Mitsubishi Electric CITY MULTI PURY-HP72TNU-A Data Book page 12

Air conditioning systems
Table of Contents
1. SPECIFICATIONS
Outdoor Model
Indoor Model
Power source
Cooling capacity
(Nominal)
Power input
(460) Current input
(Rated)
Power input
(460) Current input
Temp. range of
Indoor
cooling
Outdoor
Heating capacity
(Nominal)
Power input
(460) Current input
(Rated)
Power input
(460) Current input
Temp. range of
Indoor
heating
Outdoor
Indoor unit
Total capacity
connectable
Model/Quantity
Sound pressure level (measured in anechoic room) *3 dB
Sound power level (measured in anechoic room) *3
Refrigerant
High pressure
piping diameter
Low pressure
Minimum Circuit Ampacity
Maximum Overcurrent Protection
FAN
Type x Quantity
Airflow rate
Control, Driving mechanism
Motor output
*4 External static press.
Compressor
Type x Quantity
Manufacture
Starting method
Motor output
Case heater
Lubricant
External finish
External dimension H x W x D
Protection
High pressure protection
devices
Inverter circuit (COMP./FAN)
Fan motor
Refrigerant
Type x original charge
Control
Net weight
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Defrosting method
Drawing
External
Wiring
Standard
Document
attachment
Accessory
Optional parts
Remarks
Notes:
1.Nominal cooling conditions (Test conditions are based on AHRI 1230)
Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Nominal heating conditions (Test conditions are based on AHRI 1230)
Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.Cooling mode/Heating mode
4.External static pressure option is available (0.12 in.WG, 0.24 in.WG, 0.32 in.WG/30 Pa, 60 Pa, 80 Pa).
* Due to continuing improvement, above specifications may be subject to change without notice.
MEES19K180
Non-Ducted
*1 BTU/h
kW
kW
A
BTU/h
kW
kW
A
W.B.
D.B.
*2 BTU/h
kW
kW
A
BTU/h
kW
kW
A
D.B.
W.B.
in. (mm)
in. (mm)
A
A
cfm
3
m
/min
L/s
kW
kW
kW
in.
mm
lbs (kg)
joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1,CMY-R201,202,203,301,306S-G,CMY-R302,303,304,305S-G1
Main BC controller: CMB-P108,1012,1016NU-JA1,CMB-P1016NU-KA1
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
PURY-HP120YNU-A
3-phase 3-wire 460 V ±10% 60 Hz
120,000
35.2
8.82
12.3
114,000
33.4
8.04
11.2
59~75°F (15~24°C)
23~126°F (-5~52°C)
135,000
39.6
10.07
14.0
129,000
37.8
9.01
12.5
59~81°F (15~27°C)
-22~60°F (-30~15.5°C)
50~150% of outdoor unit capacity
P04~P96/1~30
64.0/65.0
84.0/85.0
3/4 (19.05) Brazed
1-1/8 (28.58) Brazed
21
35
Propeller fan x 2
9,550
270
4,500
Inverter-control, Brushless DC motor
0.46+0.46
0 in.WG (0 Pa)
Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Inverter
7.8
-
MEL46
Pre-coated galvanized steel sheet
71-5/8 x 49-1/4 x 29-3/8
1,818 x 1,250 x 745
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current protection
-
R410A x 23 lbs + 12 oz (10.8 kg)
Indoor LEV and BC controller
697 (316)
Salt-resistant cross fin & copper tube
-
Auto-defrost mode (Reversed refrigerant cycle)
KB94C0H0
KE94G817
Installation Manual
Details refer to External Drw
BC controller: CMB-P104,106,108,1012,1016NU-J1
Sub BC controller: CMB-P104,108NU-KB1
Hyper Heating Inverter R2-Series
Ducted
8.29
11.5
9.63
13.4
Unit converter
BTU/h
=kW x 3,412
3
cfm
=m
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.
10
Table of Contents
loading

Table of Contents