Honeywell CTS-V Series Installation Instructions

Solid and split core 0-5/10vdc output current sensors

Quick Links

Solid and Split Core 0-5/10Vdc
Output Current Sensors
CTS-V AND CTP-V SERIES
APPLICATION
The 0-5/10Vdc Output Solid and Split Core Current
Sensors are designed for use in any AC current
monitoring application in which you are looking to
monitor a particular piece of equipment.
SPECIFICATIONS
Monitored Current Type: AC Current
Maximum AC Voltage: 600 VAC
Isolation Voltage: 2200 VAC
Supply Voltage:
Induced from the Monitored Conductor (Insulated
Conductors only)
150-Amp Sensors: 0 to 10 VDC
Operating Temperature Range: 5 to 104ºF (-15 to
40ºC)
STANDARD ORDERING
Model #
Selectable Ranges Measurement
CTS-V-50
0 to 10/20/50A
CTS-V-150 0 to 50/100/150
CTP-V-50
0 to 10/20/50A
CTP-V-150 0 to 50/100/150
WARNING
This product is not intended to be used for
Life or Safety applications.
This product is not intended for use in any
hazardous or classified locations. The CTS-V
and CTP-V Series Current Sensors must be
used on Insulated Conductors Only!
Table 1. Standard Ordering.
Average
Average
Average
Average
20
INSTALLATION INSTRUCTIONS
Operating Humidity Range: 0 to 95%, non-con-
densing
Storage Temperature: 41 to 95°F (5 to 35°C)
RH Range: 40% to 85% RH, non-condensing
Wire Recommendations: 2 Conductor (Shielded
Cable)
Wire Size:
18 to 24 AWG (0.823 mm
Wires only
Terminal Block Torque Rating: 4.43 to 5.31 in-lbs.
(0.5 to 0.6 Nm)
Minimum Mounting Distance:
1" (2.6 cm) between current sensor & other magnetic
devices (Relays, Contactors, Transformers)
Agency Approvals:
UL/CUL US Listed (UL 508) Ind. Control Equipment
(File # E309723), CE, RoHS2, WEEE
AC Waveform
Pure Sinusoidal
Pure Sinusoidal
Pure Sinusoidal
Pure Sinusoidal
WARNING
Electrical shock hazard.
Disconnect and lock out all power sources
before installation as severe injury or death
may result from electrical shock due to
contact with high voltage wires.
2
to 0.205 mm) Copper
Solid-Core Split-Core
31-00144-02
Output
Signal
0 to 5 VDC
0 to 10 VDC
0 to 10 VDC
0 to 10 VDC
loading

Summary of Contents for Honeywell CTS-V Series

  • Page 1 Solid and Split Core 0-5/10Vdc Output Current Sensors CTS-V AND CTP-V SERIES INSTALLATION INSTRUCTIONS APPLICATION Operating Humidity Range: 0 to 95%, non-con- densing Storage Temperature: 41 to 95°F (5 to 35°C) The 0-5/10Vdc Output Solid and Split Core Current Sensors are designed for use in any AC current RH Range: 40% to 85% RH, non-condensing monitoring application in which you are looking to Wire Recommendations: 2 Conductor (Shielded...
  • Page 2 SOLID AND SPLIT CORE 0-5/10VDC OUTPUT CURRENT SENSORS INSTALLATION Make sure that all installations are in compliance with The current sensor may be mounted in any position all national and local electrical codes. Only qualified using the two #8 x ¾” Tek screws and the mounting individuals that are familiar with codes, standards, holes in the base, or snapped directly on to the 35mm and proper safety procedures for high-voltage...
  • Page 3 SOLID AND SPLIT CORE 0-5/10VDC OUTPUT CURRENT SENSORS NOTE: When using a shielded cable, be sure to con- sensitive and represent a linear 0 to 5 or 0 to 10 VDC nect only (1) end of the shield to ground at the output signal.
  • Page 4 By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’...

This manual is also suitable for:

Ctp-v seriesCts-v-50Cts-v-150Ctp-v-50Ctp-v-150