Generator protection
Hide thumbs Also See for Relion 670 Series:
®
Relion
670 SERIES
Generator protection REG670
Version 2.2
Product guide
Table of Contents
loading

Summary of Contents for ABB Relion 670 Series

  • Page 1 ® Relion 670 SERIES Generator protection REG670 Version 2.2 Product guide...
  • Page 2: Table Of Contents

    The information in this document is subject to change without notice and should not be construed as a commitment by Hitachi Power Grids. Hitachi Power Grids assumes no responsibility for any errors that may appear in this document. Drawings and diagrams are not binding. ABB is a registered trademark of ABB Asea Brown Boveri Ltd.
  • Page 3: Document Revision History

    Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Issued: September 2020 Revision: M 1. Document revision history GUID-34B323E4-1319-4D42-80CE-29B0F2D36E2C v4 Table 1. Document revision history Document Date Product revision History revision 2017-07 2.2.0 First release for product version 2.2 2017-10 2.2.1 Ethernet ports with RJ45 connector added.
  • Page 4: Application

    Generator protection REG670 1MRK 502 074-BEN M Version 2.2 The wide application flexibility makes this product an excellent choice for both new installations and for 2. Application refurbishment in existing power plants. SEMOD155704-4 v7 The REG670 is used for protection, control and monitoring of generators and generator-transformer Forcing of binary inputs and outputs is a convenient way blocks from relatively small units up to the largest...
  • Page 5 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Description of configuration A20 SEMOD175637-4 v5 REG670 A20 – Generator differential + backup protection 12AI (7I + 5U) GEN_QA1 2(U0>) 2(U0>) Usqi Usqi GEN_TRM_VT V MMXU V MMXU V MSQI V MSQI ROV2 PTOV ROV2 PTOV f>...
  • Page 6 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Description of configuration B30 SEMOD175637-11 v6 REG670 B30 – Generator differential + backup protection 24AI (9I+3U, 9I+3U) HV_QA1 HV_CT Control Control Control Control Control Control 50BF 3I>BF 50BF 3I>BF 51_67 4(3I>) 51_67 4(3I>) Isqi Isqi...
  • Page 7 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Description of configuration C30 SEMOD175637-18 v6 REG670 C30 – Generator and block transformer protection 24AI (9I+3U, 6I+6U) HV_QA1 HV_VT   Usqi Usqi 2(3U>) 2(3U>) U>/I< U>/I< 51_67 4(3I>) 51_67 4(3I>) OV2 PTOV OV2 PTOV FUF SPVC...
  • Page 8: Available Functions

    Generator protection REG670 1MRK 502 074-BEN M Version 2.2 3. Available functions GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v1 The following tables list all the functions available in the IED. Those functions that are not exposed to the user or do not need to be configured are not described in this manual.
  • Page 9 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 IEC 61850 or ANSI Function description Generator function name REG670 (Customized) Differential protection T2WPDIF Transformer differential protection, two winding 1-A31 1-A33 T3WPDIF Transformer differential protection, three winding 1-A33 HZPDIF High impedance differential protection, single 3-A02 phase GENPDIF...
  • Page 10 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Back-up protection functions GUID-A8D0852F-807F-4442-8730-E44808E194F0 v16 IEC 61850 or ANSI Function description Generator function name REG670 (Customized) Current protection PHPIOC Instantaneous phase overcurrent protection OC4PTOC Directional phase overcurrent protection, four 51_67 steps EFPIOC Instantaneous residual overcurrent protection EF4PTOC...
  • Page 11 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 IEC 61850 or ANSI Function description Generator function name REG670 (Customized) Frequency protection SAPTUF Underfrequency protection SAPTOF Overfrequency protection SAPFRC Rate-of-change of frequency protection FTAQFVR Frequency time accumulation protection 0-12 12-E03 12-E03 12-E03 Multipurpose protection...
  • Page 12 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Control and monitoring functions GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v20 IEC 61850 or ANSI Function description Generator function name REG670 (Customized) Control SESRSYN Synchrocheck, energizing check and synchronizing APC30 Control functionality for up to 6 bays, 1-H39 1-H39 1-H39...
  • Page 13 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 IEC 61850 or ANSI Function description Generator function name REG670 (Customized) I103IEDCMD IED commands for IEC 60870-5-103 I103USRCMD Function commands user defined for IEC 60870-5-103 Secondary system supervision CCSSPVC Current circuit supervision FUFSPVC Fuse failure supervision VDSPVC...
  • Page 14 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 IEC 61850 or ANSI Function description Generator function name REG670 (Customized) AND, GATE, INV, LLD, Extension logic package (see Table 6) OR, PULSETIMER, RSMEMORY, SLGAPC, SRMEMORY, TIMERSET, VSGAPC, FXDSIGN Fixed signal function block B16I Boolean to integer conversion, 16 bit...
  • Page 15 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 IEC 61850 or ANSI Function description Generator function name REG670 (Customized) Monitoring CVMMXN Power system measurement CMMXU Current measurement VMMXU Voltage measurement phase-phase CMSQI Current sequence measurement VMSQI Voltage sequence measurement VNMMXU Voltage measurement phase-earth EVENT...
  • Page 16 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 IEC 61850 or ANSI Function description Generator function name REG670 (Customized) I103FLTPROT Function status fault protection for IEC 60870-5-103 I103IED IED status for IEC 60870-5-103 I103SUPERV Supervison status for IEC 60870-5-103 I103USRDEF Status for user defined signals for IEC 60870-5-103...
  • Page 17 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 4. Number of function instances in APC30 Function name Function description Total number of instances SCILO Interlocking BB_ES A1A2_BS A1A2_DC ABC_BC BH_CONN BH_LINE_A BH_LINE_B DB_BUS_A DB_BUS_B DB_LINE ABC_LINE AB_TRAFO SCSWI Switch controller SXSWI Circuit switch...
  • Page 18 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 6. Total number of instances for extended logic package Extended configurable logic block Total number of instances GATE PULSETIMER RSMEMORY SLGAPC SRMEMORY TIMERSET VSGAPC Hitachi Power Grids © Copyright 2017 Hitachi Power Grids. All rights reserved...
  • Page 19 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Communication GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v18 IEC 61850 or ANSI Function description Generator function name REG670 (Customized) Station communication LONSPA, SPA SPA communication protocol LON communication protocol HORZCOMM Network variables via LON PROTOCOL Operation selection between SPA and IEC60870-5-103 for SLM RS485PROT Operation selection for RS485...
  • Page 20 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 IEC 61850 or ANSI Function description Generator function name REG670 (Customized) LD0LLN0 IEC 61850 LD0 LLN0 SYSLLN0 IEC 61850 SYS LLN0 LPHD Physical device information PCMACCS IED configuration protocol SECALARM Component for mapping security events on protocols such as DNP3 and IEC103 FSTACCSNA Field service tool access via SPA protocol over...
  • Page 21 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 IEC 61850 or ANSI Function description Generator function name REG670 (Customized) BinSignTrans1_1 Binary signal transfer, transmit 3/3/6 3/3/6 3/3/6 3/3/6 BinSignTrans1_2 BinSignTransm2 BSR2M_305 Binary signal transfer, 2Mbit receive BSR2M_312 BSR2M_322 BSR2M_306 BSR2M_313 BSR2M_323 BST2M_305...
  • Page 22 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 7. Number of function instances in Synchrophasor report, 16 phasors Function name Function description Total number of instances PMUCONF Configuration parameters for IEC/IEEE 60255-118 (C37.118) 2011 and IEEE1344 protocol PMUREPORT Protocol reporting via IEEE 1344 and IEC/IEEE 60255-118 (C37.118) PHASORREPORT1 Protocol reporting of phasor data via IEEE 1344 and IEC/IEEE 60255-118...
  • Page 23 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Basic IED functions GUID-C8F0E5D2-E305-4184-9627-F6B5864216CA v14 Table 8. Basic IED functions IEC 61850 or function Description name INTERRSIG Self supervision with internal event list SELFSUPEVLST TIMESYNCHGEN Time synchronization module BININPUT, SYNCHCAN, Time synchronization SYNCHGPS, SYNCHCMPPS, SYNCHLON,...
  • Page 24: Differential Protection

    Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 8. Basic IED functions, continued IEC 61850 or function Description name ALTMS Time master supervision ALTIM Time management CAMCONFIG Central account management configuration CAMSTATUS Central account management status TOOLINF Tools information COMSTATUS Protocol diagnostic Table 9.
  • Page 25 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 The function can be provided with up to six three-phase transformers and auto-transformers with or without sets of current inputs if enough HW is available. All load tap changer as well as shunt reactors and local current inputs are provided with percentage bias feeders within the station.
  • Page 26: Impedance Protection

    Generator protection REG670 1MRK 502 074-BEN M Version 2.2 comparison criterion. This gives excellent sensitivity and Each measurement zone is designed with the flexibility stability during through faults. to operate in either quadrilateral or mho characteristic REFPDIF can also protect autotransformers. Five mode.
  • Page 27 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 directional decision under difficult operating conditions, with current transformers. The protection function including close-in three-phase faults, simultaneous performs a simple summation of the currents of the two faults and faults with only zero-sequence in-feed. channels I3P1 and I3P2.
  • Page 28: Wide Area Measurement System

    Generator protection REG670 1MRK 502 074-BEN M Version 2.2 To implement the above concept, a separate injection box is required. The injection box generates a square 6. Wide area measurement system wave voltage signal which for example can be fed into the secondary winding of the generator neutral point Synchrophasor report, 16 phasors voltage transformer or grounding transformer.
  • Page 29: Current Protection

    Generator protection REG670 1MRK 502 074-BEN M Version 2.2 (C37.118) Phasor Measurement Data Streaming Protocol All IEC and ANSI time-delayed characteristics are Configuration. available together with an optional user-defined characteristic. Multiple PMU functionality can be configured in the IED, which can stream out same or different data at different EF4PTOC can be set to be directional or non-directional reporting rates or different performance (service) independently for each step.
  • Page 30 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 1. By external start signals which is internally latched Sensitive directional residual overcurrent and power 2. Follow external start signal only protection SDEPSDE 3. Follow external start signal and the selected SEMOD171438-5 v6 In isolated networks or in networks with high impedance FunctionMode...
  • Page 31 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 By using optional metering class CT inputs accuracy of negative sequence currents down to the continuous 0,5% can be achieved for steam turbine applications. capability of a generator. Voltage-restrained time overcurrent protection In order to match the heating characteristics of the VRPVOC generator a reset time parameter can be set.
  • Page 32: Voltage Protection

    Generator protection REG670 1MRK 502 074-BEN M Version 2.2 If internal generator components exceed its design The function is suitable to be used in distribution and in temperature limit, damage can be the result. Damage to meshed HV sub-transmission networks using high- generator insulation can range from minor loss of life to impedance grounding.
  • Page 33 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 laminated components that are not designed to carry phase-to-earth fault occurs the neutral point voltage will flux. This will cause eddy currents to flow. These eddy increase and there will be a current flow through the currents can cause excessive heating and severe neutral point resistor.
  • Page 34: Frequency Protection

    Generator protection REG670 1MRK 502 074-BEN M Version 2.2 CB 1 may not exist CB 1 may not exist stator winding stator winding x E3 x E3 (1- x) E3 (1- x) E3 CB 1 CB 1 CB 2 CB 2 Transformer 1 - x 1 - x...
  • Page 35: Multipurpose Protection

    Generator protection REG670 1MRK 502 074-BEN M Version 2.2 counters. FTAQFVR for generator protection provides just a few of possible protection arrangements with the START output for a particular settable frequency these functions. limit, when the system frequency falls in that settable Rotor earth fault protection using CVGAPC frequency band limit and positive sequence voltage SEMOD151286-4 v8...
  • Page 36: Control

