Huawei NetCol5000 C030H6B20 10020E1 Quick Manual

In-row chilled water smart cooling product

Quick Links

NetCol5000-C030 In-row Chilled Water
Smart Cooling Product
Quick Guide (Simple Configuration)
Issue: 07
Date: 2019-01-15
1
Overview
Cooling
Model
Capacity
(kW)
30
NetCol5000
30
-
C030H6B20
30
10020E1
30
NetCol5000
-
30
C030H6B20
10020E0
30
NetCol5000
-
30
C030H7B20
1E120E0
30
NetCol5000
30
-
C030H7B20
30
10020E1
NetCol5000
-
30
C030H7A20
1E120E0
NetCol5000
-
30
C030H7A20
10020E1
Air
Pipe
Deflector
Routing
Door
Bottom
No
piping
Bottom
No
piping
No
Top piping
No
Top piping
Bottom
Yes
piping
Top or
No
bottom piping
Top or
Yes
bottom piping
Top or
Yes
bottom piping
Top or
Yes
bottom piping
Top or
Yes
bottom piping
Top or
No
bottom piping
Top or
No
bottom piping
Heat
Water
and
Humidif
Pump
y
Yes
No
Yes
No
Yes
No
Yes
No
No
No
No
Yes
No
Yes
No
Yes
Yes
No
Yes
No
No
Yes
Yes
No
1
Copyright © Huawei Technologies Co., Ltd. 2019 All rights reserved.
Net
Dimension (mm)
Weight
(H x W x D)
(kg)
160
2000 x 300 x 1000
165
2000 x 300 x 1200
160
2000 x 300 x 1000
165
2000 x 300 x 1200
166
2000 x 300 x 1200
168
2000 x 300 x 1000
172
2000 x 300 x 1100
174
2000 x 300 x 1200
165
2000 x 300 x 1100
170
2000 x 300 x 1200
171
2000 x 300 x 1000
165
2000 x 300 x 1000
Table of Contents
loading

Summary of Contents for Huawei NetCol5000 C030H6B20 10020E1

  • Page 1 2000 x 300 x 1200 10020E1 bottom piping NetCol5000 Top or 2000 x 300 x 1000 C030H7A20 bottom piping 1E120E0 NetCol5000 Top or 2000 x 300 x 1000 C030H7A20 bottom piping 10020E1 Copyright © Huawei Technologies Co., Ltd. 2019 All rights reserved.
  • Page 2: Material Preparations

    The picture uses NetCol5000- C030H6B2010020E1 as an example. For the structure of other products, refer to their respective structures. Material Preparations Without the NetCol520 With the NetCol520...
  • Page 3 Condensate drainpipe, hose clamp and pagoda connector on main chilled Pipes water pipes Delivered Corrugated pipe for cabling, OT terminal, cord end terminal, 10 m cable of Materials network cable for teamwork (Silkscreen is W11), cabinet exterior humidity Cables and temperature sensor and its cable (Silkscreen is W12, 1 PCS in standard delivery), cable tie •...
  • Page 4: Installing The Device

    5. Keep the equipment upright during transportation. Tilting is forbidden. 6. Qualified electricians are required. Slowly Opening the Exhaust Removing the Air Filters Valve to Discharge Nitrogen The device has been charged 0.3–0.5 MPa nitrogen. If no nitrogen emits, contact Huawei technical support.
  • Page 5 (Bottom Piping for an Example) Connecting Water Pipe Connectors Install the water pipe adapters first, because it lacks Remove side panels space to install them after combining the cabinet. Three water pipes with 25 mm inner diameter can be connected: (1) rubber hose, (2) aluminum plastic pipe or PPR pipe, (3) seamless steel pipe.
  • Page 6 Removing the Connecting Kit from Transportation the Front and Rear Plates NOTE Screws connecting the adapter plate and cabinet are M10. Screws connecting the adapter plate and base are M12. A manual pallet truck is usually used to transport the cabinet. If a pallet truck is unavailable or not allowed, transport the cabinet by manpower.
  • Page 7 2. Level the cabinet. 3. Install the air baffle. M10x25 (4 PCS) 30 N•m NOTE Conversion bracket is no use when it is non- anchored installation on an ESD floor. Anchored installation with a base 1. Level the cabinet on the base. 2.
  • Page 8 Combining Cabinets from Front and Rear Door 1. Do not remove anchor bolts. Otherwise, you need to rework them for use. 2. Level the cabinet with the help of a measuring tape. Check that the vertical distance between the top of the cabinet and the floor is 2000 mm (tolerance±3 mm) and that the cabinet is...
  • Page 9 Installing Pipes Piping 1. The condensate pump drainpipe and auto-drainpipe should not be connected together to avoid water in the auto-drainpipe flowing back to the pump, which will cause the pump to be faulty, as shown in the following figure. 2.
  • Page 10 Bottom water inlet scenario Top water inlet scenario Connecting Auto-drainpipe Method 1 (Connecting a rubber hose): Remove reserved pipe, and install DN19 rubber hose and the clamp (required torque: 4 N•m). Warp the thermal insulation foam. Reserved Rubber Thermal pipe hose insulation foam...
  • Page 11 Method 2 (Connecting a PPR or aluminum plastic pipe): Remove plug. Connect conversion adapter (sealing with thread chloroprene adhesive, 25 N•m torque) and PPR pipe, or aluminum plastic pipe. Thermal PPR pipe or insulation foam aluminum plastic pipe Connecting Water Pump Drainpipes Bottom drainage scenario Top drainage scenario Water pump...
  • Page 12 Leak Checking (Bottom Piping) Connecting Water Inlet and Outlet Pipes 1. Hold down the button and rotate the handle to manually turn the chilled water valve to 100%. 2. Confirm that the needle valves and exhaust valves on the pipeline are closed. 3.
  • Page 13: Connecting Cables

