13. OUTDOOR INSTALLATION
In case of collective installation and continuous installation
• When installing multiple units, make sure to take into consideration factors such as providing enough space for people to pass through,
ample space between blocks of units, and sufficient space for airflow. (The areas marked with [A] in the figures below must be left open.)
• In the same way as with the single unit installation, add the dimension that exceeds the height limit (shown as "h1" through "h3" in the figures) to L1, L2,
and L3 as shown in the tables below.
• If there are walls in the front and rear of the block of units, up to six units can be installed consecutively side by side, and a space of 1000 mm (39-3/8 in)
or more must be left between each block of six units.
(1) Side-by-side installation
When the distances between the units (L4) need to
be small
[A]
L4
h1
Unit height
Required minimum distance [mm (in)]
L1 (Front)
L2 (Rear)
450 (17-3/4) + h1
450 (17-3/4) + h2
(2) Face-to-face installation
When there are walls in the front and rear of the
block of units
[A]
h1
Unit height
L1
Required minimum distance [mm (in)]
L1 (Front)
L2 (Rear)
450 (17-3/4) + h1
300 (11-13/16) + h2
(3) Combination of face-to-face and side-by-side installations
When there are walls in the front and rear of the
block of units
[A]
h2'
Unit height
L2'
Required minimum distance [mm (in)]
L2 (Rear)
450 (17-3/4) + h2
450 (17-3/4) + h2'
[A]: Leave open in two directions.
MEES19K180
h2
Unit height
L2
[A]
L1
L4 (Between)
30 (1-3/16)
h2
Unit height
L2
L4
[A]
L4
L4 (Between)
450 (17-3/4)
h2
Unit height
Unit height
L2
L4
[A]
L2' (Rear)
L4 (Between)
900 (35-7/16)
When the distance behind the block of units (L2) needs
to be small
[A]
L4
Unit height
Required minimum distance [mm (in)]
L1 (Front)
450 (17-3/4) + h1
300 (11-13/16) + h2
When there is a wall on either the right or left side of the
block of units
h3
Unit height
L3
Required minimum distance [mm (in)]
L3 (Right/Left)
30 (1-3/16) + h3
When there are two walls in an L-shape
h3
L3
[A]
Required minimum distance [mm (in)]
L2 (Rear)
L3 (Right/Left)
450 (17-3/4) + h2
1000 (39-3/8) + h3
Hyper Heating Inverter R2-Series
h2
Unit height
h1
L2
[A]
L1
L2 (Rear)
L4 (Between)
450 (17-3/4)
L4
L4
L4 (Between)
450 (17-3/4)
[A]
L4
L4 (Between)
900 (35-7/16)
[mm (in)]
h2
Unit height
L2