    Generator protection REG670 1MRK 502 074-BEN M Version 2.2 such as differential, earth-fault current and negative- unintentional operations can be prevented by fuse sequence current functions. failure supervision (VDSPVC). Current circuit supervision (CCSSPVC) compares the VDSPVC is designed to detect fuse failures or faults in residual current from a three phase set of current voltage measurement circuit, based on phase wise transformer cores with the neutral point current on a...
  • Page 37 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 at least one side dead to ensure that closing can be AddCause telling if the command was successful or if done safely. something went wrong. SESRSYN function includes a built-in voltage selection Control operation can be performed from the local HMI scheme for double bus and 1½...
  • Page 38 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 IEDs in a safe way and to prevent double operation in a Logic rotating switch for function selection and bay, switchyard part, or complete substation. LHMI presentation SLGAPC SEMOD114908-4 v11 Reservation input RESIN The logic rotating switch for function selection and M16501-3 v6 LHMI presentation (SLGAPC) (or the selector switch...
  • Page 39: Logic

    Generator protection REG670 1MRK 502 074-BEN M Version 2.2 The command function block has outputs that can be Basic configurable logic blocks used, for example, to control high voltage apparatuses M11396-4 v19 The basic configurable logic blocks do not propagate or for other user defined functionality.
  • Page 40 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 outputs. One of the outputs is inverted. The output interruption, or be reset. The function also propagates signal OUT is 1 if the input signals are different and 0 the time stamp and the quality of the input signal. if they are the same.
  • Page 41: Monitoring

    Generator protection REG670 1MRK 502 074-BEN M Version 2.2 • Retaining of the integration value. • positive, negative and zero sequence currents and • Possibilities for blocking and reset. voltages • Reporting of the integrated time. • mA, input currents •...
  • Page 42 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 be uploaded to PCM600 for further analysis using the The trip value recorder information is an integrated part disturbance handling tool. of the disturbance record (Comtrade file). Event list DRPRDRE Disturbance recorder DRPRDRE M12412-6 v9 M12156-3 v13 Continuous event-logging is useful for monitoring the...
  • Page 43 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 voltage sequence measurement functions (CMSQI and Overflow indication is included for each up-counter. VMSQI) and IEC 61850 generic communication I/O Running hour-meter TEILGAPC functions (MVGAPC) are provided with measurement GUID-464FB24F-B367-446C-963A-A14841943B87 v2 The Running hour-meter (TEILGAPC) function is a supervision functionality.
  • Page 44: Metering

    Generator protection REG670 1MRK 502 074-BEN M Version 2.2 between measured value and calculated value of the top system. It calculates the total harmonic distortion (THD) oil temperature. with respect to the fundamental signal amplitude which indicates the voltage signal quality factor. Additionally, the function calculates loss of life in form of days and years.
  • Page 45: Human Machine Interface

    Generator protection REG670 1MRK 502 074-BEN M Version 2.2 EnaAcc setting and it can be reset to and STOPACC) and initial values with RSTACC input. 18. Basic IED functions The maximum demand for active and reactive powers Time synchronization are calculated for the set time interval tEnergy and M11344-3 v11 The time synchronization function is used to select a...
  • Page 46: Station Communication

    Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Access points diagnostics GUID-20F64A6D-AA8C-47D7-AA7D-4810996B2FF2 v2 20. Station communication The access point diagnostics function blocks (RCHLCCH, SCHLCCH and FRONTSTATUS) supervise communication. SCHLCCH is used for communication Communication protocols over the rear Ethernet ports, RCHLCCH is used for M14815-3 v14 Each IED is provided with several communication redundant communications over the rear Ethernet ports...
  • Page 47 SPA communication protocol Supervison status for IEC 60870-5-103 I103SUPERV SEMOD120134-5 v1 A single glass or plastic port is provided for the ABB SPA I103SUPERV is a function block with defined functions protocol. This allows extensions of simple substation for supervision indications in monitor direction. This automation systems but the main use is for Substation FunctionType parameter;...
  • Page 48: Remote Communication

    Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Multiple command and transmit Function commands for IEC 60870-5-103 I103CMD M14791-3 v3 I103CMD is a command function block in control When IEDs are used in Substation Automation systems direction with pre-defined output signals. The signals with LON, SPA or IEC 60870-5-103 communication are in steady state, not pulsed, and stored in the IED in protocols, the Event and Multiple Command function...
  • Page 49: Hardware Description

    Generator protection REG670 1MRK 502 074-BEN M Version 2.2 signaling, alarming) between the generator and HV Binary input/output module IOM M6939-3 v6 station in power plants. The binary input/output module is used when only a few input and output channels are needed. The ten standard Galvanic X.21 line data communication module X.21- output channels are used for trip output or any signaling LDCM...
  • Page 50 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GPS time synchronization module GTM Layout and dimensions M14851-3 v5 This module includes a GPS receiver used for time IP14539-1 v1 Dimensions synchronization. The GTM has one SMA contact for IP14826-1 v1 M15243-4 v7 connection to an antenna.
  • Page 51 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 M15243-12 v11 IEC06000182-2-en.vsd IEC06000182 V2 EN-US Figure 12. A 1/2 x 19” size IED side-by-side with RHGS6. Table 10. Case dimensions Case size (mm)/ (inches) 6U, 1/2 x 19” 265.9/ 223.7/ 247.5/ 255.0/ 205.8/...
  • Page 52 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 The REX061 coupling capacitor unit grounding point and grounding brush of the rotor shaft should be properly interconnected. Shunt resistor unit REX062 GUID-90D6AF74-D9AC-49B8-B2CA-8A94E58ADEA5 v2 REX062 is required since the injection is done via a Signal Injection Transformer.
  • Page 53: Connection Diagrams

    Connection diagram, 670 series 2.2 1MRK002801-AG certificate issued by DNV GL Connection diagrams for Configured products IEC 61850 Ed1 level B1 1KHL050130 certificate issued by ABB Power Connection diagram, REG670 2.2, A20X00 Grids Switzerland Ltd, 1MRK002807-GA System Verification and Validation Center, SVC Baden Connection diagram, REG670 2.2, B30X00...
  • Page 54: Technical Data