    Connecting Cables Electrical Ports Introduction 1. Electrical Ports of NetCol5000-C030H6 Humidity and Temperature (T/H) Sensor port Teamwork networking port Remote shutdown cable port 2. Electrical Ports of NetCol5000-C030H7 Humidity and Temperature (T/H) Sensor port Teamwork networking port Remote shutdown cable port Connecting Power Cables and the Equipotential Ground Cable 1.
  • Page 14 Top cabling M6x16 (1 PCS) 3 N•m Bottom cabling M6x16 (1 PCS) 3 N•m...
  • Page 15 (Optional) Setting the Power Switch This step applies only to the NetCol5000-C030H7. Turn the power switch to the position with the same line voltage as the input line voltage using a flat-head screwdriver. Connecting the T/H Sensor 1. Connect the humidity and temperature (T/H) sensor cable (Silkscreen is W12.) NOTE The sensor in the fitting bag can be installed in the aisle.
  • Page 16 EMS Monitoring Teamwork Networking NOTE • All smart cooling products in a teamwork group must be of the same model. • Do not directly connect the first and the last smart cooling products to form a ring network. • A maximum of 32 NetCol8000-Cs are supported. In a teamwork communication, the cable length of two adjacent smart cooling products must be shorter than 10 m.
  • Page 17: Verifying The Installation

    Y-split cable connection for teamwork control Verifying the Installation Check Item Result Check the drainpipes are securely installed, clear, free of leakage (the □Passed □Failed hose gradient is 1:100), and not over bent. □Passed □Failed Wrap the chilled water pipe connector with heat insulation foam tightly. Check that the floats are leveled and the impurities, such as cables and □Passed □Failed insulation foam, are cleaned.
  • Page 18 Basic Settings For initial power-on, the system enters the quick setting screen. Set the Language, Date format, Date, Time, Zone, Monitor mode, and verifying the present voltage. For non-initial power-on, the LCD automatically enters the home screen. NOTE 1. Users include Admin, Engineer, Operator, and Guest. The Admin users have the highest permission, followed by the Engineer, Operator, and Guest users.
  • Page 19 1. CAN networking: In each CAN teamwork unit, a maximum of 32 smart cooling products can be connected. In each EMS, a maximum of four teamwork networkings are supported. One teamwork networking is recommended for the response speed of EMS. 2.
  • Page 20: Follow-Up Procedure

    5. Turn on the humidifier to maximum valve on the diagnostic mode page. After the humidifier is started, the water supply solenoid valve leads to a higher liquid level in the humidifier cylinder (figure 1). Water supply is smooth and the water pipe is free from leakage. After 10 minutes, the water inside the humidifier cylinder is with bubbles or boils (figure 2).
  • Page 21: Routine Maintenance

    Secure the sensors again. Monthly products and aisles are securely installed. For details about routine maintenance tasks, please download NetCol5000-C030 In-row Chilled Water Smart Cooling Product User Manual (Simple Configuration) from Huawei technical support website. Troubleshooting Temperature Sensor Fault 11.1...
  • Page 22 The float is faulty. float bulb Low float bulb Troubleshooting Replace the float. For details, see NetCol5000-C030 In-row Chilled Water Smart Cooling Product User Manual (Simple Configuration). Huawei Technologies Co., Ltd. Huawei Industrial Base, Bantian, Longgang Shenzhen 518129 People's Republic of China www.huawei.com...

Table of Contents