Mitsubishi Electric PZ-15RFP2-E Operating Instructions

Mitsubishi Electric PZ-15RFP2-E Operating Instructions

Advanced high efficiency filter for mitsubishi energy recovery ventilator lossnay

Quick Links

ADVANCED HIGH EFFICIENCY FILTER FOR MITSUBISHI ENERGY RECOVERY VENTILATOR LOSSNAY
Models:
PZ-15RFP
-E・PZ-25RFP
-E・PZ-35RFP
2
2
PZ-65RFP
-E・PZ-80RFP
-E・PZ-100RFP
2
2
Operating Instructions
The Advanced High Efficiency Filter is designed for commercial use Lossnay ventilators to collect small
particles present in outdoor air supplied into the room. It can be replaced with one already mounted in
Lossnay unit.
■ For applicable models and quantities required, refer to the separate delivery specifications, products brochure, etc.
■ Please read through these instructions to understand the proper and safe procedures for operating the Lossnay.
After reading these operating instructions, keep it in an easily accessible and safe place for future reference.
Safety precautions
The following symbols denote the danger and its
degree that may result from incorrect use.
Denotes misuse that could
WARNING
cause serious injury or death.
●Always turn off the Lossnay ventilator
before installing or replacing the filter.
Failure to heed this warning may result
in electric shock or injury.
Prohibited
Denotes misuse that could
CAUTION
cause injury or damage to
properties.
●Wear gloves when installing the filter.
Otherwise, edges may cause injury.
●The filter contains a small amount of
glass fiber. If you have any of the
following problems, please respond as
described and see a doctor if necessary.
・In case of inhalation of large quantities
of product dust (eg glass or synthetic
fibers), immediately remove to fresh
air and wash out of mouth.
Important
・If product dust adheres to the skin,
wash it away with running water
immediately.
・If product dust enters your eyes, rinse
immediately with running water.
Remove contact lenses immediately.
・If product dust is swallowed, exhale
and rinse mouth thoroughly with water
immediately.
2004876H51101
-E・PZ-50RFP
-E
2
2
-E
2
(For the user)
Outline drawings and Materials
A
■ Dimensions
Unit (mm)
Model
A
PZ-15RFP
-E
553
123
2
PZ-25RFP
-E
327
148
2
PZ-35RFP
-E
393
175
2
PZ-50RFP
-E
464
175
2
PZ-65RFP
-E
427
209
2
PZ-80RFP
-E
446
236
2
PZ-100RFP
-E
559
236
2
Materials are shown below, please dispose properly
according to the laws of each country.
Frame: Vinyl chloride
Filter: Synthetic fiber (PP, PET, Glass, Pulp, PVA, Acrylic
resin, PE )
Filtration specification
ASHRAE 52.2-2017: MERV16
ISO16890-2016: ePM
75%, ePM
80%, ePM
95%,
1
2.5
10
GB/T 14295-2008: YG class, 99.7%
* Filtration specification are results of tests conducted by
third-party certification bodies and are not a guaranteed
value.
Replacing (Installation)
Opening the maintenance cover may vary
depending on the model. Refer to the instruction
manual of Lossnay for more information.
1. Remove the maintenance cover.
1) Remove the black screw.
2) Slide the fix piece to out side.
3) Open hinge wire.
Maintenance cover
Fix piece
Hinge wire
2. Remove the Advanced high efficiency filters from
the upper right side of the Lossnay cores in the
case that Lossnay unit is installed standard.
25
B
Note
●When Lossnay unit is installed upside down,
Advanced high efficiency filters position is lower left
side.
3. Fill the installation date in the date entry sticker
pasted on the new Advanced high efficiency
filter. It is useful as a guide to determine the
next replacing time required.
Lossnay core
Air filter
2-7-3 Marunouchi, Chiyoda-ku, Tokyo, 100-8310 Japan
4. Push to engage the two guides of the new
Advanced high efficiency filter with the frame of
the Lossnay core so that the frame gets caught
between them; an arrow indicated on the filter
should face against the Lossnay core as shown
in the figure.
●Use a Velcro fasteners to tie up two filters. Hold the
filters up to push onto the frame in the same way as
above. (For PZ-25 to 100RFP
Frame
Guide
Velcro fastener
Lossnay
core
Black screw
Air filter
Advanced high
efficiency filter
Note
Lossnay core
●When replacing an Advanced high efficiency filter,
always clean (or replace) the air filters built in the
Lossnay ventilator.
5. Install the maintenance cover in the reverse
order of the procedure shown in "1". The cover
should be in the correct direction such that its
nameplate is legible.
Note
●This filter is a disposable filter and not cleanable/washable.
Please replace to new one when clogging. The following
table shows the approximate replacement time when the
daily operation time is 10 hours and the annual operation
days are 250 days. This is the calculation result on each
air condition, so please adjust the replacement cycle
Velcro fastener
considering the air environment in the area where the
Air flow arrow
product is actually installed and operating time and day.
Advanced high
Dust concentration
efficiency filter
PM2.5
Installation date
Air condition 1
18.5
(sticker)
Air condition 2
35.0
Air condition 3
100.0
-E)
2
Air flow arrow
Advanced high efficiency filter
Installation date (sticker)
Guide
Frame
Lossnay
Advanced high
core
efficiency filter
Standard
installation
Control
Control
Air filter
box
box
Up-side-down
installation
Advanced high
Lossnay
efficiency filter
core
(μg/m
3
)
Replacement
period
PM10
28.5
24 months
65.0
12 months
225.0
4 months
loading

Summary of Contents for Mitsubishi Electric PZ-15RFP2-E

  • Page 1 2004876H51101 Replacing (Installation) Opening the maintenance cover may vary 4. Push to engage the two guides of the new depending on the model. Refer to the instruction Advanced high efficiency filter with the frame of manual of Lossnay for more information. the Lossnay core so that the frame gets caught ADVANCED HIGH EFFICIENCY FILTER FOR MITSUBISHI ENERGY RECOVERY VENTILATOR LOSSNAY between them;...
  • Page 2 更換(安裝) 維護罩的開啟方式會因機型而有所不同。如需 4. 將新高級強效型濾網的兩個導軌下壓以使其和 Lossnay核心的框架結合,讓框架卡在兩者之 了解其他資訊請參閱 Lossnay 使用說明書。 間;如圖所示,濾網上的指示箭頭應面向 三菱能源回收式通風機 LOSSNAY 專用之高級強效型濾網 1. 取下維護罩。 Lossnay 核心。 1) 取下黑色螺絲。 型號: ● 使用黏扣帶將兩個濾網捆住。拿起濾網並以上述相同 2) 將固定件向外側滑動。 PZ-15RFP -E・PZ-25RFP -E・PZ-35RFP -E・PZ-50RFP 的方法壓到框架上。(適用於 PZ-25 至 100RFP -E) 3) 打開絞鏈。 PZ-65RFP -E・PZ-80RFP -E・PZ-100RFP 框架 導軌 維護罩 黏扣帶...

This manual is also suitable for:

Pz-65rfp2-ePz-25rfp2-ePz-80rfp2-ePz-35rfp2-ePz-100rfp2-ePz-50rfp2-e