    Generator protection REG670 1MRK 502 074-BEN M Version 2.2 25. Technical data General M10993-1 v4 IP11376-1 v3 Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified requirements Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to...
  • Page 55 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Energizing quantities, rated values and limits Analog inputs M16988-1 v11 IP15842-1 v1 Table 11. TRM - Energizing quantities, rated values and limits for protection transformer Description Value Frequency Rated frequency f 50/60 Hz Operating range ±...
  • Page 56 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 12. TRM - Energizing quantities, rated values and limits for measuring transformer Description Value Frequency Rated frequency f 50/60 Hz Operating range ± 10% Current inputs Rated current I Operating range (0-1.8) ×...
  • Page 57 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Binary inputs and outputs M12576-1 v13 IP15844-1 v1 Table 15. BIM - Binary input module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20% 110/125 V RL ±20%...
  • Page 58 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 17. IOM - Binary input/output module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20% 110/125 V RL ±20% 220/250 V RL ±20% Power consumption 24/30 V, 50 mA...
  • Page 59 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 M12318-1 v11 Table 18. IOM - Binary input/output module contact data (reference standard: IEC 61810-1) Function or quantity Trip and signal relays Fast signal relays (parallel reed relay) Binary outputs Max system voltage 250 V AC/DC 250 V DC Min load voltage...
  • Page 60 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 M12584-1 v11 Table 19. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-1) Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay) Binary outputs IOM: 10 IOM: 2...
  • Page 61 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 SEMOD175395-2 v11 Table 20. SOM - Static Output Module data (reference standard: IEC 61810-1): Heavy duty static binary outputs Function of quantity Static binary output trip Max system voltage 250 V DC Number of outputs Impedance open state High impedance...
  • Page 62 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 21. SOM - Static Output module data (reference standard: IEC 61810-1): Electromechanical relay outputs Function of quantity Trip and signal relays Max system voltage 250 V AC/DC Min load voltage 24 V DC Number of outputs Test voltage across open contact, 1 min...
  • Page 63 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 M12441-1 v11 Table 22. BOM - Binary output module contact data (reference standard: IEC 61810-1) Function or quantity Trip and Signal relays Binary outputs Max system voltage 250 V AC/DC Min load voltage 24V DC Test voltage across open contact, 1 min 1000 V rms...
  • Page 64 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 24. Auxiliary DC supply voltage influence on functionality during operation Dependence on Reference value Within nominal Influence range Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01%/% Operative range Full wave rectified Auxiliary voltage dependence,...
  • Page 65 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Type tests according to standards M16706-1 v15 IP15778-1 v1 Table 26. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-26 100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Level 3 Ring wave immunity test, 100 kHz...
  • Page 66 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 28. Environmental conditions Description Value Operating temperature range -25°C to +55°C (continuous) Short-time service temperature range -40°C to +70°C (<16h) Note: Degradation in MTBF and HMI performance outside the temperature range of -25°C to +55°C Relative humidity <93%, non-condensing Atmospheric pressure...
  • Page 67 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Injection equipment GUID-87197CB5-8590-4872-A5B6-8C6D2A815C9E v4 Table 32. Electromagnetic compatibility tests Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-26 100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Class III Electrostatic discharge...
  • Page 68 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 34. Insulation tests, REX061 Test Type test values Reference standard Dielectric test 7.48 kV DC, 1min IEEE 421.3 (connections to rotor) 2.8 kV DC, 1 min IEC 60255-27 Impulse voltage test 12.0 kV, 1.2/50 µs, 0.5 J IEC 60664-1 (connections to rotor)
  • Page 69 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-9D1F44FC-896B-4907-9609-C32781CA1798 v3 Table 37. Auxiliary DC supply voltage influence Test Type test values Influence Auxiliary voltage dependence, operate value ±20% of EL 0.01%/% Ripple in DC auxiliary voltage, operate value 15% of EL 0.01%/% GUID-A1BED9A8-2791-4ACF-8400-B20206F057A8 v3 Table 38.
  • Page 70 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Differential protection SEMOD175004-2 v10 Table 40. Generator differential protection GENPDIF Function Range or value Accuracy IBase Unrestrained differential current limit (1-50)p.u. of ±1.0% of set value Reset ratio > 95% Minimum pickup (0.05–1.00)p.u.
  • Page 71 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 M13046-1 v14 Table 41. Transformer differential protection T2WPDIF/T3WPDIF Function Range or value Accuracy Operating characteristic Adaptable ±1.0% of Ir at I ≤ Ir ±1.0% of I at I > Ir Reset ratio >...
  • Page 72 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 M13062-1 v22 Table 42. Restricted earth-fault protection, low impedance REFPDIF Function Range or value Accuracy Operating characteristic Adaptable ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >...
  • Page 73 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Impedance protection SEMOD173242-2 v14 Table 44. Full-scheme distance protection, Mho characteristic ZMHPDIS Function Range or value Accuracy Number of zones, Ph-E Max 4 with selectable direction Minimum operate current (10–30)% of IBase Positive sequence impedance, ±2.0% static accuracy (0.005–3000.000) W/phase...
  • Page 74 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-6C2EF52A-8166-4A23-9861-38931682AA7D v8 Table 45. High speed distance protection ZMFPDIS, ZMFCPDIS Function Range or value Accuracy Number of zones 5 selectable directions, 2 fixed directions Minimum operate current, Ph- (5-6000)% of IBase ±1.0% of I Ph and Ph-E Positive sequence reactance...
  • Page 75 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 SEMOD175136-2 v9 Table 47. Out-of-step protection OOSPPAM Function Range or value Accuracy Impedance reach (0.00 - 1000.00)% of Zbase ±2.0% of U /(√3 ⋅ I Rotor start angle (90.0 - 130.0) degrees ±5.0 degrees Rotor trip angle (15.0 - 90.0) degrees...
  • Page 76 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-956187E5-A466-47BF-B671-F46548A5DF2E v4 Table 50. STTIPHIZ technical data Function Range or value Accuracy Fault resistance sensitivity Can be reached at steady state 50 kΩ operating condition of the machine Typically 10 kΩ Injection frequency (50.000 - 250.000) Hz ±0.1 Hz...
  • Page 77 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Wide area measurement system GUID-F0BAEBD8-E361-4D50-9737-7DF8B043D66A v5 Table 52. Protocol reporting via IEEE 1344 and IEC/IEEE 60255-118 (C37.118) PMUREPORT Influencing quantity Range Accuracy Signal frequency ± 0.1 x f ≤ 1.0% TVE Signal magnitude: Voltage phasor (0.1–1.2) x U...
  • Page 78 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Current protection M12336-1 v14 Table 53. Instantaneous phase overcurrent protection PHPIOC Function Range or value Accuracy Operate current (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >...
  • Page 79 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 M12342-1 v22 Table 54. Directional phase overcurrent protection, four steps OC4PTOC Function Range or value Accuracy lBase Operate current, step 1-4 (5-2500)% of ±1.0% of I at I ≤ I ±1.0% of I at I > I lBase Reset ratio >...
  • Page 80 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 M12340-2 v9 Table 55. Instantaneous residual overcurrent protection EFPIOC Function Range or value Accuracy Operate current (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >...
  • Page 81 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 M15223-1 v18 Table 56. Directional residual overcurrent protection, four steps EF4PTOC Function Range or value Accuracy Operate current, step 1-4 (1-2500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >...
  • Page 82 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v6 Table 57. Four step directional negative phase sequence overcurrent protection NS4PTOC Function Range or value Accuracy lBase Operate current, step 1 - 4 (1-2500)% of ±1.0% of I at I £ I ±1.0% of I at I >...
  • Page 83 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 SEMOD173350-2 v16 Table 58. Sensitive directional residual overcurrent and power protection SDEPSDE Function Range or value Accuracy (0.25-200.00)% of IBase Operate level for 3I ·cosj directional ±1.0% of I at I £ I residual overcurrent ±1.0% of I at I >...
  • Page 84 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 M13266-2 v9 Table 59. Thermal overload protection, two time constants TRPTTR Function Range or value Accuracy IBase Base current 1 and 2 (30–250)% of ±1.0% of I Operate time: Time constant τ = (0.10– ±5.0% or ±200 ms whichever is greater 500.00) minutes ∑...
  • Page 85 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 M13279-1 v10 Table 61. Pole discordance protection CCPDSC Function Range or value Accuracy IBase Operate current (0–100)% of ±1.0% of I Independent time delay between trip (0.000-60.000) s ±0.2% or ± 30 ms whichever is greater condition and trip signal SEMOD175152-2 v11 Table 62.
  • Page 86 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-E5718F80-556D-4852-A8F2-90E0F578D763 v10 Table 64. Negative sequence time overcurrent protection for machines NS2PTOC Function Range or value Accuracy IBase Operate current, step 1 - 2 (3-500)% of ±1.0% of I Reset ratio >95% Operate time, start at 0 to 2 x I Min.
  • Page 87 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-9B1C0C10-8AF9-4D9E-8076-B3E1C238D29A v8 Table 65. Accidental energizing protection for synchronous generator AEGPVOC Function Range or value Accuracy Operate value, overcurrent (5-900)% of IBase ±1.0% of I at I≤I ±1.0% of I at I>I Reset ratio, overcurrent >95% at (20–900)% of IBase Transient overreach, overcurrent...
  • Page 88 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-A1CB5B4F-768E-4B1B-937E-B91EC3EFA2CC v4 Table 67. Generator rotor overload protection GRPTTR Function Range or value Accuracy Overcurrent start level for overload (105.0–900.0)% of IBase ±1.0% of I at I ≤ I protection ±1.0% of I at I > I Reset ratio, overcurrent >95% —...
  • Page 89 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-7EA9731A-8D56-4689-9072-D72D9CDFD795 v8 Table 68. Voltage-restrained time overcurrent protection VRPVOC Function Range or value Accuracy Start overcurrent (2.0 - 5000.0)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio, overcurrent >...
  • Page 90 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-BCCA5F2D-9FF7-4188-9B5D-DA05E8E80CC0 v1 Table 69. Average Power Transient Earth Fault Protection APPTEF Function Range or value Accuracy Minimum operate level for residual (5-80)% of UBase ±0.5% of Ur overvoltage 3Uo> start condition "UN>" Reset ratio for residual overvoltage 3Uo>...
  • Page 91 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Voltage protection M13290-1 v15 Table 70. Two step undervoltage protection UV2PTUV Function Range or value Accuracy UBase Operate voltage, low and high step (1.0–100.0)% of ±0.5% of U UBase Absolute hysteresis (0.0–50.0)% of ±0.5% of U UBase...
  • Page 92 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 M13304-1 v15 Table 71. Two step overvoltage protection OV2PTOV Function Range or value Accuracy UBase Operate voltage, step 1 and 2 (1.0-200.0)% of ±0.5% of U at U ≤ U ±0.5% of U at U > U UBase Absolute hysteresis (0.0–50.0)% of...
  • Page 93 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 M13317-2 v15 Table 72. Residual overvoltage protection, two steps ROV2PTOV Function Range or value Accuracy UBase Operate voltage, step 1 - step 2 (1.0-200.0)% of ± 0.5% of U at U ≤ U ±...
  • Page 94 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 SEMOD166919-2 v7 Table 74. Voltage differential protection VDCPTOV Function Range or value Accuracy UBase Voltage difference for alarm and trip (2.0–100.0) % of ±0.5% of U Under voltage level (1.0–100.0) % of UBase ±0.5% of U Independent time delay for voltage...
