Honeywell Ex-Or Digital Gold Series Installation And Commissioning Instructions

Honeywell Ex-Or Digital Gold Series Installation And Commissioning Instructions

Digital detector with regulating photocell

Quick Links

MLS2421DF & MLS2421DSM for DSI ballasts
MLS2421DALIF & MLS2421DALISM for DALI ballasts
Digital Gold Series Detector
with regulating photocell
MLS2421DF
MLS2421DALIF
MLS2421DALIFXAA
MLS2421DSM
MLS2421DALISM
Installation and Commissioning
Instructions
Note: QuickSet Pro required for commissioning
loading

Summary of Contents for Honeywell Ex-Or Digital Gold Series

  • Page 1 MLS2421DF & MLS2421DSM for DSI ballasts MLS2421DALIF & MLS2421DALISM for DALI ballasts Digital Gold Series Detector with regulating photocell MLS2421DF MLS2421DALIF MLS2421DALIFXAA MLS2421DSM MLS2421DALISM Installation and Commissioning Instructions Note: QuickSet Pro required for commissioning...
  • Page 2 Digital Gold Series Detector with Regulating Photocell Please note that UltraLite versions of these detectors (suffix CWL7) do not offer MLS functionality and cannot be connected using MLS cable. Only suitably qualified personnel should install this equipment. The Digital Gold is a high-performance, communicating presence detector which can be used as part of a full Ex-Or MLS Digital Managed Lighting System or as a stand-alone unit.
  • Page 3: Electrical Connections

    Electrical Connections These Digital Gold detectors should be connected in accordance with the diagrams below. Both the Digital Output and MLS connections are polarity-free however other MLS products require that polarity be maintained. The MLS cable should be mains-rated, unscreened, twisted pair of at least 1.5mm CSA. For further information please refer to Wiring Application Guide AN4001.
  • Page 4 Commissioning The units are supplied with the factory default settings shown below which render commissioning unnecessary in many applications. To make use of the programmable settings, an infrared commissioning tool is required (QuickSet Pro). A ten-second time delay is selectable to aid commissioning. Sensitivity to Movement While the factory settings will be correct for many applications, the sensitivity can be adjusted if required.
  • Page 5 Photocell Control i) Regulating Photocell Regulating photocell control tries to maintain a constant level of total illumination in the space controlled by dimming and brightening the controlled luminaires to compensate for changes in illumination from other sources. With the photocell configured as DISABLED the Regulating Control module is influenced only by the BRIGHT-OUT setting.
  • Page 6 ii) The Primary Interest is the Switching Control Output With the photocell configured as ACTIVE or PASSIVE:- 1) If the lights are not already on, switch them on manually by pressing ‘UTILITIES / LIGHTSPOT/MLS/LCM / IR REMOTE / HC5 / Luminaire+/OK’ (QuickSet Pro) or "+" (HC5A). Fluorescent lights do not reach full output until up to 15 minutes after being switched on, so ensure that the lights are fully warmed up before continuing.
  • Page 7 Important Additional Notes All terminals on this product are provided for final connections. It is not intended that the product be used as a junction box for looping cables. A means for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations.
  • Page 8 COLOUR: White RAL 9010 WEIGHT: 243g (flush version), 251g (surface version) IP RATING: 2X OPERATING TEMPERATURE: 0 C to 40 C Honeywell Ex-Or St. Marks Court, North Street, Horsham, West Sussex, RH12 1BW, UK At the end of their useful life...