APPLICATION

The F111 (Series 11000) Ceiling Media Air Cleaner is a media
air cleaner that uses a single-speed direct drive forward curve
blower motor with particle filter. When equipped with CPZ™
modules (2), gases and odors are absorbed from the air
passing through the unit. The air cleaner removes airborne
particles such as dust, soot, mold spores, pollen and some
cooking smoke from the air circulated through the filter.
® U.S. Registered Trademark
© 2004 Honeywell International Inc.
All Rights Reserved
In Ceiling Media Air Cleaner
F111 (Series 11000)

FEATURES

• High Efficiency Particulate Air (HEPA) filter models are
99.97% efficient and the hospital grade particle filter
models are 95% efficient at 0.3 micron particles. Both
models are more efficient on particles smaller and
larger. There is also a 95% ASHRAE model.
• Circulates up to 1230 cfm.
• Designed to overcome the increase in air flow
resistance normally caused by filter loading.
• White color cover to complement the ceiling.
• CPZ™ module removes up to 95% of the space odors
for up to 24 months.
Application.........................................................................1
Features ............................................................................1
Specifications ....................................................................2
Ordering Information .........................................................2
Planning the Installation ....................................................3
Installation .........................................................................4
Operation...........................................................................6
Service ..............................................................................6
Parts List ...........................................................................8
Limited Two-Year Warranty ...............................................10
PRODUCT DATA
Contents
68-0198EF-2
Table of Contents
loading

Summary of Contents for Honeywell 11000 Series

  • Page 1: Table Of Contents

    Contents Application.................1 Features ................1 Specifications ..............2 Ordering Information ............2 Planning the Installation ............3 Installation .................4 Operation................6 Service ................6 Parts List ................8 Limited Two-Year Warranty ..........10 ® U.S. Registered Trademark © 2004 Honeywell International Inc. 68-0198EF-2 All Rights Reserved...
  • Page 2: Specifications

    If you have additional questions, need further information, or would like to comment on our products or services, please write or phone: 1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory). 2. Honeywell Customer Care...
  • Page 3: Planning The Installation

    F111 (SERIES 11000) IN CEILING MEDIA AIR CLEANER If any questions should arise concerning determining the number of air cleaners needed for an area, consult your TOP VIEW distributor or local Honeywell Commercial Air Cleaner Distributor. 3/8 X 16 INTERNAL Table 3.
  • Page 4: Installation

    Risk of Fire or Electric Shock. Can cause personal injury or equipment damage. IMPORTANT Use only Honeywell 32000234 (41105) Variable Speed This air cleaner has not been investigated for use in Switch (accessory) to regulate air cleaner speed. the ceilings of fire-resistant assemblies.
  • Page 5 F111 (SERIES 11000) IN CEILING MEDIA AIR CLEANER 3. Use the four 3/8 x 16T internal nuts (one at each corner) IMPORTANT to fasten the cabinet to a structural support (bar joist, Do not touch the pleated filter media. Handle only the concrete slab or timber framing).
  • Page 6: Operation

    F111 (SERIES 11000) IN CEILING MEDIA AIR CLEANER Removing /Replacing the Lid Local, Federal and professional ventilation engineering standards and codes prescribe minimum ventilation rates to dilute air contamination in specific applications. The IMPORTANT ventilation rates usually assume the injection of outdoor air The lid is heavy.
  • Page 7 F111 (SERIES 11000) IN CEILING MEDIA AIR CLEANER 5. Install the new filter. Note direction of airflow arrows, if 1. Slowly open the lid, supporting the lid so the filters do present. If arrows are not present, install the filter with not fall out.
  • Page 8: Parts List

    F111 (SERIES 11000) IN CEILING MEDIA AIR CLEANER PARTS LIST Refer to Fig. 8 and Table 4 for replacement part information. Table 4. Replacement Parts. Fig. Reference No. Description Pack Qty Order Number Reference No. CPZ™ sorbent module (requires 2)—used with only 32004078-001 31005 95% HEPA or 95% ASHRAE particle filters...
  • Page 9 F111 (SERIES 11000) IN CEILING MEDIA AIR CLEANER CABINET ASSEMBLY SORBENT MEDIA MODULE (2 REQUIRED) CPZ PART 32004078-001 CHARCOAL PART 32004078-002 ZEOLITE PART 32004078-003 PERMANGANATE PART 32004078-004 BLOWER WHEEL PART 32002285 MOTOR CAPACITOR 120V, 60 HZ PART 32000265 208/230V, 50/60 HZ PART 32000549 277V, 60 HZ PART 32000550 MOTOR 120V, 60 HZ PART 32000270...
  • Page 10: Limited Two-Year Warranty

