21. 13. Click Network and Sharing Center. Fig. 22. 31-00160—01...
  • Page 16 EKM-E ETHER-MON KEY DE-211 14. Click Change adapter settings (WIRED ONLY). Fig. 23. 15. Double Click Local Area Connection. Fig. 24. 31-00160—01...
  • Page 17 EKM-E ETHER-MON KEY DE-211 16. Click Properties. Fig. 25. 17. Click to highlight Internet Protocol Version 4 (TCP/IPv4). 18. Click Properties. Fig. 26. 31-00160—01...
  • Page 18 EKM-E ETHER-MON KEY DE-211 19. Select Use the following IP address. Fig. 27. 20. Next you will temporarily set the IP address of your computer to be a number close to the default IP address of the EKM-E Ethernet Key. a.
  • Page 19 EKM-E ETHER-MON KEY DE-211 b. Clicking into the Subnet mask field will auto populate to 255.255.255.0. Fig. 29. c. Click OK and close any of the Internet Protocol Version 4 properties screens. 21. Launch the NPort Management Suite Configurator software. Fig.
  • Page 20 EKM-E ETHER-MON KEY DE-211 Fig. 31. 22. Click → Locate Server → Specify by IP Address. Fig. 32. 23. Type in the E10039 default IP address of 192.168.127.254 and click OK. Fig. 33. 31-00160—01...
  • Page 21 EKM-E ETHER-MON KEY DE-211 24. Model DE-211 should auto populate the IP Address, MAC Address, and Status Fixed. Fig. 34. 25. Note if the Status displays Locked, type in the password emon if prompted. Fig. 35. Fig. 36. 31-00160—01...
  • Page 22 27. Click the boxes next to IP Address, Netmask, and Gateway to modify these for your LAN or WAN settings as provided by your Internet Service Provider (ISP) or Network Administrator. IMPORTANT! The IP configuration must a Static IP to communicate properly with Honeywell E-Mon Energy software. Fig. 38. 28. Click on the OP_Mode tab.
  • Page 23 EKM-E ETHER-MON KEY DE-211 30. Select TCP Server from the dropdown menu. Fig. 39. 31. Click More Settings. Fig. 40. 31-00160—01...
  • Page 24 EKM-E ETHER-MON KEY DE-211 Fig. 41. 32. Set up the TCP Server exactly as shown below. a. TCP Port 3000 b. Check the box for Delimiter 1 and set to 13 c. Check the box for Delimiter 2 and set to 10 d.
  • Page 25 UART FIFO Enable 35. Click the Password tab. 36. Select the box Change Password. 37. Honeywell E-Mon recommends using emon (lower case) as the defalt password in the event technical support requires remote access to configure the E10039 settings. 31-00160—01...
  • Page 26 EKM-E ETHER-MON KEY DE-211 38. Type in New Password emon (lower case). 39. Confirm Password emon (lower case). Fig. 44. 40. Click OK to save and upload all changes and settings. 41. Set Configuration uploaded settings Progress OK indicates finished. Fig.
  • Page 27 EKM-E ETHER-MON KEY DE-211 43. Open the Configurator utility to confirm IP address and Status is Locked Fixed. Fig. 46. Fig. 47. 44. Be sure to change your PC back to its original settings for the Internet Protocol Version 4. Fig.
  • Page 28 EKM-E ETHER-MON KEY DE-211 Fig. 49. IMPORTANT! Port 3000 TCP must be open on all routers or switches in the network. 31-00160—01...
  • Page 29: Ez7 Rs485 Wiring Typical Installation

    EKM-E ETHER-MON KEY DE-211 EZ7 RS485 WIRING TYPICAL INSTALLATION Fig. 50. Daisy Chain configuration shown in figure 2 on the left is correct, Star connection on the right is incorrect. Fig. 51. Correct Daisy Chain Configuration Fig. 52. 31-00160—01...
  • Page 30 EKM-E ETHER-MON KEY DE-211 Please see the specific product installation manual for more detailed EZ7 RS-485 wiring. Fig. 53. Fig. 54. Front View E10039. 31-00160—01...
  • Page 31: 2-Wire Rs-485 Terminal Block Wiring

    EKM-E ETHER-MON KEY DE-211 Fig. 55. 5 Position Screw Terminal Block. 2-Wire RS-485 Terminal Block Wiring Fig. 56. Terminal 1 SGND: Do not use the ground Terminal 2 RXDB (+) DATA B (+): to RS485 HI or + Terminal 3 RXDA (-) DATA A (-): to RS485 LO or - 31-00160—01...
  • Page 32: Ez7 Rs485 Wiring

    EKM-E ETHER-MON KEY DE-211 EZ7 RS485 Wiring How many EZ7 RS485 devices may be installed on one network trunk? Up to 52 devices may be installed on a network string (EZ7 RS485 only) read with E-MonEnergy software. What wire gauge do you need? Unterminated networks with current less than 10 mA;...
  • Page 33: Typical Cable Part Numbers

    EKM-E ETHER-MON KEY DE-211 TYPICAL CABLE PART NUMBERS Table 2. Communication Cables. Product Communication Characteristic Capacitance Code Description Standard Impedance (pF/ft.) Color Packaging Part Number 3319 24/1pr Stranded EIA-485, MS/TP, 12.5 Orange 1000’ Reel-in-a-Box 33192103 Shielded CMP ® BACnet 3323 24/1.5pr Stranded EIA-485, MS/TP, 12.5...
  • Page 34: Enabling Termination Resistor

    The impedance of the termination resistor should equal the characteristic impedance of the transmission line. The resistors should be added near the receiving side. Ω Honeywell E-Mon Recommends Enabling the Built-In 120 Terminator To enable the E10039’s built-in 120 Ω termination resistor, you must short the bottom two pins of jumper 6 (JP6), on DE- 211’s circuit board.
  • Page 35 EKM-E ETHER-MON KEY DE-211 31-00160—01...
  • Page 36 EKM-E ETHER-MON KEY DE-211 By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’...

This manual is also suitable for:

Nport express de-211

Table of Contents