  • Page 95 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Frequency protection M13360-1 v16 Table 76. Underfrequency protection SAPTUF Function Range or Value Accuracy Operate value, start function, at (35.00 - 75.00) Hz ±2.0 mHz symmetrical three phase voltage, StartFrequency Reset hysteresis 10.0 mHz fixed ±2.0 mHz Start time measurement...
  • Page 96 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 M14964-1 v13 Table 77. Underfrequency protection SAPTOF Function Range or Value Accuracy Operate value, start function, (35.00 - 90.00) Hz ±2.0 mHz at symmetrical three phase voltage, StartFrequency 10.0 mHz fixed ±2.0 mHz Reset hysteresis Start time measurement with...
  • Page 97 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-E8D0EE7C-D7B8-46C3-9C0D-363FFC75DE93 v5 Table 79. Frequency accumulation protection FTAQFVR Function Range or value Accuracy Operate value, frequency high limit level at (35.00 – 90.00) Hz ±2.0 mHz symmetrical three phase voltage Operatevalue, frequency low limit level at (30.00 –...
  • Page 98 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Multipurpose protection M13095-2 v11 Table 80. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input phase1, phase2, phase3, PosSeq, - NegSeq, -3*ZeroSeq, MaxPh, MinPh, UnbalancePh, phase1- phase2, phase2-phase3, phase3- phase1, MaxPh-Ph, MinPh-Ph, UnbalancePh-Ph...
  • Page 99 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 80. General current and voltage protection CVGAPC, continued Function Range or value Accuracy Start undervoltage, step 1 - 2 (2.0 - 150.0)% of UBase ±0.5% of U at U ≤ U ±0.5% of U at U >...
  • Page 100 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 80. General current and voltage protection CVGAPC, continued Function Range or value Accuracy Impulse margin time 15 ms typically Undervoltage: Critical impulse time 10 ms typically at 1.2 x U to 0.8 x Impulse margin time 15 ms typically...
  • Page 101 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Secondary system supervision M12358-1 v10 Table 82. Current circuit supervision CCSSPVC Function Range or value Accuracy Operate current (10-200)% of IBase ±10.0% of I at I ≤ I ±10.0% of I at I > I Reset ratio, Operate current >90% Block current...
  • Page 102 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-E2EA8017-BB4B-48B0-BEDA-E71FEE353774 v5 Table 84. Fuse failure supervision VDSPVC Function Range or value Accuracy Operate value, block of main fuse failure (10.0-80.0)% of UBase ±0.5% of Ur Reset ratio <110% Operate time, block of main fuse failure at 1 x U Min.
  • Page 103 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Control M12359-1 v15 Table 87. Synchronizing, synchrocheck and energizing check SESRSYN Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase ±0.5% of U at U ≤...
  • Page 104 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 SEMOD175215-2 v14 Table 88. Tap changer control TCMYLTC/TCLYLTC Function Range or value Accuracy Tap position for lowest and highest (1–63) voltage mA for lowest and highest voltage (0.000–25.000) mA tap position Type of code conversion BIN, BCD, GRAY, SINGLE, mA Time after position change before...
  • Page 105 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Logic M12380-1 v15 Table 89. Tripping logic common 3-phase output SMPPTRC Function Range or value Accuracy Program Trip action, 3 phase, 1ph/2ph, 1ph/2ph/3ph Minimum trip pulse (0.000-60.000) s ±0.2% or ±15 ms whichever is greater length , tTripMin tWaitForPHS...
  • Page 106 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v2 Table 95. Number of INDCALH instances Function Quantity with cycle time 3 ms 8 ms 100 ms INDCALH GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v3 Table 96. Number of AND instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms...
  • Page 107 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-BE6FD540-E96E-4F15-B2A2-12FFAE6C51DB v2 Table 102. Number of RSMEMORY instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms RSMEMORY GUID-7A0F4327-CA83-4FB0-AB28-7C5F17AE6354 v2 Table 103. Number of SRMEMORY instances Logic block Quantity with cycle time 3 ms 8 ms...
  • Page 108 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-77FEBE9B-0882-4E85-8B1A-7671807BFC02 v2 Table 109. Number of INVALIDQT instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms INVALIDQT GUID-F25B94C6-9CC9-48A0-A7A3-47627D2B56E2 v1 Table 110. Number of INVERTERQT instances Logic block Quantity with cycle time 3 ms 8 ms...
  • Page 109 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-1C381E02-6B9E-44DC-828F-8B3EA7EDAA54 v1 Table 116. Number of XORQT instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms XORQT GUID-19810098-1820-4765-8F0B-7D585FFC0C78 v8 Table 117. Number of instances in the extension logic package Logic block Quantity with cycle time 3 ms...
  • Page 110 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v2 Table 121. Number of ITBGAPC instances Function Quantity with cycle time 3 ms 8 ms 100 ms ITBGAPC GUID-44D82B7D-280F-4F11-B017-784E3047AD0F v3 Table 122. IntegratorTIGAPC Table 122. IntegratorTIGAPC , continued Function Cycle time Range of Accuracy...
  • Page 111 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 125. Number of TEIGAPC instances Function Quantity with cycle time 3 ms 8 ms 100 ms TEIGAPC GUID-CEA332FF-838D-42B7-AEFC-C1E87809825E v4 Table 126. Number of INTCOMP instances Function Quantity with cycle time 3 ms 8 ms 100 ms...
  • Page 112 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Monitoring M12386-1 v16 Table 128. Power system measurement CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) x f ±2.0 mHz Voltage (10 to 300) V ±0.3% of U at U ≤ 50 V ±0.2% of U at U >...
  • Page 113 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6 Table 131. Voltage measurement phase-earth VNMMXU Function Range or value Accuracy Voltage (5 to 175) V ±0.5% of U at U ≤ 50 V ±0.2% of U at U > 50 V Phase angle (5 to 175) V ±0.5 degrees at U ≤...
  • Page 114 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 M12760-1 v12 Table 135. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 200, first in - first out Time tagging resolution 1 ms See table...
  • Page 115 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v9 Table 137. Insulation supervision for liquid medium function SSIML Function Range or value Accuracy Oil alarm level 1.00-100.00 ±10.0% of set value or 0.2 whichever is greater Oil lockout level 1.00-100.00 ±10.0% of set value or 0.2 whichever is greater Temperature alarm level...
  • Page 116 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 M12700-1 v5 Table 140. Event list Function Value Buffer capacity Maximum number of events in the list 5000 Resolution 1 ms Accuracy Depending on time synchronizing M13765-1 v6 Table 141. Indications Function Value Buffer capacity...
  • Page 117 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v3 Relion® 670 series can store up to 10240 security events. Table 145. Event counter with limit supervision L4UFCNT Function Range or value Accuracy Counter value 0-65535 Hitachi Power Grids ©...
  • Page 118 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 145. Event counter with limit supervision L4UFCNT , continued Function Range or value Accuracy Max. count up speed 30 pulses/s (50% duty cycle) GUID-F5E124E3-0B85-41AC-9830-A2362FD289F2 v1 Table 146. Running hour-meter TEILGAPC Function Range or value Accuracy...
  • Page 119 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-2068BBA0-9026-48D0-9DEB-301BCB3C600C v2 Table 149. Voltage harmonic monitoring VHMMHAI (50/60 Hz) Function Range or value Accuracy Fundamental Harmonic Frequency (0.95 - 1.05) X f 2nd order to 5th order (0.1 - 0.5) X U ±...
  • Page 120 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Metering M13404-2 v5 Table 150. Pulse-counter logic PCFCNT Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of (1–3600) s counter value SEMOD153707-2 v5 Table 151. Function for energy calculation and demand handling ETPMMTR Function Range or value Accuracy...
  • Page 121 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Station communication M15031-1 v9 Table 152. Communication protocols Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 60870–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0 Communication speed for the IEDs...
  • Page 122 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 M12589-1 v5 Table 157. SLM – LON port Quantity Range or value Optical connector Glass fiber: type ST Plastic fiber: type HFBR snap-in Fiber, optical budget Glass fiber: 11 dB (1000m/3000 ft typically *) Plastic fiber: 7 dB (10m/35 ft typically *) Fiber diameter Glass fiber: 62.5/125 mm...
  • Page 123 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 161. SFP - Galvanic RJ45 Quantity Rated value Number of channels Up to 6 single or 3 redundant or a combination of single and redundant links for communication using any protocol Standard IEEE 802.3u 100BASE-TX Type of cable...
  • Page 124 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Remote communication M12756-1 v13 Table 163. Line data communication module Characteristic Range or value Type of LDCM Short range (SR) Medium range (MR) Long range (LR) Type of fiber Multi-mode fiber Single-mode fiber Single-mode fiber glass 62.5/125 µm...
  • Page 125 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Hardware M11778-1 v7 SEMOD53385-1 v1 Table 165. Case Material Steel sheet Front plate Stainless steel with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) M12327-1 v5 Table 166.
  • Page 126 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v3 Because of limitations of space, when ring lug terminal is ordered for Binary I/O connections, one blank slot is necessary between two adjacent I/O modules. Please refer to the ordering particulars for details.
  • Page 127 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Injection equipment hardware GUID-EDF13DA3-4658-4A20-8641-CD62F6C3BE0F v3 Table 173. Injection unit REX060 Specifications Values Case size 6U, 1/2 19”; 223.7 x 245 x 267 mm (W x D x H) Weight 8.0 kg Burden, binary inputs BI 220 V: burden 0.4 W BI 110 V: burden 0.2 W...
  • Page 128 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-E7B9192F-ABD5-4395-94F2-ED0B2F0DFEB7 v3 Table 175. Shunt resistor unit REX062 Specifications Values Case size 218 x 150 x 243 mm (W x D x H) Weight 4.5 kg Assembling 6 x 5 mm screws (3 at bottom and 3 at top) Rated stator injection voltage 240 V Rated stator voltage...
  • Page 129 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Basic IED functions M11963-1 v5 Table 176. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out M12331-1 v9 Table 177. Time synchronization, time tagging Function Value Time tagging accuracy of the synchrophasor data...
  • Page 130 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 SEMOD141136-2 v10 Table 181. IRIG-B Quantity Rated value Number of channels IRIG-B Number of optical channels Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp –...
  • Page 131 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Inverse characteristic M12388-1 v23 Table 182. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 999.00 ANSI/IEEE C37.112 , 1.5 x I ≤ I ≤ 20 x I ±2.0% or ±40 ms whichever is greater æ...
  • Page 132 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 183. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 999.00 IEC 60255-151, ±2.0% 1.5 x I ≤ I ≤ 20 x I or ±40 ms whichever is greater æ...
  • Page 133 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 184. RI and RD type inverse time characteristics Function Range or value Accuracy RI type inverse characteristic 0.05 ≤ k ≤ 999.00 IEC 60255-151, ±2.0% 1.5 x I ≤ I ≤ 20 x I or ±40 ms whichever is greater ×...
  • Page 134 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 186. IEC Inverse time characteristics for Sensitive directional residual overcurrent and power protection Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 2.00 IEC 60255-151, ±5.0% 1.5 x I ≤...
  • Page 135 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 GUID-2AE8C92E-5DA8-487F-927D-8E553EE29240 v2 Table 188. ANSI Inverse time characteristics for Voltage restrained time overcurrent protection Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 999.00 ANSI/IEEE C37.112 , ± 5.0% or ±40 ms whichever is greater æ...
  • Page 136 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 SEMOD116978-2 v10 Table 190. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
  • Page 137 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 191. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ ö...
  • Page 138 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 192. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps ±5.0% or ±45 ms whichever is greater of 0.01 æ...
  • Page 139: Ordering For Customized Ied