    LIMITED TWO-YEAR WARRANTY Honeywell Inc. warrants its air cleaner products to be free from defects in workmanship or materials under normal use and service, for a period of two (2) years from the date of purchase by the original end-user. If at anytime during the warranty period the product is defective or malfunctions, Honeywell Inc., through the distributor or dealer, from which the product was purchased, or through an authorized warranty repair station, shall at...
  • Page 11 Fiche technique ..............Pour commander............... Planification de l’Installation ..........Installation ................ Fonctionnement ..............Entretien ................Liste des pièces..............Garantie limitée de deux ans..........10 ® Marque de commerce déposée aux É.-U. 68-0198EF-2 © 2004 Honeywell International Inc. Tous droits réservés...
  • Page 12 Prière d'adresser toute question additionnelle, demande d'information ou commentaires sur les produits et services par écrit ou par téléphone : 1. Au bureau des ventes de produits de régulation et d'automatisation Honeywell de votre localité (consulter les pages blanches de l'annuaire téléphonique).
  • Page 13 Pour toute question sur la façon de déterminer le nombre de filtres à air requis dans une pièce donnée, prière de consulter VUE DE DESSUS le distributeur local de filtres à air Honeywell. FILETAGE Tableau 3. Nombre de filtres à air requis en général par INTERNE volume.
  • Page 14 N’utiliser que le commutateur à vitesse variable 32000234 (41105) de Honeywell (offert en option) pour régler la vitesse du filtre à air. L’utilisation d’un MISE EN GARDE autre régulateur de vitesse peut rendre nulle la garantie.
  • Page 15 FILTRE À AIR À ÉLÉMENT FILTRANT À FIBRES ENCASTRÉ AU PLAFOND F111 (SÉRIE 11000) 3. Utiliser les quatre écrous 3/8 x 16 de filetage interne (un 8. Fixer les languettes du filtre. S’assurer d’entendre le à chaque coin) pour fixer le bâti au support de structure déclic lorsque le filtre est bien mis en place.
  • Page 16 FILTRE À AIR À ÉLÉMENT FILTRANT À FIBRES ENCASTRÉ AU PLAFOND F111 (SÉRIE 11000) Ouverture et fermeture du couvercle Le nombre minimum de changements d’air recommandé est de 2,5 renouvellements à l’heure. Dans une salle très polluée, Pour ouvrir le couvercle, tirer le verrou à ressort vers l’arrière il se peut que jusqu’à...
  • Page 17 FILTRE À AIR À ÉLÉMENT FILTRANT À FIBRES ENCASTRÉ AU PLAFOND F111 (SÉRIE 11000) Module de sorbant CPZ 3. Installer le nouveau préfiltre dans le couvercle du filtre à air. Placer le filtre de métal de façon à ce qu’il soit Le module de sorbant CPZ sert à...
  • Page 18 FILTRE À AIR À ÉLÉMENT FILTRANT À FIBRES ENCASTRÉ AU PLAFOND F111 (SÉRIE 11000) LISTE DES PIÈCES Voir la Fig. 8 et le Tableau 4 pour obtenir des renseignements sur les pièces de rechange. Tableau 4. Pièces de rechange. de référence Qté...
  • Page 19 FILTRE À AIR À ÉLÉMENT FILTRANT À FIBRES ENCASTRÉ AU PLAFOND F111 (SÉRIE 11000) BÂTI MODULE DE SORBANT CPZ (IL EN FAUT 2) 32004078-001 MODULE DE CHARBON (IL EN FAUT 2) 32004078-002 MODULE DE ZÉOLITE (IL EN FAUT 2) 32004078-003 MODULE DE PERMANGANATE (IL EN FAUT 2) 32004078-004 ROTOR DE VENTILATEUR 320002285...
  • Page 20 GARANTIE LIMITÉE DE DEUX ANS Honeywell garantit que le présent produit est exempt de tout vice de fabrication ou de matière dans la mesure où il en est fait un usage et un entretien convenables et ce, pour une période de deux (2) ans à partir de la date d’achat par un consommateur. En cas de défectuosité ou de mauvais fonctionnement pendant la période de garantie, Honeywell, par l’entremise du distributeur ou du détaillant qui a vendu le produit au...

Table of Contents