    AF-600FP BACnet Contents 1 Introduction Introduction 2 Safety Copyright, Limitation of Liability and Revision Rights 3 How to Install The BACnet Option System Specifications 4 How to Configure the System Configuring BACnet BIBBs Example of a simple setup of BACnet 5 How to Control the Drive Network Drive Control Inputs and -Outputs Drive Feedback to Network...
  • Page 3 AF-600FP BACnet...
  • Page 4: Introduction

    AF-600FP BACnet 1 Introduction 1.1 Introduction 1.1.1 About this Manual First time users can obtain the most essential information for quick installation and set-up in these chapters: Introduction How to Install How to Configure the System Application Example For more detailed information including the full range of set-up options and diagnosis tools please refer to the chapters: How to Control the Drive How to Access AF-600 FP Parameters Parameters...
  • Page 5 AF-600FP BACnet Background information Protocol name: BACnet Technology developer: ASHRAE Year introduced: 1995 Governing standards: ANSI/ASHRAE Standard 135-2004, ISO 16484-5 Openness: Open specification Physical characteristics Network topology: Physical media: Shielded twisted pair Max. Distance at low speed: 1200 meters Transport mechanism Communication methods: Master/slave Baud Rates Supported:...
  • Page 6 1.1.3 Assumptions This manual assumes you are using a GE BACnet Option Card in conjunction with a GE AF-600 FP seriesdrive. It is also assumed that your master is a BMS or PC equipped with a serial communication card supporting all the BACnet communication services required by your application, and that all requirements stipulated in the BACnet standard, as well as those pertaining to the Variable Speed Drive are strictly observed as well as all limitations therein fully respected.
  • Page 7 AF-600FP BACnet 1.1.6 Abbreviations Acyclical Control Interval Process Data Application Orientated Controller Parameter Characteristics Building Management System Parameter-Characteristics-Value Controller Area Network Protocol Data Unit Control Word Programmable Logic Control EEPROM Electrical Erasable Programmable Read Only Memory Parameter Number Electronic Industries Association: Specifies of the EIA Standard RS 485-A Parameter Value Electromagnetic Compatibility Request/Response Characteristics...
  • Page 8: Safety

    In no event shall GE be liable for direct, indirect, special, incidental, or consequential damages arising out of the use, or the inability to use information contained in this manual, even if advised of the possibility of such damages. In particular, GE is not responsible for any costs, including but not limited to those incurred as a result of lost profits or revenue, loss or damage of equipment, loss of computer programs, loss of data, the costs to substitute these, or any claims by third parties.
  • Page 9 AF-600FP BACnet 2.1.2 Safety Precautions The voltage of the drive is dangerous whenever connected to mains. Incorrect installation of the motor, drive or network may cause damage to the equipment, serious personal injury or death. Consequently, the instructions in this manual, as well as national and local rules and safety regulations, must be complied with.
  • Page 10: How To Install

    AF-600FP BACnet 3 How to Install 3.1 The BACnet Option 3.1.1 Installation of the Option Items required to install a network option in the drive: The network option Network option adaptor frame for the drive. This frame is deeper than the standard frame, to allow space for the network option beneath. Cable holders...
  • Page 11 AF-600FP BACnet Instructions: Remove the Keypad from the drive. Remove the frame located beneath and discard. Push the option into place. Two positions are possible, with cable terminal facing either up or down. The cable up position is often most suitable when several frequency converters are installed side by side in a rack, as this position permits shorter cable lengths.
  • Page 12 T-connection is used instead of permissible cable length and maximum number of nodes/Drivess with 1, 2, 3 and 4 bus segments. Drop cable connection (i.e. T-connection) beyond the cable lengths indicated is not recommended, due to the increased risk of reflection occurring. Instead, GE recommends direct connection of the drive.
  • Page 13 AF-600FP BACnet 3.1.3 Network Termination Connecting the Bus Line Connect the BACnet Option Card to the network line via terminals 62, 63 and 66. Terminal 62 is Marked Red and Terminal 62 is marked Green. These two are the RS485 lines. Terminal 66 the signal Ground for the RS485 Transmitter. Maximum Cable Lengths Maximum total network cable length: 4000Feet ~ 1200Meter...
  • Page 14: System Specifications

    AF-600FP BACnet 3.1.4 Cable Routing The BACnet communication cable must be kept away from motor cables to avoid coupling of high frequency noise from one cable to the other. Normally a distance of 200 mm is sufficient, but maintaining the greatest possible distance between cables is generally recommended, especially where cables run in parallel over long distances.
  • Page 15 AF-600FP BACnet...
  • Page 16: How To Configure The System

    AF-600FP BACnet 4 How to Configure the System 4.1 Configuring BACnet 4.1.1 Initialization Procedure The Initialization Procedure is explained by the flow chart given below: Initialization Parameter General Settings Name Parameter Number Default Value Setting for BACnet Control Site O-01 Digital and control word Digital and control word Control word source...
  • Page 17: Bibbs

