12.9.1 Extended speed supervision

Additional supervision limits can be activated via the OEM level for different operating
states. A check is only carried out to determine whether the value was exceeded or
fallen short of here. A shutdown takes place after the Maximum time outside close range
(parameter 665, default setting 3 s) has elapsed. An interruption in the speed feedback
signal results in a safety shutdown within 1 second.
These limits can also be activated in pneumatic operation if a speed signal is present.
No.
Parameter
226
Gas: Preignition time
266
Oil: Preignition time
665
Speed supervision: Maximum time outside close range
667
Minimum prepurge speed
668
Maximum ignition speed
669.0
Minimum / maximum speed limitation in operation
Index 0 = minimum speed
669.1
Minimum / maximum speed limitation in operation
Index 1 = maximum speed
Speed
Valid
prepurging
range
Minimum
prepurge
speed
(parameter
667)
Start
Prepurge
phase
phase
Figure 86: Extended speed supervision
Note!
The standardization in pneumatic operation is only possible if at least one
extended speed supervision has been activated (parameter 667, 668 or 669.0 /
669.1). The supervisory functions are deactivated in the presetting
When supervising the maximum ignition speed, the preignition time (parameter
226 / 326 or 266 / 366) must correspond to at least the time setting Maximum
time outside close range (parameter 665)
Basic documentation LMV37.4...