    Generator protection REG670 1MRK 502 074-BEN M Version 2.2 26. Ordering for customized IED GUID-0076B561-1FF1-4A89-AC04-DF53A413E2AF v12 Table 193. General guidelines Guidelines Carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
  • Page 140 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 197. Differential protection Position Table 198. Differential functions Function Function Ordering no Position Available Selected Notes and rules identification Transformer differential protection, two winding T2WPDIF 1MRK005904-FC Transformer differential protection, three winding T3WPDIF 1MRK005904-GB High impedance differential protection, single phase...
  • Page 141 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 202. Current functions Function Function Ordering no Position Available Selected Notes and rules identification Instantaneous phase overcurrent protection PHPIOC 1MRK005910-AD Directional phase overcurrent protection, four steps OC4PTOC 1MRK005910-BC Instantaneous residual overcurrent protection EFPIOC 1MRK005910-DD Directional residual overcurrent protection, four steps...
  • Page 142 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 209. Multipurpose functions Function Function Ordering no Position Available Selected Notes and rules identification General current and voltage protection CVGAPC 1MRK005915-AA Table 210. General calculation Position Table 211. General calculation functions Function Function Ordering no...
  • Page 143 Additional local HMI user dialogue language No additional HMI language HMI language, English US 1MRK002920-UB Selected Additional 2nd languages are continuously being added. Please get in touch with local ABB sales contact. Table 224. Casing selection Casing Ordering no Selection Notes and rules 1/2 x 19"...
  • Page 144 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 226. Power supply module selection Power supply module Ordering no Selection Notes and rules Compression terminals 1MRK002960-GA Ringlug terminals 1MRK002960-HA Power supply module 24-60 VDC 1MRK002239-AB Power supply module 90-250 VDC 1MRK002239-BB Selected Table 227.
  • Page 145 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 228. Analog system selection Analog system Ordering no Selection Notes and rules When more than one TRM is selected, the connector type on both TRMs must be the same (A compression or B ring lug). Slot position (front view/rear view) No Transformer input module included TRM 12I 1A, 50/60Hz, compression terminals...
  • Page 146 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 229. Maximum quantity of I/O modules, with compression terminals When ordering I/O modules, observe the maximum quantities according to the tables below. Note: Standard order of location for I/O modules is BIM-BOM-SOM-IOM-MIM from left to right as seen from the rear side of the IED, but can also be freely placed.
  • Page 147 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 231. Binary input/output module selection Binary input/ Ordering no Selection Notes and rules output modules Slot position (front view/rear view) 1/2 case with 1 █ █ 3/4 case with 1 █...
  • Page 148 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 231. Binary input/output module selection, continued Binary input/ Ordering no Selection Notes and rules output modules IOM 8 inputs, RL 1MRK000173-BE 110-125 VDC, 50mA, 10+2 output relays IOM 8 inputs, RL 1MRK000173-CE 220-250 VDC, 50mA, 10+2...
  • Page 149 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Table 232. Station communication, remote end serial communication and time synchronization selection Station communication, remote end Ordering no Selection Notes and rules serial communication and time synchronization Slot position (front view/rear view) Available slots in 1/2, 3/4 and 1/1 █...
  • Page 150: Ordering For Pre-Configured Ied

