Low Pressure Sensor (63Ls) Trouble; 5202 - Mitsubishi Electric PUMY-P250YBM Technical & Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P250YBM:
Table of Contents
Check code

5202

(F3)
Abnormal points and detection methods
When the detected pressure in the low pressure sensor is −2.3kgf/F
or less, or 23.1kgf/F or more during operation, the compressor stops
operation with check code <5202>.
For 3 minutes after compressor restarting, during defrosting operation,
and for 3 minutes after returning from defrosting operation, above
mentioned symptoms are not determined as abnormal.
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting
any connectors, or replacing boards.
Check the wiring and connector
connection.
Is there any abnormality such
as disconnection, looseness or
breakage?
Check an internal pressure of the
refrigerant circuit.
Is the detected internal pressure
normal?
Check the detected pressure in 63LS, then
compare it with the internal pressure.
Is the detected pressure normal?
OCH760

Low pressure sensor (63LS) trouble

Diagnosis
No
Yes
Yes
Causes and checkpoints
Defective low pressure sensor
Decrease of internal pressure caused by gas
leakage
Disconnection or contact failure of connector
Malfunction of input circuit on outdoor multi controller
circuit board
The black square (■) indicates a switch position.
63LS: Low pressure sensor
Connect the wiring/connector properly.
Yes
Replace it in the case of breakage.
Check the refrigerant circuit, and recharge
No
refrigerant after repairing the leakage.
The detected pressure in 63LS can be displayed by an
operation of SW1 on the outdoor multi controller circuit board.
SW1 Setting
Display on LED1,2
ON
−99.9–999.9
OFF
1 2 3 4 5 6 7 8
No
Replace the outdoor multi controller circuit
board.
72
Remedy
Unit
kgf/cm²
Replace the 63LS.
Table of Contents
loading

Table of Contents