    AF-600FP BACnet Digital/Bus settings Name Parameter Number Default Value Setting for BACnet Coasting Select O-50 Logic-or Logic-or Quick Stop Select O-51 Logic-or Logic-or DC Brake Select O-52 Logic-or Logic-or Start Select O-53 Logic-or Logic-or Reversing Select O-54 Logic-or Logic-or Set-up Select O-55 Logic-or Logic-or...
  • Page 18: Example Of A Simple Setup Of Bacnet

    AF-600FP BACnet 4.3 Example of a simple setup of BACnet This example shows the necessary steps to set up the AF-600 FP BACnet interface with the following system requirements: • MS/TP running at 38.400 Baud • MAC address 20 for the AF-600 FP •...
  • Page 19 AF-600FP BACnet...
  • Page 20: How To Control The Drive

    AF-600FP BACnet 5 How to Control the Drive 5.1.1 Reference Handling Select the drive configuration mode in par. H-40 Configuration Mode. [0] Open Loop [3] Closed Loop Open Loop For open loop operation, the reference represents the desired output speed of the drive. The speed reference value: Closed Loop For closed loop operation, the reference represents the setpoint.
  • Page 21: Network Drive Control Inputs And -Outputs

    AF-600FP BACnet 5.2 Network Drive Control Inputs and -Outputs 5.2.1 Analog Input- and Output Objects Control the drive from the BACnet network using 'objects'. The various types of 'objects' and their descriptions are shown in the following tables. Alarm Changeable Non volatile ram Triggers Bus time- Object ID...
  • Page 22 AF-600FP BACnet Alarm Changeable Non volatile ram AF-600 FPPa- Triggers Bus Time- Object ID Object Name Read/Write notifi- Description Store rameter cation AV:0 Reference AV:1 Speed Act. Value AV:2 Bus Feedback1 O-94 AV:3 Bus Feedback2 O-95 AV:4 Bus Feedback3 O-96 AV:5 Motor Voltage Read...
  • Page 23 AF-600FP BACnet Alarm Changeable Non volatile ram AF-600 FP Pa- Triggers Bus Time- Object ID Object Name Read/Write notifi- Description Store rameter cation AV:31 Ext. 2 Setpoint AF-600 FP XC-35 AV:32 Ext. 2 reference [Unit] AF-600 FP XC-37 AV:33 Ext. 2 Feedback [Unit] AF-600 FP XC-38 AV:34...
  • Page 24 AF-600FP BACnet Alarm Changeable De- Non volatile ram Triggers Bus Time- Object Id Object Name Read/Write Drive Par. notifi- scription Store cation BO:0 Digital output 27 E-90/00 BO:1 Digital output 29 E-90/01 BO:2 GPIO Output Term X30/6 E-90/02 BO:3 GPIO Output Term X30/7 E-90/03 BO:4 Relay 1 output...
  • Page 25 AF-600FP BACnet Alarm Changeable De- Non volatile ram Triggers Bus Time- Object Id Object Name Read/Write Drive Par. notifi- scription Store cation Reserved output BO:30 E-90/30 E-90/30* Reserved output BO:31 E-90/31 E-90/31* Reserved output BO:36 E-90/26 E-90/26* Reserved output BO:37 E-90/27 E-90/27* Reserved output...
  • Page 26 AF-600FP BACnet Alarm Changeable De- Non volatile ram Triggers Bus Object ID Object Name Read / Write Drive Par. notifi- scription Store Timeout cation BV:40 Brake check DR-90/00 BV:41 Pwr. Card Temp DR-90/01 BV:42 Earth Fault DR-90/02 BV:43 Ctrl.Card Temp DR-90/03 BV:44 Ctrl.
  • Page 27 AF-600FP BACnet Alarm Changeable De- Non volatile ram Triggers Bus Object ID Object Name Read / Write Drive Par. notifi- scription Store Timeout cation BV:80 Broken Belt DR-91/08 BV:81 Discharge High DR-91/08 BV:82 Start fault DR-91/10 BV:83 Speed limit DR-91/11 BV:84 State fault DR-91/12 DR-91/12...
  • Page 28 AF-600FP BACnet Alarm Changeable De- Non volatile ram Triggers Bus Object ID Object Name Read / Write Drive Par. notifi- scription Store Timeout cation BV:121 10V low DR-92/17 BV:122 Brake Overload DR-92/18 BV:123 Brake Resistor DR-92/19 BV:124 Brake IGBT DR-92/20 BV:125 Speed Limit DR-92/21...
  • Page 29 AF-600FP BACnet Alarm Changeable De- Non volatile ram Triggers Bus Object ID Object Name Read / Write Drive Par. notifi- scription Store Timeout cation BV:156 Reserved, DR-93/20 DR-93/20 BV:157 Reserved, DR-93/21 DR-93/21 BV:158 Reserved, DR-93/22 DR-93/22 BV:159 Reserved, DR-93/23 DR-93/23 BV:160 Reserved, DR-93/24 DR-93/24...
  • Page 30: Drive Feedback To Network