    Generator protection, Generator differential and back-up 1MRK004826-AG Generator protection, Generator differential and generator/transformer back-up 1MRK004826-BG Generator protection, Generator/transformer differential and back-up 1MRK004826-CG ACT configuration ABB standard configuration Selection for position #2 Hitachi Power Grids © Copyright 2017 Hitachi Power Grids. All rights reserved...
  • Page 151 No additional HMI language HMI language, English US 1MRK002920-UB Selection for position #4 Additional 2nd languages are continuously being added. Please get in touch with local ABB sales contact. Casing Ordering no Notes and rules 1/2 x 19" rack casing, 1 TRM 1MRK000151-VA 3/4 x 19"...
  • Page 152 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Mounting details with IP40 of protection from the front Ordering no Notes and rules No mounting kit included 19" rack mounting kit for 1/2 x 19" case or 2xRHGS6 or RHGS12 1MRK002420-BB 19"...
  • Page 153 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Analog system Ordering no Notes and rules When more than one TRM is selected, the connector type on both TRMs must be the same (A compression or B ring lug). Slot position (front view/rear view) No Transformer input module included TRM 9I 1A + 3U 110/220V, 50/60Hz, compression terminals 1MRK002247-BG...
  • Page 154 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Binary input/output modules Ordering no Notes and rules For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used. Note: 1BIM and 1 BOM required in slots P3 and P4. Slot position (front/rear view) 1/2 Case with 1 TRM...
  • Page 155 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 These black marks indicate the maximum number of modules per casing type and the slots that can be occupied. Only for A20 Only for B30/C30 Maximum 4 (BOM+SOM+MIM) boards. MIM not in A20, Maximum 1 MIM board in 1/2 case. SOM must not to be placed in the position nearest to NUM: 1/2 case slot P5, 3/4 case 1 TRM slot P10, 3/4 case 2 TRM slot P7, 1/1 case 2 TRM slot P13, 1/1 case, 1 TRM slot P16.
  • Page 156: Ordering For Accessories

