Honeywell UVL-COIL-60D Manual

Uvl-coil ultraviolet lamp kits for ahu coils

Quick Links

UVL-COIL Ultraviolet Lamp Kits
for AHU Coils
APPLICATION
The system is designed for installation into commercial air
handling units for the purpose of surface disinfection
using ultraviolet germicidal irradiation. For maximum
installation flexibility and cost-effectiveness, the UV
lamps are mounted onto a framework of standard ½ inch
EMT tubing (not included). The remotely mounted weather
resistant power supply can withstand the wet environment
found inside of air handlers or the exposed conditions of
outdoor packaged air conditioning systems. The number
and placement of lamps is determined by the coil
dimensions.
FEATURES
• UV-C light irradiates coil & air handler interior, killing
mold, bacteria and viruses
• Scalable design allows wide variety of multi-lamp
configurations
• High quality water-resistant lamps
• Mounts using off-the-shelf ½ inch EMT conduit
tubing
• Includes 10 foot cable & all mounting hardware
except ½ inch EMT conduit
• Saves energy by keeping components cleaner
APPLICATION ...............................................................................
FEATURES .....................................................................................
SPECIFICATIONS ........................................................................
PLANNING THE INSTALLATION ..........................................
ORDERING INFORMATION ....................................................
INSTALLATION ............................................................................
WIRING ............................................................................................
MAINTENANCE ...........................................................................
TROUBLESHOOTING ................................................................
PRODUCT DATA
Contents
1
1
2
3
2
5
6
6
7
31-00402-02
loading

Summary of Contents for Honeywell UVL-COIL-60D

  • Page 1 UVL-COIL Ultraviolet Lamp Kits for AHU Coils PRODUCT DATA FEATURES • UV-C light irradiates coil & air handler interior, killing mold, bacteria and viruses • Scalable design allows wide variety of multi-lamp configurations • High quality water-resistant lamps • Mounts using off-the-shelf ½ inch EMT conduit tubing •...
  • Page 2 RTU / AHU 32" Double Bulb (MFG# TUVCPS-H32D) (MFR# TUVCL-232HO) UVL-60-LAMP UVL-COIL-60S RTU / AHU 60" Single Bulb (MFG# TUVCPS-HS) (MFR# TUVCL-260HO) UVL-60-LAMP (2) UVL-COIL-60D RTU / AHU 60" Double Bulb (MFG# TUVCPS-H46-60D) (MFR# TUVCL-260HO) *Power supply not available for purchase outside of kit. 31-00402—02...
  • Page 3 Table 2. Sizing Based on Coil Dimensions. Coil Width (inches) UVL-COIL-32S UVL-COIL-32S UVL-COIL-32S UVL-COIL-32S UVL-COIL-32D UVL-COIL-60S UVL-COIL-32S UVL-COIL-32S UVL-COIL-32S UVL-COIL-32D UVL-COIL-60S UVL-COIL-60S UVL-COIL-32S UVL-COIL-32S UVL-COIL-32S UVL-COIL-32D UVL-COIL-60S UVL-COIL-60D UVL-COIL-32D UVL-COIL-32D UVL-COIL-32D UVL-COIL-32D UVL-COIL-60D UVL-COIL-60D UVL-COIL-32D UVL-COIL-32D UVL-COIL-32D UVL-COIL-32D UVL-COIL-60D UVL-COIL-60D UVL-COIL-32D UVL-COIL-32D UVL-COIL-32D UVL-COIL-32D UVL-COIL-60D UVL-COIL-60D Table 3.
  • Page 4 UVL-COIL ULTRAVIOLET LAMP KITS FOR AHU COILS Coil 12” Lamp to Coil 36” 36” Lamp to Multiple lamps with Optional Vertical Support to prevent sagging Lamp Fig. 4. Vertical Support Configuration. UV Lamp Configuration Guidelines • Maximum germicidal effectiveness is within an 18 inch radius from UV lamp center axis.
  • Page 5 UVL-COIL ULTRAVIOLET LAMP KITS FOR AHU COILS INSTALLATION tubing length. Measure the distance from floor to ceiling then measure and cut tubing 1.75 inches less than that length. Use ½ inch pipe coupling to extend When Installing This Product… the vertical support to the floor and ceiling for a snug fit.
  • Page 6 Fig. 11. Align Pins and Lamp Key. MAINTENANCE Fig. 9. Sight Glass Installation. Honeywell UVC lights are made of Hard Quartz. Unlike Soft WIRING Quartz, these lamps do NOT need to be wiped of grease or other contaminants, and are NOT affected by humidity.
  • Page 7 UVL-COIL ULTRAVIOLET LAMP KITS FOR AHU COILS TROUBLESHOOTING Table 4. Troubleshooting. Problem Solution UV Lamp(s) Not Lighting 1. Check that power is applied. 2. Check that the unit is turned ON. 3. Ensure the remote lamp cables are properly connected. 4.
  • Page 8 UVL-COIL ULTRAVIOLET LAMP KITS FOR AHU COILS Honeywell Building Technologies In the U.S.: Honeywell 715 Peachtree Street NE Atlanta, GA 30308 ® U.S. Registered Trademark customer.honeywell.com ©2020 Honeywell International Inc. 31-00402—02 M.S. Rev. 09-20 buildingcontrols.honeywell.com Printed in United States...

This manual is also suitable for:

Uvl-coil-32sUvl-coil-32dUvl-coil-60s