Page 3
___________________ Line filter Safety information ___________________ General ___________________ Mechanical installation SINAMICS ___________________ Electrical installation SINAMICS G130 ___________________ Line filter Technical specifications Operating Instructions Control version V4.5 03/2012 A5E00331460A...
Page 4
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Safety information Warnings WARNING Hazardous voltages are present when electrical equipment is in operation. Severe personal injury or substantial material damage may result if these warnings are not observed. Only qualified personnel are permitted to work on or around the equipment. This personnel must be thoroughly familiar with all the warnings and maintenance procedures described in these operating instructions.
The operating manual and machine documentation are written in different languages as specified in the delivery contracts. Note We recommend engaging the support and services of your local Siemens service center for all planning, installation, commissioning and maintenance work. Line filter...
Safety information 1.3 Components that can be destroyed by electrostatic discharge (ESD) Components that can be destroyed by electrostatic discharge (ESD) CAUTION The board contains components that can be destroyed by electrostatic discharge. These components can be easily destroyed if not handled properly. If you do have to use electronic boards, however, please observe the following: •...
Page 10
Safety information 1.3 Components that can be destroyed by electrostatic discharge (ESD) Line filter Operating Instructions, 03/2012, A5E00331460A...
General Description The line filters limit the conducted interference emitted by the converter units to permissible values. To reduce emissions, the Power Modules are equipped as standard with a line filter in accordance with the limit values defined in category C3 (environment 2). The additional line filters described here can be fitted for use in environment 1 (category C2).
Page 12
If a high-voltage test is conducted with alternating voltage in the system, the line filter must be disconnected to obtain correct measurement results. CAUTION Using line filters not approved by SIEMENS for SINAMICS can lead to line-side harmonics that can interfere with or damage other loads powered from the network. CAUTION Provisions for component cooling must be made at the installation site.
Page 13
General Assignment of line filter and Power Module Table 2- 1 Assignment of line filter and Power Module Power Module Unit rating of the Power Module Suitable line filter Line voltage 380 – 480 V 3 AC 6SL3310-1GE32-1AAx 110 kW 6SL3000-0BE32-5AA0 6SL3310-1GE32-6AAx 132 kW...
Page 14
General Line filter Operating Instructions, 03/2012, A5E00331460A...
Mechanical installation When the line filter is installed in a cabinet, it must be positioned directly beside the Power Module. The line reactor must be positioned between the line filter and Power Module. Cabling must be kept as short as possible. To prevent interference being injected into the interference-suppressed line cable (this can, in some cases, nullify the effects of the line filter), the line cable to the line filter must be routed separately from other cables.
Page 16
Mechanical installation Table 3- 1 Dimensions of the line filter (all data in mm) 6SL3000- 0BE32-5AA0 0BE34-4AA0 0BE36-0AA0 0BE41-2AA0 0BG32-5AA0 0BG34-4AA0 0BG36-0AA0 0BG41-2AA0 78.2 78.2 127.5 Lengths n1 and n2 correspond to the drill hole spacing Line filter Operating Instructions, 03/2012, A5E00331460A...
Electrical installation Important safety precautions WARNING The devices are operated with high voltages. All connection procedures must be carried out when the cabinet is de-energized. All work on the device must be carried out by trained personnel only. Death, serious injury, or substantial material damage can result if these warnings are not taken into account.
Page 18
Electrical installation Connection When connecting the line filter and line reactor, you must take into account the following conditions to ensure that they function correctly: ● Use shielded control cables. The shield must be connected at both ends. ● With analog control cables, connecting the shield at both ends can result in coupled-in noise.
Technical specifications General technical data Table 5- 1 General technical data Line frequency 47 ... 63 Hz Product standard EN 61800-5-1 Overload capacity 1.60 x I for 3 s followed by 1.36 x I for 60 s followed by 1.00 x I for 240 s Ambient conditions Storage...
Page 20
Technical specifications Detailed technical data Table 5- 2 Technical data of line filter 380 V – 480 V 3 AC Order number 6SL3000- 0BE32-5AA0 0BE34-4AA0 0BE36-0AA0 0BE41-2AA0 Rated voltage 380 V 3 AC –10 % to 480 V 3 AC +10% (-15% < 1 min) Rated current I 1200 Power loss...
Page 21
Technical specifications Line filter Operating Instructions, 03/2012, A5E00331460A...