    IEDs is described in 1MRK 512 001-BEN and 1MRK three winding transformers in single or multi-breaker 001024-CA. Please refer to the website: arrangement (ordering number RK926 315-BH). www.abb.com/protection-control for detailed Three winding transformer with internal neutral on information. current circuits (ordering number RK926 315-BX).
  • Page 157 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 External resistor unit SEMOD120228-4 v9 High impedance resistor unit with resistor and voltage dependent resistor 20-100V, Quantity : RK 795 101-MA Quantity : High impedance resistor unit with resistor and voltage dependent resistor 20-100V, RK 795 101-MB High impedance resistor unit with resistor and voltage dependent resistor Quantity :...
  • Page 158 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Injection equipment GUID-3447C871-562C-46B4-A36C-0B8B62D38E48 v7 Rule: If injection equipment is ordered, ROTIPHIZ or STTIPHIZSensitive rotor earth fault protection, injection based (option B31) or 100% stator earth fault protection, injection based (option B32) is required in the IED.
  • Page 159 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 Combiflex IP15161-1 v1 Key switch for settings SEMOD130356-4 v7 Key switch for lock-out of settings via LHMI Quantity: 1MRK 000 611-A Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used. SEMOD130267-5 v8 Mounting kit Ordering number...
  • Page 160 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 User documentation Specify the number of printed manuals requested Application manual Quantity: 1MRK 502 071-UEN ANSI Quantity: 1MRK 502 071-UUS Technical manual Quantity: 1MRK 502 072-UEN ANSI Quantity: 1MRK 502 072-UUS Commissioning manual Quantity: 1MRK 502 073-UEN...
  • Page 161 Generator protection REG670 1MRK 502 074-BEN M Version 2.2 ANSI Quantity: 1MRK 511 398-UUS Cyber security deployment guideline Quantity: 1MRK 511 399-UEN Application guide, Communication set-up Quantity: 1MRK 505 382-UEN Reference information M2175-3 v4 For our reference and statistics we would be pleased to be provided with the following application data: Country: End user: Station name:...
  • Page 163 ABB Power Grids Sweden AB Grid Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 10 738 00 00 Scan this QR code to visit our website https://www.abb.com/protection-control © Copyright 2017 Hitachi Power Grids. All rights reserved.