    AF-600FP BACnet 5.2.3 Multi-state Input- and Output Objects Multi-state Variable Changeable De- Non volatile ram Alarm notifi- Triggers Bus Object Id Object Name Read/Write Drive Par. scription Store cation Timeout MSV:0 LC Controller State DR-38 MSV:1 Setup selection Bit13&14 in CTW Mailbox variable Changeable De- Non volatile ram...
  • Page 31 AF-600FP BACnet...
  • Page 32 AF-600FP BACnet...
  • Page 33 AF-600FP BACnet...
  • Page 34: Parameters

    AF-600FP BACnet 6 Parameters 6.1 Parameter Overview 6.1.1 Parameter List Conversion in- Data Title Default value Range type O-01 Control Site Dig. and ctrl. word [0] [0 - 2] O-02 Control Source Drive RS485 [0] [0 - 4] O-03 Control Timeout Time 0.1 - 18000 O-04 Control Timeout Function...
  • Page 35: Parameter Description

    AF-600FP BACnet 6.2 Parameter Description 6.2.1 O-## Options / Comms Parameter group for configuring communications and options. O-01 Control Site Option: Function: The setting in this parameter overrides the settings in par. O-50 Coasting Select to par. O-56 Preset Ref- erence Select.
  • Page 36 AF-600FP BACnet O-04 Control Word Timeout Function Option: Function: Select the time-out function. The time-out function is activated when the control word fails to be updated within the time period specified in par. O-03 Control Word Timeout Time. Choice [20] only appears after setting the N2 protocol.
  • Page 37: Protocol

    AF-600FP BACnet O-10 Control Word Profile Option: Function: Select the interpretation of the control and status words corresponding to the installed network. Only the selections valid for the network installed in slot A will be visible in the Keypad display. [0] * Drive Profile PROFIdrive profile...
  • Page 38: Coasting Select

    AF-600FP BACnet O-33 Drive Port Parity Option: Function: Parity and Stop Bits for the protocol par. O-30 Protocol using the Drive Port. For some of the protocols, not all options will be visible. Default depends on the protocol selected. [0] * Even Parity, 1 Stop Bit Odd Parity, 1 Stop Bit No Parity, 1 Stop Bit...
  • Page 39 AF-600FP BACnet O-53 Start Select Option: Function: Select control of the drive start function via the terminals (digital input) and/or via the network. Digit Input Activates Start command via a digital input. Activates Start command via the serial communication port or network option module. Logic AND Activates Start command via the network/serial communication port, AND additionally via one of the digital inputs.
  • Page 40: Bacnet Device Instance

    AF-600FP BACnet O-56 Preset Reference Select Option: Function: Select control of the drive Preset Reference selection via the terminals (digital input) and/or via the net- work. Digit Input Activates Preset Reference selection via a digital input. Activates Preset Reference selection via the serial communication port or network option module. Logic AND Activates Preset Reference selection via the network/serial communication port, AND additionally via one of the digital inputs.
  • Page 41 AF-600FP BACnet BN-75 Initialization Password Range: Function: [0 - 0 ] Enter the password needed for execution of Drive Re-initialisation from BACnet. This parameter is active only when par. O-30 Protocol is set to [9] Drive Option.
  • Page 42: Troubleshooting

    AF-600FP BACnet 7 Troubleshooting 7.1 Alarm-, Warning and Extended Status Word 7.1.1 Alarm and warning messages General There is a clear distinction between alarms and warnings. In the event of an alarm, the drive will enter a fault condition. After the cause for the alarm has been cleared, the master must acknowledge the alarm message in order to start operation of the drive again.
  • Page 43: Alarm Words

    AF-600FP BACnet 7.1.2 Alarm words Alarm word, par. DR-90 Alarm Word Alarm word 2, par. DR-91 Alarm Word 2 Alarm Word Alarm Word 2 (Hex) (par. DR-90 Alarm Word) (Hex) (par. DR-91 Alarm Word 2) 00000001 Brake check 00000001 Service Trip, read / Write 00000002 Power card over temperature 00000002...
  • Page 44: Warning Words

    AF-600FP BACnet 7.1.3 Warning words Warning word , par. DR-92 Warning Word Warning word 2, par. DR-93 Warning Word 2 Warning Word Warning Word 2 (Hex) (par. DR-92 Warning Word) (Hex) (par. DR-93 Warning Word 2) 00000001 Brake check 00000001 Start Delayed 00000002 Power card over temperature...
  • Page 45: Extended Status Words

    AF-600FP BACnet 7.1.4 Extended status words Extended status word, par. DR-94 Ext. Status Word Extended status word 2, par. DR-95 Ext. Status Word 2 Extended Status Word Extended Status Word 2 (par. DR-95 Ext. (Hex) (par. DR-94 Ext. Status Word) (Hex) Status Word 2) 00000001...
  • Page 46: Led Status

    AF-600FP BACnet 7.2 LED Status Check the LEDs. The two bi-colour LEDs on the BACnet card indicate the status of BACnet communication. LED 1: Net Status Phases Status Bi-colour LED Power On. Hardware Not OK Self test Green ▂█▂█▂█▂█▂█ Running Module OK Green ██████████...
  • Page 47 Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the GE company. AF-650 GP and AF-600 FP are trademarks of the General Electric Company.